HomeMy WebLinkAboutE001 ELECTRICAL NOTESSYMBOL DESCRIPTION SYMBOL DESCRIPTION
SWITCH: SINGLE POLE 120V SMOKE DETECTOR WITH BATTERY BACKUP,
INTERCONNECTED WITHIN AN APARTMENT UNIT
SWITCH: THREE WAY 120V SMOKE DETECTOR WITH STROBE AND BATTERY
BACKUP, INTERCONNECTED WITHIN AN APARTMENT UNIT
SWITCH: FOUR WAY 120V STROBE ONLY, INTERCONNECTED WITH SMOKE
DETECTORS WITHIN AN APARTMENT UNIT
SWITCH: WALL OCCUPANCY SENSOR
120V C.O. DETECTOR WITH BATTERY BACKUP,
INTERCONNECTED WITH SMOKE DETECTORS WITHIN AN
APARTMENT UNIT
SWITCH: OCCUPANCY SENSOR OVERRIDE
SYSTEM FIRE ALARM: DETECTOR, X = TYPE
S = SMOKE DETECTION, H = HEAT DETECTION,
T = LOW TEMPERATURE DETECTION
CEILING OCCUPANCY SENSOR SYSTEM FIRE ALARM: 520HZ HORN AND STROBE
RECEPTACLE: 120V DUPLEX SYSTEM FIRE ALARM: 520 HZ HORN
RECEPTACLE: 120V DUPLEX G.F.C.I. PROTECTED SYSTEM FIRE ALARM: FUTURE NOTIFICATION DEVICE
PROVISION
RECEPTACLE: 120V DUPLEX G.F.C.I. PROTECTED EXTERIOR
RATED WITH WEATHERPROOF IN-USE COVER
SYSTEM FIRE ALARM: HORN STROBE
WP = WEATHERPROOF
RECEPTACLE INSTALLED AT COUNTER HEIGHT (TYPICAL)SYSTEM FIRE ALARM: STROBE
RECEPTACLE: DOUBLE DUPLEX (QUAD)SYSTEM FIRE ALARM: PULL STATION
RECEPTACLE: DUPLEX FLOOR BOX WITH TV AND DATA,
(1) RG-6 AND (1) CAT6 SYSTEM FIRE ALARM: TAMPER SWITCH MONITOR MODULE
RECEPTACLE: DUPLEX LOWER HALF SWITCHED SYSTEM FIRE ALARM: FLOW SWITCH MONITOR MODULE
D = RECEPTACLE: SINGLE DEDICATED CIRCUIT
DM = RECEPTACLE: SINGLE DEDICATED CIRCUIT FOR
MICROWAVE. LOCATE IN UPPER CABINET.
SYSTEM FIRE ALARM: CONTROL RELAY
RECEPTACLE: 120/208-240V 4-WIRE
50 = 50 AMP RATED
30 = 30 AMP RATED
SYSTEM FIRE ALARM: FIRE ALARM CONTROL PANEL
SERVICE DISCONNECT: NON-FUSED SYSTEM FIRE ALARM: ANNUNCIATOR PANEL
SERVICE DISCONNECT: FUSED SYSTEM FIRE ALARM: NAC PANEL
JUNCTION: JUNCTION LOCATED IN EQUIPMENT OR INSTALL
JUNCTION BOX WITH COVER (WHERE APPLICABLE).ELECTRICAL PANELBOARD
LOW VOLTAGE PANEL WITH 120V DUPLEX RECEPTACLE,
(1) RG-6 AND (1) CAT6 TO TELECOM SERVICE ROOM.
CEILING MOUNT LIGHT FIXTURE
X = TYPE
ELECTRICAL LOAD CENTER.WALL MOUNT LIGHT FIXTURE
X = TYPE
SECURITY CAMERA: TYPE IP TYPE: RM - REMOTE EMERGENCY EGRESS LIGHT
TV AND DATA, (1) RG-6 AND (1) CAT6 TO LOW VOLTAGE
PANEL WITHIN APARTMENT UNIT.
TYPE: EXIT/EM - EXIT AND EMERGENCY LIGHT
SHADED AREAS INDICATED ORIENTATION OF SIGN FACES
ARROWS, IF PRESENT, INDICATE EGRESS DIRECTION
DATA, (1) CAT6 TO NEAREST IT ROOM TYPE: EM - EMERGENCY LIGHT
TV, (1) RG-6 TO NEAREST IT ROOM ACCESS CONTROL: CALL BOX
DATA IN CEILING, (1) CAT6 TO NEAREST IT ROOM FOR
FUTURE WIRELESS ACCESS POINT.ACCESS CONTROL: CARD READER
PHOTOCELL
1
3
4
OS
G
WP/G
HS
H
X
HS
S
s
V
F
TS
FS
FACP
ANN
HS
WP
50 30
CR
X
X
HP-XX
s
CB
PC
R
NAC
s VO
WAP
DM D
OS
J
c
X
s
R
TYPE MANUFACTURER AND MODEL NUMBER LAMP
TYPE MOUNTING DESCRIPTION
A RAB: DSK34-6R16930120WS LED SURFACE UNIT CLOSET / LAUNDRY AREA
B SEA GULL / GENERATION LIGHTING: 89181EN3-71 LED WALL SMALL COACH
NOT LESS THAN 80" TO BOTTOM
C RAB: DSK34-6R16930120WS LED SURFACE COMMON AREA
D KUZCO: 492208-BK LED PENDANT UNIT KITCHEN BAR
E KICHLER: 55092BK LED WALL UNIT BATHROOM VANITY
EF-1 PROVIDED AND INSTALLED BY M.C.,
WIRING AND CONNECTION BY E.C.X RECESSED UNIT BATHROOM EXHAUST FAN
G RAB: DSK34-6R16930120WS LED SURFACE UNIT BATHROOM
H RAB: DSK34-6R16930120WS LED SURFACE UNIT KITCHEN / HALLWAY / ENTRY
J KICHLER: 330171SBK LED PENDANT UNIT CEILING FAN AND LIGHT
K SEA GULL / GENERATION LIGHTING: 89193DEN3-71 LED WALL LARGE COACH
NOT LESS THAN 80" TO BOTTOM
L RAB: DSK34-6R16930120WS LED SURFACE UNIT DINING AREA
M EPCO: 16531 LED SURFACE GARAGE
N ETI: VT-4-70-850-MV-D LED WALL /
SURFACE ELEVATOR SHAFT
P SEA GULL / GENERATION LIGHTING: 89181EN3-71 LED WALL SMALL COACH
NOT LESS THAN 80" TO BOTTOM
SL1 RAB: FFLED26N LED YARD POST SITE
SL3 CBMC LIGHTING SOLUTIONS:
DL147942 FIXTURE - DL147941 POLE LED POLE SITE
SL5 CBMC LIGHTING SOLUTIONS:
DL147942 FIXTURE - DL147941 POLE LED POLE SITE
EM EXITRONIX: LED-90 LED WALL EMERGENCY
EXIT/EM EXITRONIX: CLED-U-WH LED WALL / CEILING EXIT SIGN WITH EMERGENCY
RM EXITRONIX: MLED2-G-WP LED WALL / CEILING REMOTE EGRESS
RATING OR SETTING OF
AUTOMATIC OVERCURRENT
DEVICE IN (AMPERES)
MINIMUM
SIZE (AWG OR KCMIL)
COPPER
MINIMUM
SIZE (AWG OR KCMIL)
ALUMINUM OR COPPER-CLAD
ALUMINUM
15 14 X
20 12 X
25 10 X
30 10 X
40 8 X
50 6 X
125 1 2/0
150 1/0 3/0
200 3/0 250
225 4/0 300
NOTE: SIZE ALL CONDUCTORS BASED ON ALL N.E.C. REQUIREMENTS INCLUDING THOSE FOR VOLTAGE DROP, ADJUSTMENTS
AND CORRECTIONS.
CEILING-MOUNTED DETECTOR
WALL-MOUNTED DETECTOR
GENERAL NOTES:
1. MOUNTING HEIGHTS SHOWN IN THIS DETAIL ARE
TYPICAL UNLESS OTHERWISE NOTED ON THE PLANS.
2. SEE ARCHITECTURAL ELEVATIONS FOR SPECIAL
CONDITIONS. NOTIFY ARCHITECT IMMEDIATELY OF ANY
CONFLICTS.
3. ALL INSTALLATIONS SHALL COMPLY WITH ADA.
VISUAL FIRE ALARM NOTIFICATION DEVICES (STROBE)
LOCATE DEVICE SO THE BOTTOM OF THE DEVICE IS
BETWEEN 80" AND 96" A.F.F. (NFPA) OR 6" BELOW
CEILING, WHICHEVER IS LOWER (ADA).
AUDIBLE FIRE ALARM NOTIFICATION DEVICES (HORN)LOCATE DEVICE SO THAT THE TOP OF UNIT IS NOT MORE
THAN 90" A.F.F. AND NOT LESS THAN 6" BELOW CEILING
(NFPA)
POWER/COMMUNICATION DEVICES: OUTLETS SHALL
BE LOCATED NOT LESS THAN 16" A.F.F. TO THE
BOTTOM OF THE BOX. ABOVE COUNTER DEVICES SHALL
BE LOCATED AT 2" ABOVE THE BACKSPLASH OF THE
COUNTER TO THE BOTTOM OF THE DEVICES. VERIFY
WITH ARCHITECTURAL DETAILS. IN ALL FHA/TYPE B UNITS,
WALL-MOUNTED OPERABLE DEVICES: OPERABLE DEVICES
SHALL BE LOCATED NOT MORE THAN 48" A.F.F. TO
THE TOP OF THE OPERABLE PORTION OF THE DEVICE.
WALL-MOUNTED OPERABLE DEVICES INCLUDE, BUT ARE
NOT LIMITED TO THE FOLLOWING:
LIGHT SWITCHES, DIMMERS, CONTROLS, ETC.
PUSH BUTTONS
INTERIOR AND EXTERIOR
POWER AND COMMUNICATION
HORN/STROBESTROBE
FINISH FLOOR
16"
40"
48"
80"
FINISH CEILING
88"
DO NOT PLACE
DETECTOR IN
THIS AREA 12" MAX.
4"
4"
96"
HORN
CEILING-MOUNTED HORN
OR HORN/STROBE
54"
FIRE ALARM ACTIVATION DEVICES (PULL STATION)LOCATE FRONT-APPROACH DEVICES SO THAT THE
HIGHEST OPERABLE PORTION OF THE DEVICE IS NOT
MORE THAN 48" A.F.F (ADA) AND NOT LESS THAN 42"
A.F.F. (NFPA).
OUTLETS
GARAGE DOOR
OPENER BUTTON
UNIT LOAD CENTER
44"
ABOVE COUNTER DEVICES.
COORDINATE WITH ARCH.
ELEVATIONS AND CABINETRY
SHOP DRAWINGS.
MAXIMUM HEIGHT FOR
WALL-MOUNTED
OPERABLE DEVICES PULL STATION
LOCATE ABOVE COUNTERTOP OUTLETS 12" MINIMUM FROM
A PERPENDICULAR WALL, REFRIGERATOR OR OTHEROBSTRUCTION.
1. WORK SHALL INCLUDE STARTUP OF ALL SYSTEMS, FURNISHING OF
OPERATING AND MAINTENANCE INSTRUCTIONS AND ONE-YEAR
GUARANTEE COMMENCING ON DATE OF PROJECT ACCEPTANCE.
2. VERIFY LOCAL CONDITIONS AT SITE.
3. COMPLY WITH ALL APPLICABLE CODES.
4. SECURE AND PAY FOR ALL REQUIRED PERMITS AND SUPPLY TO G.C.
PRIOR TO STARTING OF WORK.
5. ALL BRANCH CIRCUITS TO BE COPPER. BRANCH WIRING TO BE TYPE
N.M.
6. IDENTIFY AND LABEL ALL ELECTRICAL SERVICE EQUIPMENT. PROVIDE
AND INSTALL ENGRAVED LABELS WITH UNIT NUMBERS ON ALL A/C
DISCONNECTS AND ELECTRICAL METERS. PROVIDE AND INSTALL
TYPE WRITTEN PANEL DIRECTORY.
7. CONNECT TELEPHONE AND TELEVISION SYSTEMS PER LOCAL UTILITY
REQUIREMENTS. VERIFY LOCATIONS AND TYPE OF EQUIPMENT
REQUIRED WITH ARCHITECT AND OWNER.
8. PROVIDE AND INSTALL FIRE ALARM SYSTEM COMPLETE WITH CELL
DIALER. ENGINEERED FIRE ALARM DRAWINGS TO BE SUBMITTED TO
THE STATE AFTER AWARD OF PROJECT.
9. ALL ELECTRICAL DEVICES AND COVER PLATES TO BE WHITE WHERE
APPLICABLE.
MOUNTING HEIGHTS
SCALE: N.T.S.
ELECTRICAL SYMBOLS LIGHTING SCHEDULE CONDUCTOR SIZES
GENERAL ELECTRICAL NOTES
E001 ELECTRICAL NOTES, SCHEDULES AND SYMBOLS LEGEND
E100 SITE - ELECTRICAL PLAN
E101 BUILDING TYPE 2 - 1ST AND 2ND FLOOR ELECTRICAL PLANS
E102 BUILDING TYPE 2 - 3RD AND 4TH FLOOR ELECTRICAL PLANS
E103 BUILDING TYPE 3 - 1ST AND 2ND FLOOR ELECTRICAL PLANS
E104 BUILDING TYPE 3 - 3RD AND 4TH FLOOR ELECTRICAL PLANS
E201 UNIT TYPES U2, U3, D1 AND D1A - ELECTRICAL PLANS
E202 UNIT TYPES D2, D3, D3A AND D4 - ELECTRICAL PLANS
E203 UNIT TYPES D5, D6 AND T1 - ELECTRICAL PLANS
E601 METER CENTER DETAILS AND PANEL SCHEDULES
E602 ELECTRICAL LOAD CALCULATIONS
DRAWING INDEX
NOT ALL SYMBOLS MAY BE USED FOR THIS PROJECT.
E001
SHEET NO.
REVISIONS
DATE: LAKESIDE APARTMENTS - PHASE 2CARMEL, INDIANA03.04.20215345 LEXINGTON AVEINDIANAPOLIS, IN 46219317-782-10081
ELECTRICAL NOTES, SCHEDULES AND SYMBOLS LEGEND07/26/22