HomeMy WebLinkAboutE601 METER CENTER DETAILS AND PANEL SCHEDULESGRADE
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125 HP-2
225A
120/208V
3Ø
NEMA 3R
250KCMIL AL S.E.R. TO
HOUSE PANEL, SIZED FOR
VOLTAGE DROP PER
N.E.C.
3/225
MAIN
DISCONNECT
SERVICE
RATED
1600A
120/208V 3Ø
65KAIC
UNIT
PANEL
125A
120/208V
1Ø
NEMA 1
2/O AL S.E.R. TO UNIT PANEL,
SIZED FOR VOLTAGE DROP PER
N.E.C. (TYPICAL FOR ALL UNITS)
TO INCOMING METAL
WATER PIPE
(1)3/O CU
TO CONCRETE INCASED
ELECTRODE
(1)#4 CU
(4) 4" PVC SCH. 80 TO
TRANSFORMER BY E.C;
SECONDARY CONDUCTORS
BY DUKE ENERGY
GROUND BAR
SP-2
60A
120/208V
1Ø
NEMA1
3-#6CU, 1-#10 CU
IN 1" PVC SCH 80
CONDUIT TO
SUB-PANEL, SIZED
FOR VOLTAGE
DROP PER N.E.C.
EZML331225
EZMR315125X EZMR315125X EZMR316125X EZMR316125X EZMR315125X EZMR315125X
EZM31600GCBC
GROUND BAR
TO CONCRETE INCASED
ELECTRODE
(1)#4 CU
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
3/200
MAIN
DISCONNECT
SERVICE
RATED
1200A
120/208V 3Ø
65KAIC
UNIT
PANEL
125A
120/208V
1Ø
NEMA 1
2/O AL S.E.R. TO UNIT PANEL,
SIZED FOR VOLTAGE DROP PER
N.E.C. (TYPICAL FOR ALL UNITS)
GROUND BAR
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
1/125
GRADE
MAIN
DISCONNECT
SERVICE
RATED
1000A
120/208V 3Ø
65KAIC
UNIT
PANEL
125A
120/208V
1Ø
NEMA 1
2/O AL S.E.R. TO UNIT PANEL,
SIZED FOR VOLTAGE DROP PER
N.E.C. (TYPICAL FOR ALL UNITS)
TO INCOMING METAL
WATER PIPE
(1)3/O CU
TO CONCRETE INCASED
ELECTRODE
(1)#4 CU
GROUND BAR
HP-3A
125A
120/208V
1Ø
NEMA 3R
2/O AL S.E.R. TO HOUSE
PANEL, SIZED FOR
VOLTAGE DROP PER
N.E.C.
HP-3B
200A
120/208V
3Ø
NEMA 3R
250KCMIL AL S.E.R. TO
HOUSE PANEL, SIZED FOR
VOLTAGE DROP PER
N.E.C.
(3) 4" PVC SCH. 80 TO
TRANSFORMER BY E.C;
SECONDARY CONDUCTORS
BY DUKE ENERGY
(3) 4" PVC SCH. 80 TO
TRANSFORMER BY E.C;
SECONDARY CONDUCTORS
BY DUKE ENERGY
(1)3/O CU
EZML331225
EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125XEZM31000CBEZM31000CB
F.A.C.P.
FIRE
ALARM
CONTROL
PANEL
TS
DACT DEDICATED TELEPHONE LINE FOR
OUTPUT TO MONITORING SERVICE.
NOTE:
THE EQUIPMENT AND
INSTALLATION FOR DIFFERENT
DUAL MEANS OF TRANSMISSIONTO MONITORING COMPANYPROVIDED BY OTHERS.
TO 120V POWER
TO 120V POWER
PROVIDE NOTIFICATION APPLIANCE
CIRCUIT EXPANDER AS REQUIRED
FOR SIGNALING DEVICES.
HS H S X
FS
TO OTHER NOTIFICATION DEVICES.
sA
TO OTHER INITIATING DEVICES.
PIV
NAC
GENERAL METER CENTER NOTES
MC-2
SCALE: N.T.S.
1. VERIFY REQUIRED K.A.I.C. RATING OF INCOMING SERVICE WITH ELECTRICAL UTILITY COMPANY BEFORE PURCHASE AND
INSTALL OF ELECTRICAL EQUIPMENT.
2. VERIFY METER CENTER LOCATIONS WITH G.C. AND ELECTRICAL UTILITY BEFORE PURCHASE AND INSTALLATION.
3. GROUND AND BOND ACCORDING TO N.E.C. ART. 250.
4. INSTALL PERMANENT PLAQUE IDENTIFYING ALL SERVICE DISCONNECTS THAT SERVICE A STRUCTURE AND THE LOCATIONS OF
ALL OTHER SERVICE DISCONNECTS THAT SERVICE THE SAME STRUCTURE. SEE N.E.C. 225.37, 230.2(E), 230.70(B) AND 230.72(B).
MC-3A AND MC-3B
SCALE: N.T.S.
E601
SHEET NO.
REVISIONS
DATE: LAKESIDE APARTMENTS - PHASE 2CARMEL, INDIANA03.04.20215345 LEXINGTON AVEINDIANAPOLIS, IN 46219317-782-10081
METER CENTER DETAILS AND PANEL SCHEDULESGENERAL PANEL NOTES
1. VERIFY REQUIRED K.A.I.C. RATING BEFORE PURCHASE AND INSTALL OF ELECTRICAL EQUIPMENT
2. CONFIRM BREAKER SIZES FOR MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.
3. CONFIRM BREAKER SIZES AND CIRCUITS REQUIRED FOR ELEVATOR EQUIPMENT WITH ELEVATOR CONTRACTOR.
SYSTEM FIRE ALARM RISER
SCALE: N.T.S.