HomeMy WebLinkAboutM501 MECHANICAL DETAILSANSI/UL1479 (ASTM E814)CAN/ULC S115
F Ratings —1 and 2 Hr (See Items 1 and 3)F Ratings — 1 and 2 Hr (See Items 1 and 3)
T Rating — 0 Hr FT Rating — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft FH Ratings —1 and 2 Hr (See Items 1 and 3)
L Rating at 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr
L Rating at Ambient — Less Than 1 CFM/sq ft
L Rating at 400 F — Less Than 1 CFM/sq ft
Hilti Firestop Systems
System No. W-L-1054
WL 1054C R US
Page: 1 of 2
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
October 14, 2015
Classified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified
in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction
features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm)
lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are
used and the diam of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed
between the vertical studs and screw-attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152
mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diam of the penetrating item such that, when the penetrating item is installed in the
opening, a 2 to 3 in. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of
layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance
Directory. Max diam of opening is 32-1/4 in. (819 mm) for steel stud walls. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls.
The F and FH Ratings of the firestop system are equal to the fire rating of the wall assembly.
SECTION A-A
A
A
1A
3
2 1BCLASSIFI
E
DCEILING EXHAUST FAN DETAIL
NOT TO SCALE
VERTICAL AHU INSTALLATION DETAIL
NOT TO SCALE
DETAIL 'A'
FIRE DAMPER AT FIRE RATED WALL DETAIL
NOT TO SCALE
DETAIL 'A'
FIRE DAMPER AT FIRE RATED WALL DETAIL
NOT TO SCALE
GRILLE
EXHAUST
RECTANGULAR OR
BACKDRAFT
DAMPER
CEILING
MOUNT FAN TO FINISHED
CEILING FRAMING.
PROVIDE
NEOPRENE VIBRATION
ISOLATORS.
ROUND DUCTWORK
AS SPECIFIED ON
PLANS
INSTALLATION TO BE
IN COMPLIANCE WITH
MANUFACTURERS
INSTRUCTIONS
PROVIDE CLEARANCE
ON TOP & SIDES FOR
EXPANSION
FIRE RATED WALL
18 GAUGE SLEEVE
FIRE RATED WALL
SEE DETAIL 'A' WHERE
WALL IS CONSTRUCTED
OF WOOD OR STEEL
JOISTS
VERTICAL CURTAIN TYPE STATIC
FIRE DAMPER WITH UL RATING FOR
1-1/2 HR UNLESS OTHERWISE NOTED.
(SIMILAR TO RUSKIN IBD2 STYLE "A")
FASTEN DUCT TO SLEEVE
WITH 'S' SLIP ON TOP &
BOTTOM & DRIVE SLIP ON
SIDES
RETAINING ANGLES SHALL BE 2"x2"x1/8"
& SHALL BE SECURED TO 18 GA. SLEEVE
WITH 1/2" WELDS AT 6" O.C. DO NOT
SECURE ANGLES TO WALL. PROVIDE ANGLES
ON ALL FOUR SIDES OF SLEEVE &
BOTH SIDES OF WALL.
WOOD OR STEEL JOISTS
CARRY FIRE
RESISTANT
LINING ON ALL SIDES
OF OPENING
RETAINING ANGLE
18 GAUGE
SLEEVE
GRILLE
FIRE DAMPER FRAME
FUSIBLE LINK (165°F)
STEEL BLADES WITH
INTERLOCKING JOINTS
EXPAND DUCT SO THAT
FIRE DAMPER DOES NOT
REDUCE AREA OF DUCT,
EXPANSION IN WIDTH
IS ACCEPTABLE
PROVIDE SEALANT TO JOINT
ALL AROUND
DUCTWORK-SEE
PROJECT
DRAWINGS FOR SIZE
AND CONTINUATION
GRILLE
INSTALLATION TO BE
IN COMPLIANCE WITH
MANUFACTURERS
INSTRUCTIONS
PROVIDE
CLEARANCE
ON TOP & SIDES FOR
EXPANSION
FIRE RATED WALL
PROVIDE SEALANT TO JOINT
ALL AROUND ON BOTH
SIDES OF WALL
18 GAUGE COLLAR
FIRE RATED WALL
SEE DETAIL 'A' & 'B'
WHERE WALL IS CONSTRUCTED
OF WOOD OR STEEL JOISTS
VERTICAL CURTAIN TYPE
STATIC FIRE DAMPER WITH
UL RATING FOR 1-1/2 HR
UNLESS OTHERWISE NOTED.
(SIMILAR TO RUSKIN IBD2
STYLE "B")
DUCTWORK-SEE PROJECT
DRAWINGS FOR SIZE
AND CONTINUATION
DOUBLE WALL, HINGED, GASKETED
AND INSULATED ACCESS PANEL,
(LABEL "FIRE DAMPER ACCESS DOOR")
FASTEN DUCT TO SLEEVE
WITH 'S' SLIP ON TOP &
BOTTOM & DRIVE SLIP ON
SIDES
RETAINING ANGLES SHALL BE 2"x2"x1/8" & SHALL BE
SECURED TO 18 GA. COLLAR WITH 1/2" WELDS AT 6" O.C.
DO NOT SECURE ANGLES TO WALL OR FLOOR.
PROVIDE ANGLES ON ALL FOUR SIDES OF SLEEVE &
BOTH SIDES OF WALL OR FLOOR.
FIRE DAMPER FRAME
RETAINING ANGLE
WOOD OR STEEL
JOISTS
CARRY FIRE
RESISTANT
LINING ON ALL SIDES
OF OPENING
SLEEVE
FUSIBLE LINK (165°F)
STEEL BLADES WITH
INTERLOCKING JOINTS
SOUND LINING
WHERE INDICATED
METAL NOSING
OVER INTERNAL
INSULATION
FIRE DAMPER ACCESS PANEL IN CEILING
ELECTRIC UNIT HEATER DETAIL
NOT TO SCALE
POWER SUPPLY
JUNCTION BOX
WALL
SWITCH
DISCONNECT
NON-FUSED
EXPANSION ANCHORS MINIMUM7'-0" A.F.F.ELECTRIC
SLAB
J
MOUNTING RODS
(4) THREADED
SUPPLY AIR
UNIT HEATER
WATER HEATER PAN
A.O. SMITH
ENL-40 WATER
HEATER
FAN COIL
DUCT
CLEARENCE MIN. 20"
DOOR MIN. 30"
REFRIGERANT
LINE SET
DUCT RADIATION
DAMPER
FLEX
CENNECTOR
CONDENSATE TRAP & DRAIN RAN
TO O.S.D.
MAIN SHUT-OFF
SUBMETER
VALVE
A.O SMITH
ENL-40 WATER
HEATER
WATER HEATER PAN
FIRE
DAMPER
30"x12" R.A.G. WHEN SOLID CLOSET DOOR IS
USED -NOT REQUIRED WITH LOUVERED
DOOR
MATERIALS EXPOSED WITHIN PLENUM SHALL BE NON-
COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX
OF NOT MORE THAN 25 AND A SMOKE DEVELOPMENT INDEX OF
NOT MORE THAN 50.
MIN. STUD TO STUD
HW
EXPANSION TANK
33
1/2
108
36
30
38
33 1/4
26 ∅
21"
∅26
16 1/8"
42
CW
MOORE ENGINEERING
SERVICES, INC.
6340 LaPas Trail
Indianapolis, IN 46268
Phone (317) 291-1052
FAX (317) 298-2729
T R
NNDIA A
STATE OF DERI
G EEIS
PE60860351
No.REENIGNELANOISSEFORPDOUGLAS.R MOO
RESHEET NO.architects and land planners6201 carrollton avenueIndianapolis, in 46220phone 317 202 0661fax 317 202 0662email office@weaversherman.comweaver sherman designREVISIONS
DATE:
M501 MECHANICAL DETAILSLAKESIDE APARTMENTS - PHASE 2
03/04/2021
No.Date
07/26/22