HomeMy WebLinkAboutLS101 TYPE 2 1ST 2ND FLOOR LIFE SAFETYHSHS11. REFER TO THE STRUCTURAL FRAMING PLANS FOR LOCATIONS OF
SHEAR WALLS IN THE FLOOR BOXES.
12. PROVIDE PORTABLE FIRE EXTINGUISHERS AND ADA-COMPLIANT
SEMI-RECESSED FIRE EXTINGUISHER CABINETS (F.E.C.) WHERE INDICATED.
6. WALLS SURROUNDING EXIT ENCLOSURES ARE CLASSIFIED AS FIRE
BARRIERS AND MUST MEET REQUIREMENTS PER SECTION 707 OF THE I.B.C.
(SEE STAIR SECTIONS FOR ADDITIONAL INFORMATION).
APPLICABLE BUILDING CODE: 2014 INDIANA BUILDING CODE.
FIRE EXTINGUISHERS AND FIRE EXTINGUISHER CABINETS SHALL BE EQUAL
TO J.L. INDUSTRIES "AMBASSADOR" 1017F17 STEEL NON-RATED,
SEMI-RECESS CABINET; "AMBASSADOR "1013F17 STEEL NON-RATED,
SURFACE MOUNTED CABINETS WHERE INDICATED ON DRAWINGS; AND
"COSMIC" #10E MULTI-PURPOSE DRY CHEMICAL EXTINGUISHERS. PROVIDE
EXTINGUISHER SIZE AS REQUIRED INSIDE ELEVATOR EQUIPMENT ROOMS.
PROVIDE CABINETS THAT COMPLY WITH ADA REQUIREMENTS.
13. PRIVATE GARAGE CEILINGS SHALL CONSIST OF (1) LAYER OF 5/8" F.C.
GYPSUM BOARD APPLIED DIRECTLY TO THE UNDERSIDE OF THE FLOOR
TRUSSES ABOVE, FOLLOWED BY (1) ADDITIONAL LAYER OF 1/2" GYPSUM
BOARD FACING THE GARAGE SPACE. STAGGER ALL JOINTS BETWEEN GYP.
BD. LAYERS.
14. SPRINKLER PIPING INSTALLER SHALL NOT LOCATE WET PIPE
SPRINKLER PIPING INSIDE THE ROOF/ATTIC CAVITY. FIRE PROTECTION
CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE ARCHITECT FOR
REVIEW PRIOR TO START OF CONSTRUCTION.
2. THE CONTRACTOR, SUB-CONTRACTORS AND MATERIAL SUPPLIERS SHALL
REVIEW AND BECOME FAMILIAR WITH DESIGNATED FIRE-RESISTIVE
REQUIREMENTS OF UNDERWRITERS LABORATORIES (U.L.) ASSEMBLY
DESIGNS AS PERTAINING TO THE PROJECT DESIGN.
3. THE CONTRACTOR, SUB-CONTRACTORS AND GYPSUM BOARD SUPPLIER
SHALL REVIEW AND BECOME FAMILIAR WITH APPLICABLE SECTIONS OF THE
CURRENT EDITION OF THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN
MANUAL.
4. REFER TO THE LIFE SAFETY WALL SECTIONS
FOR LISTED FIRE RATED WALL, FLOOR/CEILING AND ROOF
ASSEMBLIES.
5. PENETRATIONS INTO AND OPENINGS THROUGH EXIT ENCLOSURES
(STAIRWELLS) ARE PROHIBITED BY CODE EXCEPT FOR ELECTRICAL
CONDUIT AND SPRINKLER PIPING SERVING THE EXIT ENCLOSURE AREA.
LIFE SAFETY NOTES:
1. FOR BASIC BUILDING CODE DATA PERTAINING TO THIS PROJECT, REFER
TO THE "CODE INFORMATION" SECTION ON THE COVER SHEET.
10. REFER TO THE BUILDING ELEVATION DRAWINGS FOR LOCATIONS OF
FIRE DEPARTMENT KEY ACCESS KNOX BOXES AT BUILDING ENTRANCES
AND AT ENTRY DOORS TO BUILDING SPRINKLER CLOSETS.
7. ALL AREA AND DWELLING UNIT SEPARATION WALLS (FIRE PARTITIONS)
AND THEIR POINTS OF INTERSECTION WITH OTHER WALLS SHALL INCLUDE
CONTINUOUS (FULL-HEIGHT) WOOD BLOCKING TO SUPPORT GYPSUM
DRYWALL.
8. REFER TO SHEET BA-101 FOR ASSIGNED BUILDING AND DWELLING UNIT
STREET ADDRESSES.
9. THE GENERAL CONTRACTOR SHALL PROVIDE PERMANENT
IDENTIFICATION SIGNAGE ABOVE THE CEILING LINE THAT IDENTIFIES A FIRE
OR SMOKE BARRIER OR FIRE PARTITION SEPARATING DEFINED FIRE AREAS.
THE SIGNAGE SHALL BE PLACED ADJACENT TO EACH STAIRWELL AND
ABOVE PRIVATE GARAGE CEILINGS LOCATED ADJACENT TO A DWELLING
UNIT. THE SIGNAGE SHALL BE LOCATED IN ACCESSIBLE CONCEALED FLOOR,
FLOOR/CEILING OR ATTIC SPACES AS DEFINED BY THE INDIANA BUILDING
CODE, SECTION 703.7.
APPROVED DRAFTSTOP AT FLOOR BOX OR IN ATTIC SPACE
AS APPROPRIATE AT THESE LOCATIONS. REFER TO THE
LIFE SAFETY WALL SECTIONS FOR ADDITIONAL
INFORMATION.
THE CEILING ABOVE THIS AREA IS THE BOTTOM OF THE
EXIT ENCLOSURE ABOVE AND MUST BE TREATED AS PART
OF THE EXIT ENCLOSURE ASSEMBLY. PENETRATIONS INTO
AND OPENINGS THROUGH EXIT ENCLOSURE ASSEMBLIES
ARE PROHIBITED BY CODE EXCEPT FOR ELECTRICAL
CONDUIT AND SPRINKLER PIPING SERVING THE EXIT
ENCLOSURE AREA.
LIFE SAFETY KEY:
DRAFT STOPPING SHALL BE LOCATED ABOVE AND IN LINE
WITH THE DWELLING UNIT SEPARATION WALLS AND AT
CORRIDOR WALLS.
CONSTRUCTION BELOW THE FLOOR LINE IN THIS SHADED
AREA IS INCLUDED IN THE EXIT ENCLOSURE ON THE FLOOR
BELOW AND MUST BE TREATED AS PART OF THE
FIRE-RESISTIVE EXIT ENCLOSURE ASSEMBLY. PENETRATIONS
INTO AND OPENINGS THROUGH EXIT ENCLOSURE
ASSEMBLIES ARE PROHIBITED BY CODE EXCEPT FOR
ELECTRICAL CONDUIT AND SPRINKLER PIPING SERVING THE
EXIT ENCLOSURE AREA.
WHERE INDICATED, SUBSTITUTE 1-HOUR FIRE RATED
PLYWOOD SHEATHING OR EQUIVALENT IN LIEU OF
STANDARD OSB SHEATHING AT PLANE OF EXTERIOR
WALL. EXTERIOR WALL SHALL BE RATED FOR 1-HOUR F.R.
CONSTRUCTION ON BOTH SIDES OF WALL FOR A MINIMUM
DISTANCE OF 4 FEET IN EITHER DIRECTION (UNLESS
OTHERWISE NOTED) OF A DESIGNATED FIRE WALL. REFER
TO BUILDING ELEVATIONS FOR ADDITIONAL INFORMATION.
F.W. "A"
REFER TO LIFE SAFETY WALL SECTIONS AND DETAILS -
REFER TO SHEETS A621 THRU A624.
OCCUPANCY CLASSIFICATIONS PERTAINING TO SPRINKLER DESIGN,
INSTALLATION AND WATER SUPPLY REQUIREMENTS AS DEFINED BY NFPA 13
STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS ARE AS LISTED:
RESIDENTIAL DWELLING UNITS: LIGHT HAZARD
NFPA OCCUPANCY
CLASSIFICATIONS:
APPLICABLE BUILDING CODE: NFPA 13 AND NFPA 13-R
DENOTES FIRE BARRIER AT WALL. PROVIDE FIRE-RATED
CONSTRUCTION AS NOTED. REFER TO THE DOOR
SCHEDULE FOR RATED OPENINGS.
IN ACCORDANCE WITH THE 2014 INDIANA BUILDING CODE, TABLE 803.9 - INTERIOR WALL AND
CEILING FINISH REQUIREMENTS BY OCCUPANCY, PROVIDE INTERIOR FINISHES COMPLYING WITH
THE FOLLOWING FLAME SPREAD INDEX FOR THE INTENDED USES:
INTERIOR FINISH RATINGS:
GROUP R-2
SPRINKLERED DWELLING
UNITS:
GROUP INTERIOR EXIT
STAIRWAYS CORRIDORS
ROOMS AND
ENCLOSED
SPACES
C C C
FLAME SPREAD INDEXES SHALL NOT EXCEED THE VALUES
DESCRIBED ABOVE FOR THEIR DESIGNATED LOCATION.
PENETRATIONS INTO AND OPENINGS THROUGH EXIT
ENCLOSURE ASSEMBLIES ARE PROHIBITED BY CODE
EXCEPT FOR ELECTRICAL CONDUIT AND SPRINKLER
PIPING SERVING THE EXIT ENCLOSURE AREA.
LS1
1. FIRE PROTECTION CONTRACTOR SHALL PROVIDE AN NFPA 13R
AUTOMATIC SPRINKLER SYSTEM IN ALL GROUP R-2 OCCUPANCIES IN
ACCORDANCE WITH I.B.C. SECTION 903.3.1.2.
THE PRIVATE GARAGES (USE GROUP U) SHALL BE PROTECTED WITH
AUTOMATIC SPRINKLERS HYDRAULICALLY CALCULATED PER NFPA 13.
FIRE PROTECTION NOTES:architects and land planners6201 carrollton avenueIndianapolis, in 46220phone 317 202 0661fax 317 202 0662email office@weaversherman.comweaver sherman design07/26/22