HomeMy WebLinkAboutA404 ELEVATOR SECTIONSFURNISH AND INSTALL (2) IDENTICAL PASSENGER ELEVATORS EQUAL TO "ENDURA" MRL SERIES AS MANUFACTURED BY THYSSEN KRUPP ELEVATOR COMPANY ELEVATOR PERFORMANCE SPECIFICATIONS SIDEWALL PANELS:PLASTIC LAMINATE, "STANDARD" SELECTION WALL PANEL REVEALS: #4 STAINLESS STEEL HANDRAILS: CYLINDRICAL, 1 1/2" DIA., SATIN STAINLESS STEEL SUSPENDED CEILING: METAL PAN, #4 STAINLESS STEEL, BRUSHED FINISH LIGHTING:RECESSED LED DOWNLIGHTS DOORS & FRAMES:#4 STAINLESS STEEL FINISH FLOORING:CARPET BY OWNER PERFORMANCE SPECIFICATIONSCAPACITY:3,500 LBS. TYPE:A:HYDRAULIC SPEED:150 FPM UP/DOWN NUMBER OF STOPS:4 FLOOR STOPS:LEVELS 1, 2, 3, 4 NET TRAVEL:32'-1 1/8" OVERHEAD CLEARANCE:12'-11" MIN. HOISTWAY CEILING:13'-9" CAR HEIGHT:7'-4" CLEAR HOISTWAY SIZE:8'-8" x 6'-11" INSIDE DIM. CAB SIZE:6'-8" x 5'-5" DOOR POSITION:SIDE OPENING - LEFT DOOR ENTRANCE WIDTH:3'-6" DOOR ENTRANCE HEIGHT:7'-0" EMERGENCY POWER:BATTERY LOWERING PADS AND HOOKS: YES PIT DEPTH: 4'-0" SIGNALIZATION FIXTURE: STANDARD BUILDING VOLTAGE: 208V. 3 PHASE, 60 HZ. HOISTWAY CONSTRUCTION: REINFORCED CMU MACHINE ROOM: NOT REQUIRED CONTROLLER: LOCATED IN DOOR JAMB ON LEVEL 2 FIRE SERVICE ACCESS REQUIRED ELEVATOR (FSAE) - ACCOMMODATE 24"x84" STRETCHER * *DENOTES DIMENSIONING TO UNDERSIDE OF 8" WF HOIST BEAM ELEVATOR No. 1 CAB FINISHES ELEVATOR No. 2FEATURE architects and land planners6201 carrollton avenueIndianapolis, in 46220phone 317 202 0661fax 317 202 0662email office@weaversherman.comweaver sherman designADDENDUM 1 10/22/2021 OMIT HOISTWAY VENTING 07/26/22