HomeMy WebLinkAboutH6.02 - HVAC DETAILSSHEET METAL ELBOW REQUIRED 1D RADIUS MINIMUM SECURE FLEXIBLE DUCT TO DUCT COLLARS WITH SCREWS & DRAWBANDS. PROVIDE ADDITIONAL DRAWBANDS AND SEAL FLEX OUTER JACKET TO DUCT COLLARS VOLUME DAMPER LOCATION WHERE DAMPER WOULD BE INACCESSIBLE AT TAKE-OFF, PROVIDE WITH 3" EXTENDED SHAFT, HANDLE AND COLLAR INSULATED ROUND DUCT 18" LONG ORANGE MARKER TAPE ATTACHED TO DAMPER TO IDENTIFY LOCATION INSULATED NON-METALIC FLEXIBLE CONNECTION (MAX. 5 FT.)SUPPLY AIR DIFFUSER (LAY-IN FRAME) TO S.A. MAIN THERMAL INSULATION WITH VAPOR MEMBRANE STRUCTUREOC AIR COOLED CONDENSING UNIT VIBRATION ISOLATOR (BOLTED DOWN) COUNTER FLASHING ROOFING MATERIAL ROOF RAILS: COORDINATE WITH ROOF PITCH OC ROOF PLANTO ROOF PLAN)12" MIN. (REFERVARIES SEE ARCH.PRIMARY AIR FLOW AIR FLOW DISCHARGE PLAN VIEW CONTROLS LOW PRESSURE DUCT (TRANSITION AS REQUIRED) NOTE: 1. MAINTAIN MANUFACTURER'S MINIMUM CLEARANCES FOR ACCESS TO FILTER, CONTROLS AND ACTUATOR. INSULATED HIGH VELOCITY DUCT TRANSITION AS REQUIRED 18" SERVICE SPACE STRAIGHT LENGTH 3X DIA. MIN. 24V PWR FROM TRANSFORMER BY DIV. 23 TEMPERATURE CONTROL CONTRACTOR T TERMINAL BOX W/ REHEAT (TYP.) L H TO ZONECH SUPPLY ALL CONTROL WIRING BY DIV. 23 CONTRACTOR TERMINAL BOX VELOCITY CONTROL MULTIPOINT VELOCITY PICKUP TERMINAL BOX ACTUATOR WITH OR WITHOUT REHEAT COIL ATTACH DUCT TO TOP OF CURB WIRING BY OTHERS PRE-FABRICATED ROOF CURB ROOF INSULATION ROOFING MATERIAL METAL DECK AND STRUCTURE FRAMING BACKDRAFT DAMPER IN SHEET METAL SLEEVE THROUGH ROOF OC OC OC OCOC VARIES SEE ARCH ROOF PLAN 12" MIN. REFER TO ROOF PLAN 1¼" (TYP.) DAMPER SIZE DUCT AND ROOF OPENING OPENING THROUGH ROOF PLAN VIEW ROOFING MATERIAL ROOF INSULATION PIPE INSULATION PIPE INSULATION FRAMING ACRYLIC CLAD THERMOPLASTIC COVER, FASTENING SCREWS, GRADUATED STEP BOOTS WITH STAINLESS STEEL CLAMPS EXPANDING POLYURETHANE FOAM INSUL. AROUND PERIM. OF DUCT IN METAL DECK PLANE PRE-FABRICATED ROOF CURB OC OC OC OC OC METAL DECK AND STRUCTURE ( 15" )VARIES SEE ARCH.ROOF PLANCEILING PLENUM DUCT LINER RETURN GRILLE 4" MIN.( 2'-0" ) CFM DUCT SIZE 0-300 22/4 301-450 22/6 451-600 22/8 601-750 22/10 751-900 22/12 901-1050 22/14 LAY-IN CEILING SEE BELOW FOR SIZES PROJECT NUMBER: CHECKED BY: DESIGNED BY: 1650 WATERMARK DRIVE COLUMBUS, OHIO 43215 SUITE 200 DRAWN BY: © 2021 M+A Architects PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: PROJECT NUMBER: Sheet Name: DATE: SHEET NUMBER: REVISION: STATUS: 2021-0012 20297 HVAC DETAILS 04 MARCH 2022 H6.02Eric Stephens Caleb Ledford Ann Guan MEDVET INDIANAPOLIS -ANIMAL HOSPITAL9650 MAYFLOWER PARK DRIVE | CARMEL, IN 46032RENOVATION AND ADDITIONDETAIL N.T.S. 1 DIFFUSER MOUNTING (SUPPLY DUCT CLOSE TO CEILING) DETAIL N.T.S. 2 ROOF RAILS DETAIL N.T.S. 3 V.A.V. TERMINAL BOX DETAIL N.T.S.4 VARIABLE AIR VOLUME TERMINAL BOX W/ REHEAT DETAIL N.T.S. 5 ROOF MOUNTED EXHAUST FAN DETAIL N.T.S. 6 PIPE CURB DETAIL N.T.S.7 RETURN GRILLE WITH SOUND ELBOW CONNECTION 07/13/22