HomeMy WebLinkAboutF0.01 - FIRE PROTECTION INDEX SHEETGENERAL NOTES -FIRE PROTECTION (APPLY TO ALL FIRE PROTECTION DRAWINGS) 1. THE SYSTEM DESIGN IS BASED ON THE LATEST EDITION OF THE INDIANA BUILDING CODE INCLUDING ALL AMENDMENTS THROUGH THE DATE OF DRAWING ISSUE. 2. THE SPRINKLER DRAWINGS ARE SCHEMATIC IN NATURE AND ARE INTENDED TO BE USED AS A GUIDELINE. THE CONTRACTOR WILL BE RESPONSIBLE FOR LOCATING AND COORDINATING SPRINKLER MAINS AND BRANCHES, THE EXACT NUMBER OF SPRINKLER HEADS AND EXACT PIPE SIZE BASED UPON THE HYDRAULIC CALCULATIONS TO MEET ALL GUIDELINES SET BY THE OWNER'S REQUIREMENTS, BUILDING CODES AND THE AUTHORITY HAVING JURISDICTION. 3. AUTOMATIC SPRINKLER PROTECTION FOR ALL AREAS OF THIS CONTRACT WILL BE PROVIDED BY THE FIRE PROTECTION CONTRACTOR. ALL AREAS ARE TO BE FULLY SPRINKLED. 4. PROVIDE AIR VENTS, DRAIN VALVES AND PIPING TO ALLOW COMPLETE DRAINAGE OF ALL FIRE PROTECTION SYSTEMS. 5. THE CONTRACTOR SHALL COORDINATE THE WORK WITH THE ARCHITECTURAL REFLECTED CEILING PLANS, ROOM FINISH SCHEDULES, STRUCTURAL DRAWINGS, MECHANICAL DRAWINGS AND ELECTRICAL DRAWINGS. 6. PROVIDE SPRINKLER HEADS & PIPING THROUGHOUT THE WORK AREA AS PER NFPA 13. 7. HAZARD CLASSIFICATIONS: A. LIGHT HAZARD: a. OFFICES, ASSEMBLY AREAS, PATIENT ROOMS, PROCEDURE ROOMS, OPERATING ROOMS, WAITING ROOMS. b. WET PIPE DENSITY = 0.10 GPM PER SQUARE FOOT. MAXIMUM AREA OF SPRINKLER DEMAND IS 1500 SQUARE FEET, MAXIMUM OF 225 SQUARE FEET SPRINKLER SPACING. 1/2" ORIFICE SPRINKLER. c. ORDINARY TEMP. HEADS, 165 DEG. F. 100 GPM HOSE DEMAND. B. ORDINARY HAZARD -GROUP 1: a. MECHANICAL ROOMS, ELECTRICAL ROOMS, STORAGE ROOMS. b. WET PIPE DENSITY = 0.15 GPM PER SQUARE FOOT. MAXIMUM AREA OF SPRINKLER DEMAND IS 1500 SQUARE FEET, MAXIMUM OF 130 SQUARE FEET SPRINKLER SPACING. c. WHEN USING QUICK RESPONSE SPRINKLER HEADS, NO REDUCTION IN SPRINKLER. AREA SHALL BE MADE. 8. THE FIRE PROTECTION CONTRACTOR WILL BE RESPONSIBLE FOR PROVIDING AN UP TO DATE FLOW TEST AT THE HYDRANT CLOSEST TO THIS BUILDING ONCE THE NEW WATER SERVICE HAS BEEN INSTALLED (ON THE MAIN SERVING THIS BUILDING). A. DESIGN FLOW TEST DATA: DATE: 02/01/2022 B. LOCATION: HYDRANTS ON MAYFLOWER PARK DRIVE C. STATIC = 85 PSI RESIDUAL = 80 PSI FLOW = 1121 GPM 9. THE FIRE PROTECTION SYSTEM PIPING SHALL BE SIZED BY HYDRAULIC CALCULATIONS WITHIN THE LIMITS OF THE MAXIMUM ALLOWABLE SPRINKLER DEMAND FLOW AND AVAILABLE PRESSURE LISTED. THIS MEANS LARGER THAN NORMAL PIPE SIZES WILL BE REQUIRED TO MINIMIZE FRICTION LOSS IN THE PIPING SYSTEM AND REDUCE THE PRESSURE REQUIREMENT. A. ALL HYDRAULIC CALCULATION REFERENCE POINTS/NODES SHALL BE IDENTIFIED ON PLANS. B. NO TWO REFERENCE POINTS/NODES SHALL BE USED TWICE. PRESSURE REQUIREMENTS SHALL INCLUDE AN 8 PSI CUSHION. PS DC DC M T EXISTING SPRINKLER HEAD EXISTING SPRINKLER HEAD SPRINKLER HEAD WITH DEFLECTOR EXTENDED THROW SIDEWALL NON-FREEZE SIDEWALL NON-FREEZE PENDANT INSPECTOR'S TEST CONNECTION FIRE DEPARTMENT VALVE DRY PIPE ALARM VALVE ELECTRICALLY SUPERVISED VALVE WET PIPE ALARM VALVE PRESSURE REDUCING VALVE WALL INDICATOR VALVE SPRINKLER HEADS FIRE PROTECTION SYMBOLS LIST NOTE: ALL SYMBOLS NOT NECESSARILY USED FIRE HOSE/EXTINGUISHER CABINET CONNECT TO EXISTING WITH BYPASS METER DETECTOR CHECK VALVE DETECTOR CHECK VALVE FIRE RATED OR WATER TIGHT SIGHT GLASS ROOF HYDRANT TEST CONNECTION WALL TYPE SIAMESE CONNECTION ELECTRIC ALARM BELL WATER MOTOR GONG FIRE VALVE CABINET FIRE HOSE RACK PIPE SLEEVE UNION GAUGE TO BE REMOVED TO REMAIN SIDEWALL RECESSED FLUSH/CONCEALED PENDANT UPRIGHT FIRE HOSE CABINET FIRE EXTINGUISHER CABINET FIRE EXTINGUISHER EXISTING TO BE ABANDONED EXISTING TO BE REMOVED EXISTING TO REMAIN COMB. SPRINKLER & STANDPIPE SPRINKLER PIPE COMB. FIRE & WATER SERVICE STANDPIPE DRY PIPE DELUGE DRAIN ANTIFREEZE FIRE MAIN GLOBE VALVE SP SPECIALTIES DP DL D S SPR PRESSURE SWITCH STRAINER FLOOR STAND VALVE FLOW SWITCH DELUGE VALVE PIPING AF FW F GATE VALVE CHECK VALVE R E VALVES OC FOR COORDINATION OR REFERENCE DENOTES ITEM PROVIDED BY ANOTHER CONTRACTOR, SHOWN FE FEC FHC FHEC FHR FVC N N MISCELLANEOUS VALVE IN DROP VALVE IN RISE GENERAL F FDDELECTRIC ALARM BELL SIAMESE SPR PIPE FULL SIZE TO NEAREST ACCEPTABLE DRAIN WITH APPROVED AIR GAP RETARD CHAMBER ELECTRIC SPRINKLER ALARM SWITCH WET PIPE ALARM VALVE MAIN DRAIN VALVE PIPE FULL SIZE TO NEAREST ACCEPTABLE DRAIN WITH APPROVED AIR GAPT CENTER IN TILE CENTER IN PARTIAL TILE DIFF., LIGHT, GRILLE, ETC. CENTER IN ONE 12 X 12 SECTION CENTER IN 24 X 24 SECTION CENTER IN 24 X 24 OR 24 X 48 SECTION CENTER IN TILE GENERAL NOTE: NO. 2 TYPICAL FOR ANY STYLE OF CEILING TILE GENERAL NOTES: (APPLY TO ALL SHEETS) 1. SEE SKETCHES ABOVE FOR TYPICAL SPRINKLER HEAD LOCATION FOR VARIOUS CEILING TILE CONFIGURATIONS. COORDINATE WITH ARCHITECTURAL FINISH SCHEDULES AND DETAILS. 2. THE FIRE PROTECTION CONTRACTOR SHALL REFER TO THE REFLECTED CEILING PLAN FOR COORDINATION OF THE SPRINKLER LOCATIONS. 1 3 5 2 4 6 PROJECT NUMBER: CHECKED BY: DESIGNED BY: 1650 WATERMARK DRIVE COLUMBUS, OHIO 43215 SUITE 200 DRAWN BY: © 2021 M+A Architects PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: 2021-0012 20297 FIRE PROTECTION INDEX SHEET 04 MARCH 2022 F0.01Eric Stephens Nathan Criss Nathan Criss MEDVET INDIANAPOLIS -ANIMAL HOSPITAL9650 MAYFLOWER PARK DRIVE | CARMEL, IN 46032RENOVATION AND ADDITIONFIRE PROTECTION SHEET INDEX SHEET NUMBER SHEET NAME F0.01 FIRE PROTECTION INDEX SHEET F2.01 FIRST FLOOR FIRE PROTECTION NEW WORK F2.02 SECOND FLOOR FIRE PROTECTION NEW WORK DETAIL N.T.S. 1 SPRINKLER - WET PIPE RISER PIPING DETAIL N.T.S.2 SPRINKLER LOCATIONS IN VARIOUS CEILING TILE TYPES 07/13/22