HomeMy WebLinkAboutE6.02 - ONE LINE DIAGRAM - NEW WORKCODED NOTES 1. PROVIDE CONTROL TO ALLOW THE TRIP UNIT TO BE PLACED IN MAINTENANCE MODE TO REDUCE POTENTIAL ARC FLASH ENERGY. 2. 84 CIRCUIT PANELBOARD. 3. ELEVATOR SHUNT TRIP SAFETY SWITCH. TRANSFORMER SCHEDULE NOTES: SOME ENTRIES MAY NOT BE USED. REFER TO ONE LINE DIAGRAM AND FLOOR PLANS FOR LOCATIONS XTMR NO.KVA VOLTAGE PRIMARY SECONDARY OCP FEEDER OCP FEEDER T1 15 480 DELTA // 208/120 Y 40/3 50/3 #8 AWG T2 30 480 DELTA // 208/120 Y 70/3 100/3 #6 AWG T3 45 480 DELTA // 208/120 Y 125/3 175/3 #4 AWG T4 75 480 DELTA // 208/120 Y 175/3 250/3 #2 AWG T5 112.5 480 DELTA // 208/120 Y 300/3 400/3 #1/0 AWG T6 150 480 DELTA // 208/120 Y 350/3 500/3 #2/0 AWG T7 225 480 DELTA // 208/120 Y 600/3 800/3 #3/0 AWG T8 300 480 DELTA // 208/120 Y 700/3 1000/3 #3/0 AWG T9 65 480 DELTA // 240/120 Y 175/3 3 5 8 OR 3A 9 OR 4A 13 OR 8A 62 14 OR 9A 17 OR 12A 18 OR 13A 63 OR 70A 64 OR 71A 65 OR 72A 66 OR 73A 67 OR 74A 68 OR 75A 69 OR 76A GROUNDING ELECTRODE (COPPER ONLY) 250/3 #2 AWG9 OR 4A 65 OR 72A DIESEL EMERGENCY GENERATOR 480/277 V, 3 PHASE, 4 W, 300 KW 2 2 2 2 22 2 1 ONE LINE N.T.S. WIRING DIAGRAM 1 3 19 400/3 27A 60/3 18 G #4 AWG 19A PANEL EP ATS #2 400/4 POLE ATS #1 60/4 POLE 60/3400/3 MRI 44 MCA RTU9 3R 60/60/3 400 AMP, 480/277 V, 3 PHASE, 4 W STANDBY POWER PANELBOARD EDP 2 350/3 28A 6 60/3 5 9A 400/3 27A 19A 19A 27A #6 N G 1600 AMP, 480/277 V, 3 PHASE, 4 W MAIN SWITCHBOARD MSB1 7 6 1 M 34A N G #1/0 SPD 60/3 62 100/3 40A PANEL L1 100/3 40A PANEL L2 8 100/3 9 30/3 14 80/3 15 17 2 700/3 2 225/3 PANEL P1 23A 800/3 800 AMP, 208/120 V, 3 PHASE, 4 W DISTRIBUTION PANELBOARD DP1 17 MCA RTU1 3R 30/20/3 UTILITY CO. TRANSFORMER UTILITY CO. METER MOUNTED ON POST 1 SPD 60/3 62 59A 13A 1600/3 GF #3/0 12 13 150/3 5 4 225/3 PANEL 225/3 PANEL 3 225/3 PANEL P2 23A MP1 MP2 1 30/3 SPARE 21 FUTURE T6 150 KVA 480 V, 3 ∅ - 208/120 V,3 ∅ FUTURE T7 225 KVA 480 V, 3 ∅ - 208/120 V,3 ∅ 23A TRIPLE SWITCH NEC 700 LIFE SAFETY NEC 702 OPTIONAL 10 30/3 11 20/3 8.5 MCA RTU3 3R 30/20/3 3R 100/80/3 2 2 4 225/3 7 50/3 VACUUM PUMP VP1 (2)5 HP M 60/50/3 4 5 100/3 16 22 500 AMP, 208/120 V, 3 PHASE, 4 W STANDBY POWER PANELBOARD SDP 1 200/3 500/3 PANEL SP1 2 200/3 PANEL SP2 22A 3 100/3 PANEL SP3 19A22A 6 100/3 XRAY1 5 175/3 9 100/100/3 XRAY2 4 175/3 9 100/100/3 65 65 T9T9 SPARE MRI CHILLER 18 17 30/3 1200 AMP, 208/120 V, 3 PHASE, 4 W EXISTING DISTRIBUTION PANELBOARD MDP 6 5 1 N G 45/3 30/3 7 200/3 8 200/3 13 30/3 14 200/3 SPACE 16 SPACE 2 11 200/3 12 30/3 4 3 30/3 30/3 199 225/3 10 225/3 45/3 15 1200/3 EXISTING PANEL M1 EXISTING PANEL M2 LIFT STATION EXISTING SPACE 45/3 45/3 T8 300 KVA 480 V, 3 ∅ - 208/120 V,3 ∅ 3R 60A 225/3 SPARESPARESPARESPARESPARESPARESPARESPARESPARESPARE 400/3 400/3 20/3 8.5 MCA RTU7 3R 30/20/3 2 125/3 118 MCA RTU8 3R 200/125/3 8 13 MCA RTU2 3R 30/20/3 2 20/3 7.6 MCA RTU4 3R 30/20/3 2 20/3 8.5 MCA RTU5 3R 30/20/3 2 20/3 8.5 MCA RTU6 3R 30/20/3 2 3 600/3 12A PANEL P3 22A EXISTING CT CASSETTE 60/3 23 24 25 60/3 100/3 SPARE SPARE SPARE TEMPORARY GENERATOR 19A 20 200/3 10 200/200/3 HUMIDIFER 3 20/3 12 A 1 30/20/3 SPARE 100/3 PANEL P4 22A FUTURE CT 7 200/3 50 HP ELEVATOR SPARE 3R 800/600/3 3R 1200/1200/3 FEEDER FROM UTILITY TRANSFORMER DURING ENABLING PHASE. SHALL BE FED FROM MSB1 DURING PHASE 2 PROJECT NUMBER: CHECKED BY: DESIGNED BY: 1650 WATERMARK DRIVE COLUMBUS, OHIO 43215 SUITE 200 DRAWN BY: © 2021 M+A Architects PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: 2021-0012 20297 ONE LINE DIAGRAM -NEW WORK 04 MARCH 2022 E6.02Stanley J. Kmonk Dustin J. Ruby Garrett W. Strauss MEDVET CARMEL -ANIMAL HOSPITAL650 MAYFLOWER PARK DRIVE|CARMEL, IN 46032RENOVATION AND ADDITION07/13/22