Loading...
HomeMy WebLinkAboutH6.01 - HVAC DETAILSBACKDRAFT DAMPER IN SHEET METAL SLEEVE CAULK AROUND PERIMETER COORDINATE EXACT LOCATION AND ELEVATION WITH ARCHITECT. BRANCH DUCT (TYP.) VOLUME DAMPER (TYP.)AIRFLOWPROVIDE 18" LONG ORANGE MARKER TAPE ON EACH VOLUME DAMPER HANDLE TO IDENTIFY LOCATION SINGLE LINE AIR FLOW AIR FLOW AIR FLOW LOW VELOCITY SUPPLY LOW VELOCITY SUPPLY (CONICAL SPIN IN) LOW VELOCITY RETURN/EXHAUST MAIN DUCT (TYP.)45.00°45.00°AIRFLOWAIRFLOWFLEXIBLE CONNECTION (MIN. 3 FT., MAX. 4 FT.) SECURE FLEXIBLE DUCT TO DUCT COLLARS WITH DRAWBANDS. PROVIDE ADDITIONAL DRAWBANDS AND SEAL FLEX. OUTER JACKET TO DUCT COLLARS NOTES: 1. THIS CONNECTION DETAIL APPLIES WHEN DUCT WIDTH IS LESS THAN 70% OF THE AIR DEVICE WIDTH. 2. CONNECTION MAY ALSO BE ON THE SHORT END. SAME REQUIREMENTS APPLY. SHEETMETAL PLENUM FULL SIZE OF GRILLE SUPPORT FROM STRUCTURE LAY-IN CEILING SEE PLANS FOR SIZES IF DUCT DIMENSION IS AT LEAST 6" LESS THAN AIR DEVICE DIMENSION, THIS SHALL BE 3". IF NOT, THIS SHALL BE 1" MINIMUM. PLENUM SHALL BE SIZE OF AIR DEVICE NECK FACE OF AIR DEVICE *** 45.00° RETURN / EXHAUST GRILLE LAY-IN CEILING **12" MIN. (REFER TO ROOF PLAN)*VARIES SEE ARCHITECTURAL ROOF PLAN DUCTWORK ISOLATION SPRINGS WEATHER SEAL***EXPANDING POLYURETHANE FOAM INSUL. AROUND PERIM. OF DUCT IN METAL DECK PLANE SEE DETAIL TO RIGHT HURRICANE CLIPS WHERE REQUIRED ISOLATION RAIL PROVIDE VERTICAL AND LATERAL RESTRAINTS FOR MOUNTING ISOLATION RAIL TO STEEL SUPPORT ROOFTOP AIR HANDLING UNIT FLEXIBLE DUCT CONNECTION ROOFTOP AIR HANDLING UNIT GASKET (SUPPLIED WITH CURB) CONTINUOUS VIBRATION ISOLATOR WITH WEATHERTIGHT SEAL PRE-FABRICATED ROOF CURB BY HVAC CONTRACTOR ROOFING MATERIAL METAL DECK AND STRUCTURE STEEL CHANNEL FASTENED TO ROOF FRAMING INDOOR DUCT INSULATION IN-FILL BETWEEN EQUIPMENT CURB AND DUCTWORK ALL SIDES WITH TWO LAYERS (STAGGERED) OF 5/8" GYPSUM WALL BOARD STEAM GENERATOR 6" MINPREFERRED INSTALLATION INSTALLATION ONLY ALLOWED WHEN REQUIRED DUE TO INSUFFICIENT CLEARANCE ABOVE CEILING OPTIONAL INSTALLATION MOUNT TO WALL ABOVE CEILING STRAINER ISOLATION VALVE STEAM VAPOR HOSE SHALL BE SIZED AS INDICATED ON DRAWINGS, BUT NOT LESS THAN THE OUTLET SIZE ON THE GENERATOR. HOSE SHALL BE MAXIMUM 10' LONG. SLOPE DUCT TO (1) CENTRAL LOW POINT AND PROVIDE TRAPPED DRAIN PROVIDE STAINLESS DUCTWORK 1'-0" UPSTREAM AND 5'-0 DOWNSTREAM OF DISPERSION TUBES. DUCT DISPERSION TUBES STRUCTURE DISPERSION TUBES TRAPPED DRAIN CEILING SLOPE SLOPE VENT, EXTEND TO ABOVE ALL DRAINED EQUIPMENT CONDENSATE PUMP ¾" MIN. ½" MAKE-UP WATER SLOPE DUCT WIDTH DUCT HEIGHT16" MIN.SLOPE DUCT TO (1) CENTRAL LOW POINT AND PROVIDE TRAPPED DRAIN PROVIDE STAINLESS DUCTWORK 1'-0" UPSTREAM AND 5'-0 DOWNSTREAM OF DISPERSION TUBES. DUCT DISPERSION TUBES STRUCTURE DISPERSION TUBES DUCT WIDTH DUCT HEIGHTSLOPE MOUNT TO WALL ABOVE CEILING STRAINER ISOLATION VALVE ½" MAKE-UP WATER CEILING CONDENSATE PUMP ¾" MIN.16" MIN.STEAM GENERATOR TRAPPED DRAIN VENT, EXTEND TO ABOVE ALL DRAINED EQUIPMENT ROUTE TO DRAIN PER PLANS ROUTE TO DRAIN PER PLANS WATER FILTER SIMILAR TO AMERICAN PLUMBER MODEL W2015-PR STEAM VAPOR HOSE SHALL BE SIZED AS INDICATED ON DRAWINGS, BUT NOT LESS THAN THE OUTLET SIZE ON THE GENERATOR. HOSE SHALL BE MAXIMUM 10' LONG. WATER FILTER SIMILAR TO AMERICAN PLUMBER MODEL W2015-PR PROJECT NUMBER: CHECKED BY: DESIGNED BY: 1650 WATERMARK DRIVE COLUMBUS, OHIO 43215 SUITE 200 DRAWN BY: © 2021 M+A Architects PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: 2021-0012 20297 HVAC DETAILS 04 MARCH 2022 H6.01Eric Stephens Caleb Ledford Ann Guan MEDVET INDIANAPOLIS -ANIMAL HOSPITAL9650 MAYFLOWER PARK DRIVE | CARMEL, IN 46032RENOVATION AND ADDITIONDETAIL N.T.S. 1 WALL MOUNTED EXHAUST FAN DETAIL N.T.S. 2 TYPICAL DUCT CONNECTIONS DETAIL N.T.S.3 RETURN / EXHAUST GRILLE CONNECTION DETAIL N.T.S. 4 ROOFTOP AIR HANDLING EQUIPMENT DETAIL N.T.S.5 ELECTRIC DUCT MOUNTED HUMIDIFIER PIPING 07/13/22