H5.02 - HVAC SCHEDULES
0.3328 ESVTB22 TB26 16 30 TB25 TB24 14 12 TB23 10 29 33 29 VARIABLE AND CONSTANT AIR VOLUME TERMINAL BOXES WITH ELECTRIC HEATING COILS ELECTRIC REHEAT TERMINAL BOX SCHEDULE TB21 6 ESV UNIT DATA TAG NECK SIZEMODEL 0.326 REMARKS UNLESS OTHERWISE NOTED EQUIPMENT BASED ON DAIKIN *OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT* 301-600 1,801-3,200 1,501-1,800 901-1,500 601-900 80-300 SHEETMETAL PLANS: SIZE-MAX.CFM/MIN.CFM(-KW) UNIT-NUMBER CFM RANGE MAX. DISCH. N.C. LEVEL @ 2" ΔP MAX. S.P. DROP GENERAL COIL CAP. BASED ON 50% AIRFLOW. SEE PLANS FOR SPECIFIC CAPACITIES. 0.5 0.5 0.7 0.5 ESV ESV ESV ESV MAX KW E.A.T. °F L.A.T. °F STAGES UNIT DATA 2.0 55 100 SEE BELOW GENERAL COIL CAP. BASED ON 50% AIRFLOW. SEE PLANS FOR SPECIFIC CAPACITIES.4.0 55 100 GENERAL COIL CAP. BASED ON 50% AIRFLOW. SEE PLANS FOR SPECIFIC CAPACITIES.7.0 55 100 GENERAL COIL CAP. BASED ON 50% AIRFLOW. SEE PLANS FOR SPECIFIC CAPACITIES.10.0 55 100 GENERAL COIL CAP. BASED ON 50% AIRFLOW. SEE PLANS FOR SPECIFIC CAPACITIES.17.0 55 100 GENERAL COIL CAP. BASED ON 50% AIRFLOW. SEE PLANS FOR SPECIFIC CAPACITIES.25.0 55 100 NOTE: • PROVIDE TERMINAL BOX CONTROL PANELS WITH INTEGRAL DISCONNECT SWITCH • TERMINAL BOXES SHALL BE PROVIDED WITH ONE STAGE OF HEAT THROUGHT 1KW UNLESS NOTED OTHERWISE. • TERMINAL BEXES SERVING OPERATION ROOMS SHALL HAVE SCR HEATING CONTROLS. • TERMINAL BOXES SHALL BE PROVIDED WITH TWO STAGES OF HEAT 1.5KW THROUGH 2.0KW UNLESS NOTED OTHERWISE. • TERMINAL BOXES SHALL BE PROVIDED WITH THREE STAGES OF HEAT GREATER THAN 2KW UNLESS NOTED OTHERWISE. • TERMINAL BOXES SHALL BE 277V/1PH THROUGH 6KW, TERMINAL BEXES GREATER THAN 6KW WHALL BE 408/1PH SEE BELOW SEE BELOW SEE BELOW SEE BELOW SEE BELOW 0.1368 ESVTRE2 16 33 14 12 ESV 10 ESV 30 36 33 VARIABLE AND CONSTANT AIR VOLUME COOLING ONLY TERMINAL BOXES RETURN/EXHAUST TERMINAL BOX SCHEDULE TRE1 6ESV UNIT DATA TAG NECK SIZEMODEL 0.133 REMARKS UNLESS OTHERWISE NOTED EQUIPMENT BASED ON DAIKIN *OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT* 301-600 1,801-3,200 1,501-1,800 901-1,500 601-900 80-300 SHEETMETAL PLANS: SIZE-MAX.CFM/MIN.CFM UNIT-NUMBER CFM RANGE MAX. DISCH. N.C. LEVEL @ 2" ΔP MAX. S.P. DROP 0.1 0.1 0.1 0.1 ESV ESV TRE3 TRE4 TRE5 TRE6 MODEL LOCATIONTAG A.P.D. IN. W.G. UNIT DATA AIR DATA MOTOR DATA REMARKS E. REDUCED VOLTAGE STARTER F. TWO SPEED STARTERS CODED NOTES: A. DISCONNECT SWITCH B. CONTROL PANEL WITH INTEGRAL DISCONNECT SWITCH C. CONTROL PANEL D. LINE VOLTAGE PANEL L. WALL SWITCH G. VARIABLE FREQUENCY DRIVE H. EMERGENCY POWER J. PLUG-IN UNIT K. THERMOSTAT DIV 26 INDICATED COMPONENTS PROVIDED BY DIV 23 TYPE KW CFM E.A.T. °F L.A.T. °F HP VOLTS PHASE SEE PLANSEWH1 AWH WALL HEATER 4.8 - - -- 208 1 A K - RECESSED MOUNTED, UNIT MOUNTED THERMOSTATFREE DISCH. ELECTRIC WALL HEATER SCHEDULE UNLESS OTHERWISE NOTED EQUIPMENT BASED ON QMARK *OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT* MODEL LOCATION TAG A.P.D. IN. W.G. UNIT DATA AIR DATA HEATING ELEMENTS MOTOR DATA ELECTRIC UNIT HEATER SCHEDULE UNLESS OTHERWISE NOTED EQUIPMENT BASED ON QMARK *OWNER FURNISHED, CONTRACTOR INSTALLED EQUIPMENT* REMARKS E. REDUCED VOLTAGE STARTER F. TWO SPEED STARTERS CODED NOTES: A. DISCONNECT SWITCH B. CONTROL PANEL WITH INTEGRAL DISCONNECT SWITCH C. CONTROL PANEL D. LINE VOLTAGE PANEL L. WALL SWITCH G. VARIABLE FREQUENCY DRIVE H. EMERGENCY POWER J. PLUG-IN UNIT K. THERMOSTAT DIV 26 INDICATED COMPONENTS PROVIDED BY DIV 23 TYPE MBH CFM E.A.T. °F L.A.T. °F HP RPM VOLTS PHASE SEE PLANUH1 MUH0381 HORIZ. ELECTRIC 10 350 - -1/100 1,600 277 1 B A- TOTAL KW VOLTS NO.PHASE 1 277 3 1 PROJECT NUMBER: CHECKED BY: DESIGNED BY: 1650 WATERMARK DRIVE COLUMBUS, OHIO 43215 SUITE 200 DRAWN BY: © 2021 M+A Architects PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: 2021-0012 20297 HVAC SCHEDULES 04 MARCH 2022 H5.02Eric Stephens Caleb Ledford Ann Guan MEDVET INDIANAPOLIS -ANIMAL HOSPITAL9650 MAYFLOWER PARK DRIVE | CARMEL, IN 46032RENOVATION AND ADDITION07/13/22