HomeMy WebLinkAboutE104 BUILDING TYPE 2 3RD 4TH FLOOR ELECTRICALGENERAL COMMON
AREA NOTES
1. ALL EXTERIOR LIGHTING CONTROLLED BY PHOTOCELL UNLESS
OTHERWISE NOTED.
2. VERIFY ALL MECHANICAL EQUIPMENT REQUIREMENTS AND
LOCATIONS WITH M.C. PRIOR TO ROUGH IN.
3. PROVIDE SYSTEM FIRE ALARM MONITORING OF SPRINKLER VALVES
AND P.I.V. AS NEEDED. VERIFY LOCATIONS WITH F.P.C. AND G.C.
5. PROVIDE (1) 20A 120V G.F.C.I. PROTECTED RECEPTACLE WITHIN 25'
OF ALL EXTERIOR MECHANICAL EQUIPMENT. USE "IN-USE" STYLE
WEATHER PROOF COVERS IDENTIFIED AS "EXTRA-DUTY". USE
EXTERIOR RATED RECEPTACLES.
1 PROVIDE RECEPTACLE IN CEILING FOR GARAGE DOOR
OPENER. PROVIDE AND INSTALL LOW VOLTAGE WIRING FOR
GARAGE DOOR OPENER BUTTON AND SENSORS.
2 WALL HEATER BY M.C., PROVIDE CIRCUIT AND CONNECTION.
3 CEILING UNIT HEATER BY M.C., PROVIDE CIRCUIT AND
CONNECTION.
4 EXHAUST FAN BY M.C, PROVIDE POWER FROM NEAREST
LIGHTING CIRCUIT AND CONNECTION.
5 NOT USED.
6 PROVIDE (2) CAT5E CABLE FROM TELEPHONE D-MARK TO
ELEVATOR CONTROL BOX. VERIFY LOCATION WITH
ELEVATOR CONTRACTOR.
7 PROVIDE DEDICATED CIRCUIT AND (2) CAT5E CABLE FROM
TELEPHONE D-MARK TO FIRE ALARM CONTROL PANEL.
8 PROVIDE PULL CHAIN LIGHT FIXTURE AND G.F.C.I.
PROTECTED RECEPTACLE IN ATTIC AT ACCESS POINT.
9 FOR EACH MAIN LOW VOLTAGE EQUIPMENT ROOM PROVIDE
(2) DEDICATED QUAD RECEPTACLE, (1) 4X8 SHEET
OF FIRE RATED PLYWOOD, (1) TERMINAL STRIP WITH #6
COPPER CONDUCTOR FROM ELECTRICAL SYSTEM FOR
INTERSYSTEM BONDING AND (2) 4" CONDUIT WITH PULL
STRING TO EXTERIOR SERVICE LOCATION.
KEY COMMON
AREA NOTES
CC C C
S s S s S s SsC
HS HS HS HS
SF-1
4 C C
S s C C
S s C C
S s C C C CC C Ss
HS
CC
C
S
C
CSs
CC C C
WP/1 B 11/20 3/100
R RR
6
C
S
s NNG
1C
CC
C
C C
5
8S s S s S s SsC
HS HSHS HS
SF-1
4
S s C
S s
Ss
HS
CC
C
S
C
C
C CC C sC
S s C C CC C C 8
Ss
S s S s
WP/G WP/G
3RD FLOOR ELECTRICAL PLAN - BUILDING TYPE 3
SCALE: 1/8" = 1'-0"E104
SHEET NO.
REVISIONS
DATE: LAKESIDE APARTMENTS - PHASE 2CARMEL, INDIANA03.04.20215345 LEXINGTON AVEINDIANAPOLIS, IN 46219317-782-10081
4TH FLOOR ELECTRICAL PLAN - BUILDING TYPE 3
SCALE: 1/8" = 1'-0"BUILDING TYPE 3 - 3RD AND 4TH FLOOR ELECTRICAL PLANS07/26/22