Loading...
HomeMy WebLinkAboutCPC-Pavilion_Permit Set_20220620_Sheet-G.105BUILDING AREA LIMITATION (ADDITION) : TOTAL AREA ALLOWED :6,000 S.F.FRONTAGE INCREASE: If = [ F / P -0.25] W /30If = AREA INCREASE FOR BUILDING FRONTAGEF = BUILDING PERIMETER THAT FRONTS ON A PUBLIC WAY OR OPEN SPACE HAVING A WIDTH OF 20' OR MORE : 131 LFP = PERIMETER OF ENTIRE BUILDING : 336 LFW = MIN. PUBLIC WAY WIDTH = 30'AREA INCREASES FOR FRONTAGE AND FIRE SPRINKLER SYSTEM:Aa = {At + [At x If] + [At x Is]}Aa = ALLOWABLE BUILING AREA PER STORYAt = TABULAR BUILDING AREA PER STORY IN ACCORDANCE WITH TABLE 503 (SQUARE FEET) = 6,000If = AREA INCREASE FACTOR DUE TO FRONTAGE AS CALCULATED IN ACCORDANCE WITH SECTION 506.2 = 75% (see above)Is = AREA INCREASE FACTOR DUE TO SPRINKLER PROTECTION AS CALCULATED IN ACCORDANCE WITH SECTION 506.3 = 300% FOR 1-STORY BUILDING (PER SECTION 506.3)→Aa = 6,000 + [6,000 x .14]→Aa = 6,000 +840 →Aa = 6,840 SF.EXISTING BUILDING: NAPROPOSED BUILDING: ASSEMBLY GROUP A-3EXISTING BUILDING CONSTRUCTION TYPE: NAPROPOSED BUILDING CONSTRUCTION TYPE: VbFIRE DETECTION: NAFIRE SUPPRESSION: NABUILDING CODE DATABUILDING OVERVIEW : ALLOWABLE HEIGHT (PER TABLE 503)40 FEET, 1 STORIESHEIGHT AND AREA LIMITATIONS :FIRE RATINGSSTRUCTURAL FRAME:0 HRBEARING WALLS -EXT:0 HRBEARING WALLS -INT:0 HRNON BEARING WALLS:0 HRFLOOR CONSTRUCTION:0 HRROOF CONSTRUCTION:0 HRNEW CORRIDOR WALLS: 0 HREXISTING BUILDING FIRE RATING REQUIREMENTS (Vb)ACCORDING TO TABLE 706.43 HOUR BARRIER WALLS AS SHOWN ON G.107FIRE WALL / BARRIER SEPARATIONPLUMBING REQUIREMENTSOCCUPANT CALCULATIONBASED ON ANTICIPATED PEAK OL FOR ENTIRE BUILDING BUILDING TYPE USED FOR PLUMBING CALCULATIONS PER PLUMBING CODE: ASSEMBLY ( A-3 )OCCUPANCY BASED ON OLF CALCULATIONSTOTAL ANTICIPATED OL: 252 OCCUPANTSFEMALE ANTICIPATED LOAD: 126 OCCUPANTSMALE ANTICIPATED LOAD: 126 OCCUPANTSBASED ON 2012 INDIANA PLUMBING CODE 1 per 1251 per 651 per 2001 per 2002411--2-----6220-67% OF WC*ACTUAL PLUMBING FIXTURES---01--112-311-2--* 2014 INDIANA BUILDING CODE, CHAPTER 29/ SECTION 29, (7) : URINALS MAY BE SUBSTITUTED FOR NOT MORE THAN 67% OF THE REQUIRED MALE WATER CLOSETS IN ASSEMBLY AND EDUCATIONAL OCCUPANCIES.REQUIRED PLUMBING FIXTURESWATER CLOSETSLAVATORIESURINALSSHOWERSDRINKING FOUNTAINSSERVICE SINKSWATER CLOSETSLAVATORIESURINALSSHOWERSDRINKING FOUNTAINSSERVICE SINKSMALEFEMALEMALEFEMALEUNISEXTOTAL1 per 1,0001 PROVIDEDREQ.PROVIDEDREQ.PROVIDEDREQ.PROVIDEDREQ.PROVIDEDREQ.PROVIDEDREQ.---------1-1-1-1WOMEN'SA03MEN'SA04STORAGE104STG.103OLFOL156HOSPITALITY1511OLFOL3615COVEREDPAVILION1524150'92'TABULAR OCCUPANT LOAD (PER 2012 IBC TABLE 1004.1.2 & 2014 INDIANA AMENDMENTS): 252MAXIMUM OCCUPANT LOAD FOR SINGLE DOOR ROOMS ACCORDING TO TABLE 1015.1 : 49MAXIMUM EXIT TRAVEL DISTANCE ACCORDING TO TABLE 1016.2 : WITHOUT SPRINKLER SYSTEM: 200'WITH SPRINKLER SYSTEM: 250'MAX. TRAVEL DISTANCE IN SPRINKLERED AREA : 92'MIN. # OF EXITS OR ACCESS TO EXITS PER STORY (SECTION 1021.2.4) : 2 ON EACH LEVEL REQUIRED AMOUNT OF EXITS PROVIDED ON MAIN LEVEL: 5TABULAR LOADTABULAR WIDTH REQ'DACTUALCAPACITYEXTERIOR EXIT #FACTOREXITING REQUIREMENTS123450.2494949494924.5"24.5"24.5"24.5"24.5"165165ACTUAL CLEAR WIDTHNOMINAL DOOR WIDTH36" 36"0.20.20.20.233"36"16533"36" 36" 33"33"33"165165ASPEN PROJECT #:SEAL:9645 Lincoln-Way Lane Suite 201 Frankfort, IL. 60423PRE-GP/PERMIT SETCOPYRIGHT ASPEN GROUP INC. USE OF THESE DOCUMENTS SHALL BE RESTRICTED TO THE ORIGINAL SITE FOR WHICH THEY WERE PREPARED, PUBLICATION THEREOF IS EXPRESSLY LIMITED TO SUCH USE. RE-USE, REPRODUCTION, OR PUBLICATION IN WHOLE OR IN PART IS PROHIBITED. READ DIMENSIONS. DO NOT SCALE DRAWINGS. REPORT ANY INCONSISTENCIES TO THE ARCHITECT IMMEDIATELY. EXPIRES:6/22/2022 3:51:23 PMCollege Park Church -Outdoor Pavilion07-00552606 West 96th Street, Indianapolis, ING.105BUILDING DATA3/16" = 1'-0"1MAIN LEVEL LIFE SAFETY PLANREVISIONSNo. Date By DescriptionA 06/ 20/ 2022 Pre-GP / Permit Set