* DIMENSION SUBJECT TO CHANGE22" *6"1
2
"
28
"1 2" *1 2" *
22
"
PACK CURB WITH FIBERGLASS
R-6 INSULATION AFTER
LINESET INSTALLATION
COMPLETED
SQUARE CEILING DIFFUSER INSTALLATION DETAIL
SCALE: NOT TO SCALE
CEILING MOUNTED SUPPLY REGISTER INSTALLATION DETAIL
NOT TO SCALE
CEILING
INSULATED FLEXIBLE DUCT.
SIZE SAME AS SCHEDULED
DIFFUSER NECK SIZE
SUPPLY DUCT
CEILING DIFFUSER W/
MANUAL VOLUME DAMPER
INSULATED FLEX DUCT
CEILING
SUPPLY AIR REGISTER
WITH OPPOSED
BLADE
VOLUME DAMPER
SUPPLY DUCT
RADIATION DAMPER
AT RATED CEILINGS
CONNECTION
REFRIGERANT GAUGE
CONTROL WIRING
REFRIGERANT LIQUID LINE
WITH INSULATION
REFRIGERANT SUCTION LINE
SERVICE VALVES
HEAT PUMP UNIT
FAN GUARD
PAD MOUNTED AIR-COOLED CONDENSING UNIT DETAIL
NOT TO SCALE
REFRIGERANT PIPING ROOF HOOD & CURB DETAIL
SCALE: NONE
(NOTE: COORDINATE CURBS & FLASHING WITH SPECIFIED ROOF CONSTRUCTION)
OPEN SPACE TO BE LOOSLEY PACKED WITH INULATION
MOORE ENGINEERING
SERVICES, INC.
6340 LaPas Trail
Indianapolis, IN 46268
Phone (317) 291-1052
FAX (317) 298-2729
T R
NNDIA A
STATE OF DERI
G EEIS
PE60860351
No.REENIGNELANOISSEFORPDOUGLAS.R MOO
RESHEET NO.architects and land planners6201 carrollton avenueIndianapolis, in 46220phone 317 202 0661fax 317 202 0662email office@weaversherman.comweaver sherman designREVISIONS
DATE:
M500 MECHANICAL DETAILSLAKESIDE APARTMENTS - PHASE 2
03/04/2021
H-BLOCK / AC ROOFTOP SUPPORT DETAIL
NOT TO SCALE