HomeMy WebLinkAboutE601 METER CENTER DETAILS AND PANEL SCHEDULESGRADE 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 HP-2 225A 120/208V 3Ø NEMA 3R 250KCMIL AL S.E.R. TO HOUSE PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. 3/225 MAIN DISCONNECT SERVICE RATED 1600A 120/208V 3Ø 65KAIC UNIT PANEL 125A 120/208V 1Ø NEMA 1 2/O AL S.E.R. TO UNIT PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. (TYPICAL FOR ALL UNITS) TO INCOMING METAL WATER PIPE (1)3/O CU TO CONCRETE INCASED ELECTRODE (1)#4 CU (4) 4" PVC SCH. 80 TO TRANSFORMER BY E.C; SECONDARY CONDUCTORS BY DUKE ENERGY GROUND BAR SP-2 60A 120/208V 1Ø NEMA1 3-#6CU, 1-#10 CU IN 1" PVC SCH 80 CONDUIT TO SUB-PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. EZML331225 EZMR315125X EZMR315125X EZMR316125X EZMR316125X EZMR315125X EZMR315125X EZM31600GCBC GROUND BAR TO CONCRETE INCASED ELECTRODE (1)#4 CU 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 3/200 MAIN DISCONNECT SERVICE RATED 1200A 120/208V 3Ø 65KAIC UNIT PANEL 125A 120/208V 1Ø NEMA 1 2/O AL S.E.R. TO UNIT PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. (TYPICAL FOR ALL UNITS) GROUND BAR 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 1/125 GRADE MAIN DISCONNECT SERVICE RATED 1000A 120/208V 3Ø 65KAIC UNIT PANEL 125A 120/208V 1Ø NEMA 1 2/O AL S.E.R. TO UNIT PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. (TYPICAL FOR ALL UNITS) TO INCOMING METAL WATER PIPE (1)3/O CU TO CONCRETE INCASED ELECTRODE (1)#4 CU GROUND BAR HP-3A 125A 120/208V 1Ø NEMA 3R 2/O AL S.E.R. TO HOUSE PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. HP-3B 200A 120/208V 3Ø NEMA 3R 250KCMIL AL S.E.R. TO HOUSE PANEL, SIZED FOR VOLTAGE DROP PER N.E.C. (3) 4" PVC SCH. 80 TO TRANSFORMER BY E.C; SECONDARY CONDUCTORS BY DUKE ENERGY (3) 4" PVC SCH. 80 TO TRANSFORMER BY E.C; SECONDARY CONDUCTORS BY DUKE ENERGY (1)3/O CU EZML331225 EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125X EZMR315125XEZM31000CBEZM31000CB F.A.C.P. FIRE ALARM CONTROL PANEL TS DACT DEDICATED TELEPHONE LINE FOR OUTPUT TO MONITORING SERVICE. NOTE: THE EQUIPMENT AND INSTALLATION FOR DIFFERENT DUAL MEANS OF TRANSMISSIONTO MONITORING COMPANYPROVIDED BY OTHERS. TO 120V POWER TO 120V POWER PROVIDE NOTIFICATION APPLIANCE CIRCUIT EXPANDER AS REQUIRED FOR SIGNALING DEVICES. HS H S X FS TO OTHER NOTIFICATION DEVICES. sA TO OTHER INITIATING DEVICES. PIV NAC GENERAL METER CENTER NOTES MC-2 SCALE: N.T.S. 1. VERIFY REQUIRED K.A.I.C. RATING OF INCOMING SERVICE WITH ELECTRICAL UTILITY COMPANY BEFORE PURCHASE AND INSTALL OF ELECTRICAL EQUIPMENT. 2. VERIFY METER CENTER LOCATIONS WITH G.C. AND ELECTRICAL UTILITY BEFORE PURCHASE AND INSTALLATION. 3. GROUND AND BOND ACCORDING TO N.E.C. ART. 250. 4. INSTALL PERMANENT PLAQUE IDENTIFYING ALL SERVICE DISCONNECTS THAT SERVICE A STRUCTURE AND THE LOCATIONS OF ALL OTHER SERVICE DISCONNECTS THAT SERVICE THE SAME STRUCTURE. SEE N.E.C. 225.37, 230.2(E), 230.70(B) AND 230.72(B). MC-3A AND MC-3B SCALE: N.T.S. E601 SHEET NO. REVISIONS DATE: LAKESIDE APARTMENTS - PHASE 2CARMEL, INDIANA03.04.20215345 LEXINGTON AVEINDIANAPOLIS, IN 46219317-782-10081 METER CENTER DETAILS AND PANEL SCHEDULESGENERAL PANEL NOTES 1. VERIFY REQUIRED K.A.I.C. RATING BEFORE PURCHASE AND INSTALL OF ELECTRICAL EQUIPMENT 2. CONFIRM BREAKER SIZES FOR MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR. 3. CONFIRM BREAKER SIZES AND CIRCUITS REQUIRED FOR ELEVATOR EQUIPMENT WITH ELEVATOR CONTRACTOR. SYSTEM FIRE ALARM RISER SCALE: N.T.S. 07/26/22