HomeMy WebLinkAbout2020-08-04_Full_plan_design_release04292005_modified.pdfELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 1/3
CONSTRUCTION DESIGN RELEASE
State Form 41191 (R9/5-98)
Report Printed on: August 4, 2020
Project number Release date
416901 08/03/20
Construction type Occupancy classification
Scope of release
I-B, SPK A-3, ADD, REM, S-2
Type of release
Project name
Street address
City County
ARCH ELEC FDN MECH
PLUM STR
Standard
Carmel Clay Public Library Renovation
55 4th Ave SE
CARMEL HAMILTON
To: Owner / Architect / Engineer
RATIO Architects, Inc.
William A Browne AR00034154
101 S. Pennsylvania St.
Indianapolis IN 46204
Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
14B
4G0412AC
14W1104A
A2
ABPV
14B10099
14B0505
14B050522
This project has been reviewed under the 2014 Indiana Building Code.
NOTE: This projects has the following:
Remodel of the existing library.
Addition to the existing library.
Construction of a parking garage.
No addition or alteration shall cause an existing building, structure, or any part of the permanent
heating, ventilating, air conditioning, electrical, plumbing, sanitary, emergency detection, emergency
communication, or fire or explosion suppression systems to become unsafe or overloaded under
the provisions of the rules of the Commission for new construction in accordance with 675 IAC 12-4-
12(c).
Required means of egress shall be maintained during construction and demolition, remodeling or
alterations and additions to any building, in accordance with Section 1104, IFC (675 IAC 22-2.5).
An elevator installation permit shall be obtained from the Elevator Safety Division in accordance with
IESC (675 IAC 21-1-1). Please visit: http://www.in.gov/dhs/2374.htm
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 2/3
14B2902
9E21008
9E21063
9E51112
14B1600
14B11012
14B03113
14B16082
4G0603AE
4G0603AF
AREL
NOTE: Flexible air ducts, both metallic and nonmetallic, shall comply with Sections 603.6.1,
603.6.1.1, 603.6.3 and 603.6.4, IMC. Flexible air connectors, both metallic and nonmetallic, shall
comply with Sections 603.6.2 through 603.6.4, IMC, in accordance with Section 603.6, IMC.
Plumbing facilities shall be provided in accordance with Chapter 29 and Table 2902.1, IBC (675 IAC
13-2.6).
Commercial bathrooms, kitchens, and rooftops shall be provided with GFCI protection in
accordance with Section 210.8, IEC (675 IAC 17-1.8).
A GFCI protected receptacle shall be located within twenty-five (25) feet of Heating/Cooling
Equipment in accordance with Section 210.63 and 210.8 (b) IEC (675 IAC 17-1.8)
Where electrical portable hand tools or portable lighting is used GFCI protection shall be provided in
accordance with Section 511.12, IEC (675 IAC 17-1.8).
Buildings, or portions thereof, shall be designed and constructed to sustain all dead, live, and
environmental loads in accordance with Chapter 16, IBC (675 IAC 13-2.6).
Buildings and facilities shall be designed and constructed to be accessible in accordance with
Section 1101.2, IBC (675 IAC 13-2.6) and ICC standard A117.1 2009 edition (675 IAC 13-2.6).
Buildings classified as S-2 Occupancies (low-hazard storage) shall only store items described in
accordance with Section 311.3, IBC (675 IAC 13-2.6).
Footings shall have a minimum depth in accordance with Table 1608.2 (Indiana Amendments), IBC
(675 IAC 13-2.6).
Detailed plans and specifications of the fire suppression system shall be filed with the required
application and appropriate fees in accordance with 675 IAC 12-6-3(a), 675 IAC 12-6-7(g)(17), and
675 IAC 13-1-8. (N.F.P.A. 13)
NOTE; This is for the parking structure and the additional area to the library..
Detailed plans and specifications for the revised fire suppression system shall be filed with the
required application and appropriate fees in accordance with 675 IAC 12-6- 3(a), 675 IAC 12-6-
7(g)(17), and 675 IAC 13-1-8. (N.F.P.A. 13)
Note; This refers only to the remodeled area in the library.
Pursuant to 675 IAC 12-6-21, the issuance of a design release does not relieve the owner from
required compliance with all applicable rules of the commission, even if noncompliant conditions
appear in the plans and specifications that have been filed with the division. The owner is
responsible for correcting any and all areas of noncompliance even if they are discovered
subsequent to the issuing of this design release.
This order is effective upon service. If you would like to request informal review of this order, please complete the informal review form located at
https://www.in.gov/dhs/4149.htm. Following receipt of this form, the Department may modify or reverse the order, however, a request for an informal
review does not extend the deadline for filing a petition for review with the Fire Prevention and Building Safety Commission (Commission).
Additionally, if you have any questions regarding this order, you may contact that Department at (317) 232-2222.
If you desire a formal administrative review of this order by the Commission, you must comply with the requirements of Indiana Code § 4-21.5-3-7
and file a written petition for review within 15 days of the date this order was served, however, this period is extended to 18 days if service is made by
mail. Your petition for review must state facts demonstrating that you are: (1) a person to whom the order is specifically directed; (2) aggrieved or
adversely affected by the order; or (3) entitled to review under any law. You may submit your petition by the following methods:
U.S. MAIL OR PERSONAL SERVICE ONLINE
Fire Prevention and Building Safety Commission By completing the form at
c/o Legal Counsel https://www.in.gov/dhs/4148.htm
302 W. Washington Street, Rm. E208
Indianapolis, IN 46204
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http://www.in.gov/dhs/2650.htm.
This on-line filing is through a secure site, you can use it to submit your project information, pay the fees and upload your project plans.
Use Internet Browser to View this report, other browsers are not compatible to view this report
Page 3/3
Code review official
Address (name,title of local official,street,city,state and ZIP code
DAUDA ISHOLA-GBENLA
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL, IN 46032
DEPT OF COMMUNITY SERVICE
Fax & e-mail: 3175712499, jblanchard@carmel.in.gov
dishola-gbenla@dhs.in.gov Indiana State Building Commissioner
For additional information about the administrative review process and applicable templates that may be used for filings, visit the following link
https://www.in.gov/dhs/appeals.htm.
NOTE: A boiler installation permit shall be obtained from the Boiler and Pressure Vessel Safety
Division in accordance with 675 IAC 12-3-13, GAR.
All stairways shall be built of materials consistent with types permitted for the type of construction of
the building, except that wood handrails shall be permitted for all types of construction in
accordance with Section 1009.9, IBC (675 IAC 13-2.6).
The design and construction of mezzanines and equipment platforms shall be in accordance with
Section 505, IBC (675 IAC 13-2.6).
The means of egress for mezzanines shall comply with the applicable provisions of Chapter 10, in
accordance with Section 505.2.2, IBC (675 IAC 13-2.6).
Indiana Department of Homeland Security
DIVISION OF FIRE & BUILDING SAFETY
PLAN REVIEW DIVISION
402 W. Washington St., Room E245
Indianapolis, IN 46204
Fax & e-mail:
SUPPORT HOOSIER SAFETY
Available At Your Local Licence Branch
In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
3176334153, asgro@ratiodesign.com