HomeMy WebLinkAboutS-400 - TYPICAL CONCRETE DETAILSTYPICAL DETAIL OF CONCRETE
COLUMN (TYP.)S3" MAX.3" MAX.U.N.O.LTSBEND BARS INTO SLAB
WHEN NOT POSSIBLE
FLOOR/ROOF
SLAB
TYPICAL DETAIL OF CONCRETE COLUMN AT
UPSET BEAM OR STEP IN FRAMED SLAB
COLUMN LTS(U.N.O.)COLUMN
CONSTRUCTION
JOINT
COLUMN
CONSTRUCTION
JOINT
FLOOR
SLAB
(TYP.)
PLACE THIS PART OF CONC.
COLUMN MONOLITHICALLY
WITH BEAM AND SLAB.
CONCRETE STRENGTH TO
BE GREATEST OF BEAM,
SLAB OR COLUMN
ELEVATION
PLA
INTERIOR
TYPICAL STUDRAIL
EDGECORNER
TYPICAL STUDRAIL LAYOUT
D0.56D0.5D2.5D
3"1 1/2"
3"
NARROW
SIDE
LONGSIDELONGSIDENARROW
SIDE
FACE
OF COLUMN
(TYP.)
SPACED
EQUALLY
TO CORNERS OF COLUMNS
PLACE STUDRAILS ADJACENT
10 TIMES STUD AREA
HEAD AREA IS MINIMUM
SEE PLAN FORSLAB THICKNESSNUMBER OF STUDS)
(SEE TYPES FOR
N = 1/2"Ø STUDS
BASE RAIL
TYPE D1: Z RAILS x Z STUDS/RAIL
AS SHOWN U.N.O. (TYP.)2" CLR.(TYP.)2" CLR.(TYP.)TYPE D4: Z RAILS x Z STUDS/RAIL
TYPE D2: Z RAILS x Z STUDS/RAIL
TYPE D3: Z RAILS x Z STUDS/RAIL
TYPE D5: Z RAILS x Z STUDS/RAIL
EQUALLY
SPACED
(TYP.)
(TYP.)SPACED
EQUALLY
AS SHOWN U.N.O. (TYP.)
PLACE STUDRAILS ADJACENT
TO CORNERS OF COLUMNS
AS SHOWN U.N.O. (TYP.)
PLACE STUDRAILS ADJACENT
TO CORNERS OF COLUMNS
(NOTE: DISTRIBUTE RAILS EQUALLY OVER EACH FACE U.N.O.)
CLEAR COVER (SEE
GENERAL NOTES)
NOTES:
1) STUD RAILS AS MANUFACTURED BY DECON OR ENGINEER-OF-RECORD
APPROVED EQUAL.
2) "D" IS THE STUD DIAMETER.
3) PLACEMENT LOCATIONS ARE SHOWN ON FRAMING PLANS.
TYPE D7: Z RAILS x Z STUDS/RAIL
TYPE D8: Z RAILS x Z STUDS/RAIL
CLEAR COVER (SEE
GENERAL NOTES)
SMALL OPENING
M.E.P. SLEEVE
12"Ø MAX.Ld(TYP.)2" CLR.
(TYP.)
(1) #5
(T&B) (TYP.)
NOTE:
SEE M.E.P. DRAWINGS
FOR LOCATION OF SLEEVES
1
'
-
8
"
2"
PLAN
ADDITIONAL INSIDE CORNER
(2) #5 x 5'-0"
2" CLEAR FROM
TOP & BOTTOM
OF SLAB3"3"NOTE: NOT REQUIRED IF SLAB EDGES ARE SUPPORTED BY BEAM OR WALL.
MULTIPLE SLAB
D ¦D ¦D D D
2'-0" MIN.
D ¦D ¦D D D ¦D ¦D D D
2'-0" MIN.
D D ¦D¦D
LARGE
2'-0" MIN.8"1'-6"D
LARGE
OUTLINE OF EFFECTIVE
OPENING (TYPICAL)
NOTES:
1) PROVIDE (1) #5 (T&B) TRIM BARS ALL AROUND EFFECTIVE OPENING.
EXTEND BARS A MINIMUM OF Ld PAST THE EDGE OF OPENING.
DIAGONAL BARS ARE NOT REQUIRED AT THESE CONDITIONS.
2) IF THE EFFECTIVE LENGTH OF AN OPENING IS GREATER THAN
3'-0", USE THE TYPICAL SLAB OPENING DETAIL FOR THE
REINFORCING REQUIREMENTS.
2'-1 1 "
7"7"7"7"7"5" 5"5" 5"5" 5" 5" 5"5"
3 '-9"
8"
1 '-6"
3 '-1"
8"8"7"7"7"
PLAN
ADDITIONAL OUTSIDE CORNER
(2) #4x8'-0"
(3) #4x5'-0"
TYPICAL VERTICAL CONSTRUCTION
JOINT IN CONCRETE WALL
TYPICAL VERTICAL CONTROL
JOINT IN CONCRETE WALL
3"
TYP.EQ.EQ.EQ.1 1/2"
KEY
3"
TYP.
CUT ALTERNATING HORIZONTAL
BARS AT JOINTS ON EACH FACE
WHERE BARS ARE #5 OR SMALLER
PROVIDE KEY WHERE
CONST. JOINT OCCURS
AT CONTROL JOINT
INTERIOR FACE
EXTERIOR FACEVERT.
REINF.
3/4"x3/4" V-JOINT
(SEE ARCH. DWGS.
FOR SEALANT
REQUIREMENTS) (TYP.)
INTERIOR FACEHORIZ. REINF.
VERT.
REINF.
(PROVIDE @ 30'-0" o/c MAXIMUM FOR EXPOSED WALLS)
(NO CONTROL JOINTS IN VAULT WALLS)
HORIZ. REINF.
(CONT. THROUGH
JOINTS)
.
4"
4"
4"
3 1/ 4"
.EQ.EQ.EQ.4"
4"
4"
EXTERIOR FACE
3/4"x3/4" V-JOINT
(SEE ARCH. DWGS.
FOR SEALANT
REQUIREMENTS) (TYP.)
SYNKO-FLEX
WATERSTOP
AS REQUIRED
AT VAULT WALLS
NOTE:
AT VAULT WALLS
HORIZONTAL REINFORCEMENT
AT EXTERIOR
TYPICAL WALL OPENING REINFORCING
(CAST IN PLACE CONCRETE
2" TYP.
Ld (TYP.)
2'-0" MIN.
Ld (TYP.)
2'-0" MIN.
OPENING
(2) #5 EACH LAYER
MIN. (TYPICAL)MIN. (TYPICAL)
(2) #5 EACH LAYER
(2) #5 x 4'-0" EACH LAYER AT (4) CORNERS
OPENING
(NOTE: Ld PER TABLES FOR DEVELOPMENT LENGTH)(1) BAR DIA. OR1" MIN. CLEARANCENOTE: PLACE BARS (EACH LAYER) ON EACH SIDE OF OPENING EQUAL TO
NUMBER OF BARS INTERRUPTED BY OPENING. (REINFORCING TO MATCH SIZE &
NUMBER OF WALL REINF. (2) #5 MIN. TYPICAL)
2"
3/
4
"
8 1 /4"8 1/ 4"
TYPICAL MILD REINFORCED SLAB OPENING
****INTERRUPTED
BARS
ADDED BARS: ADD SAME
DIAMETER BARS EACH
SIDE OF OPENING EQUAL
TO AT LEAST 1/2 TOTAL
NUMBER OF
INTERRUPTED BARS.
(MIN. (1) #4 TOP &
BOTT. EACH SIDE).
INTERRUPTED
BARS
INTERRUPTED
BARS
INTERRUPTED
BARS
(TYPICAL UNLESS NOTED OTHERWISE ON PLAN)
(2) #5x4'-0"
WITHIN EACH LAYER,
TYPICAL AT
EACH CORNER
NOTES:
1) "*" = EXTEND 2.0 Ld PAST EDGE OF OPENING.
2) HOOK ALL INTERRUPTED BARS.
3) OMIT ADDED BARS IF STANDARD BAR SPACING CAN BE PLACED ON EITHER SIDE
OF THE OPENING.
4) WHERE OPENINGS ARE NEAR OR AGAINST EXTERIOR BEAMS OR COLUMNS AND
ADDED REINFORCEMENT CANNOT BE EXTENDED 2.0 Ld, HOOK ADDED BARS.
1'-7"
1
'
-
4
"
1
'
-
4
"
1 '-7"
TYPICAL DETAIL OF VERTICAL CONCRETE COLUMNSS (TYP.)COLUMN
COLUMN 3"MAX.LTS(U.N.0.)S/2S(TYP.)SS (TYP.)COLUMN
COLUMN 3" MAX.LTS(U.N.0.)LTS(U.N.0.)S/2S (TYP.)SS (TYP.)COLUMN
COLUMN LTS(U.N.0.)LTS(U.N.0.)h0"
(TYP.)
0"
(TYP.)
NOTE: IN TIED COLUMNS, THE TOTAL AMOUNT OF REINFORCEMENT IN LAPPED SPLICE SHALL NOT
EXCEED A STEEL RATIO OF 8% IN ANY THREE FEET LENGTH OF COLUMN. IF STEEL RATIO
EXCEEDS 8% USE LENTON COUPLERS TO CONNECT VERTICAL REINFORCING BETWEEN LIFTS.3" MAX.LTS(U.N.O.)S/20"
(TYP.)S(TYP.)1
6
FLOOR
SLAB
ADDITIONAL (2)
TIES @ BEND,
MAX. SPACING 6"
3" MAX. SEE "TYPE B"
WHEN OFFSET IS
LARGER THAN 3"
TYPE A - WHEN COLUMN IS OFFSET
BY LESS THAN 3"
FLOOR
SLAB
SEE "TYPE A"
WHEN OFFSET IS
LESS THAN 3"
TYPE B - WHEN COLUMN ABOVE IS SMALLER
THAN COLUMN BELOW
BEND BARS
INTO SLAB
FLOOR
SLAB
TYPE C - WHEN COLUMN SIZE ABOVE IS
LARGER THAN COLUMN BELOW
ADD DOWELS IF AREA
OF REINF. IN COLUMN
ABOVE IS LARGER THAN
COLUMN BELOW.
WHEN OFFSET IS
GREATER THAN
h/4, SEE SPECIFIC
DETAIL
DOWELS SIZE AND
NUMBER TO MATCH
LARGER OF UPPER
AND LOWER COLUMN
ADD DOWELS IF AREA
OF REINF. IN COLUMN
ABOVE IS LARGER
THAN COLUMN BELOW
BOTTOM
OF BEND
TYPICAL CONCRETE COLUMN TIE
REINFORCING DETAILS/2S (TYP.)ZS (TYP.)COLUMN
COLUMN3" MAX.NOTES :
1) SIZE AND SPACING OF INTERMEDIATE TIES SHALL BE THE SAME AS TABULATED
ABOVE UNLESS NOTED OTERWISE ON COLUMN SCHEDULE.
2) IF BEAMS FRAME FROM FOUR DIRECTIONS INTO COLUMN WITH TOP
ELEVATIONS EQUAL, TIES MAY BE TERMINATED NOT MORE THAN 3" BELOW
LOWEST REINFORCING IN THE SHALLOWEST BEAM.
3) SEE TYPICAL CONCRETE COLUMN DETAIL FOR TIE CONFIGURATIONS.
4) SEE TYPICAL DETAIL OF VERTICAL CONCRETE COLUMN REINFORCEMENT FOR
ADDITIONAL INFORMATION.
#5 #3 @ 10"*
#6 #3 @ 12"*
#7 #3 @ 14"*
#8 #3 @ 16"*
#9 #3 @ 18"*
#10 #3 @ 18"*
#11 #4 @ 18"*
MAX. SPACING
"S" OF COLUMN
TIES
FLOOR SLAB
ADDITIONAL (2)
TIES @ BEND,
MAX. SPACING 6"* TIE SPACING NOT TO
EXCEED LEAST COLUMN
DIMENSION
VERTICAL TIE SIZE
BAR AND
SIZE SPACING*
ADD TIES WHERE
'Z' DIMENSION >
TYP. TIE SPACING.
BOTTOM
OF BEND
PROVIDE ADDITIONAL
TIE WITHIN 6" OF
START OF BEND
TIE
(3) TIES @ 3" @
ENDS OF ALL
SPLICES
TYPICAL CONSTRUCTION JOINT
IN
IN FRAMED
1 1/2"D/3D/3D/3D5'-0"
TOP & BOTT. BARSTO RUN THROUGH JOINT
ADD (1) #6 x 5'-0"
FOR EACH 8" OF BEAM
WIDTH (MIN. OF (2) BARS)
ADD (2) #6 x 5'-0"
IF NO CONT. TOP BARS
BARS TO RUN
THROUGH JOINT
ADD BARS SAME SIZE
& SPACING AS BOTT. BARS
@ ® OF SPANU.N.O. ON PLAN
1 1 /2"
1 1/2"1 1 /2"
1
'
-
0
"
4"
4"
4"
@ ® OF SPAN
U.N.O. ON PLAN
D/3D/3D/3D1'-0
"
4"
4"
4"
5'-0"
TYPICAL TWO-WAY STRUCTURAL SLAB DETAIL
0.3 GREATER L1 OR L2
0.2 GREATER L1 OR L2
ADDITIONAL TOP BARS - LENGTH
L1
DISCONTINUOUS END
ADDITIONAL TOP BARS - LENGTH
6" MIN.
2" CLEAR
L2
CONTINUOUS END
0.3 GREATER L1 OR L2
0.2 GREATER L1 OR L2
h.3 L1 - 50%
.2 L1 - BAL. }ALT.50% MIN.
BAL. ALT.}
SEE GENERAL
NOTES
SEE STANDARD
HOOK DETAIL
SUPPORT
WIDTH
SEE NOTE #3
FOR ALL TOP
BARS
(MIN. LTS)
(MIN. LTS)(MIN. LTS)
NOTES:
1) ALL BOTTOM BARS MUST BE CONTINOUS OR SLPICED OVER THE SUPPORT WITH LAP SPLICE (EQUAL TO LTS).
A MINIMUM OF (2) BARS IN EACH DIRECTION MUST PASS WITHIN THE COLUMN CORE AND ANCHORED AT EXTERIOR
SUPPORTS.
2) SEE TYPICAL PLAN OF TOP AND BOTTOM BARS IN COLUMN STRIP DETAIL FOR MORE INFORMATION.
3) CONTINUOUS BOTTOM BARS MUST BE ANCHORED PER STANDARD HOOK DETAIL.
4) ALL TOP BARS MUST BE CONTINUOUS OR SPLICED AT MIDSPAN BETWEEN SUPPORTS WITH CLASS 'B' LAP
SPLICE (EQUAL TO LTS).
0.15L
SEE NOTE 1
0.15L 0.15L
#5 CONT. SUPP. BAR w/
INDIVIDUAL HI-CHAIRS
@ 4'-0" o/c MAX.
TYPICAL PLAN OF TOP BARS IN COLUMN STRIP
1.5ta1.5ta + 3t COLUMN STRIPMIN. 3" o/c
25% TOP BARS25% TOP BARS50% TOP BARS25% TOP BARS1.5taa + 3tMIN. 3" o/c50% TOP BARS
25% TOP BARS
COLUMN STRIP
(MILD STEEL REINFORCED TWO-WAY CONCRETE SLAB)MAXIMUMMINIMUMMAXIMUMMAXIMUM
MINIMUM
MAXIMUM
NOTES:
1) ALTERNATE SHORT AND LONG BARS.
2) a = COLUMN WIDTH t = SLAB DEPTH
3) PROVIDE A MINIMUM OF (2) BARS WITHIN
THE COLUMN CORE IN EACH DIRECTION.1'-6"1'-6"4"1 0"4"4" 10 "4"
1 '-6"
1 '-6"
1.5t
2'-9" 1 '-6" 2 '-9"
2'-9"
1'-6"
2'-9"
7'-0"
7'-0"
SHEET TITLE
SHEET NUMBER
KITE Realty Group
30 S. Meridian Street, #1100
Indianapolis, Indiana 46204
Owner
Republic Airways Holdings
RATIO
101 South Pennsylvania Street
Indianapolis, Indiana 46204
317-633-4040
Architect
McComas/O'Donnell & Naccarato
Structural Engineer
Civil Engineer
8909 Purdue Road, Suite 300
Indianapolis, Indiana 46268
450 East 96th Street, Suite 175
Indianapolis, IN 46240
317-580-0402
Kimley Horn
250 East 96th Street, Suite 580
Indianapolis, Indiana 46240
PROJECT NO.
SHEET ISSUE
SEAL | DATE
COPYRIGHT NOTICE: THIS ARCHITECTURAL
AND ENGINEERING DRAWING IS GIVEN IN
CONFIDENCE AND SHALL BE USED ONLY
PURSUANT TO THE AGREEMENT WITH RATIO.
NO OTHER USE, DISSEMINATION OR
DUPLICATION MAY BE MADE WITHOUT PRIOR
WRITTEN CONSENT OF RATIO. ALL COMMON
LAW RIGHTS OF COPYRIGHT AND OTHERWISE
ARE HEREBY SPECIFICALLY RESERVED.
450 EAST 96th STREET, SUITE 175, INDIANAPOLIS, IN 46240
(317) 580-0402 | WWW.O-N.com | Project No. 7167.0013.00
FOUNDATION PERMIT
07/08/2022
F.A. Wilhelm Construction
3914 Prospect Street
Indianapolis, Indiana 46203
317-359-5411
Construction Manager
Mechanical / Electrical/ Plumbing Engineer
CIRCLE DESIGN GROUP
9229 Delegates Row #150
Indianapolis, Indiana 46240 BIM 360://22014-Republic Airways HQ/Republic_Garage-STRC-V21.rvt7/8/2022 3:35:47 PMS-400
TYPICAL CONCRETE
DETAILS
21040.000
REPUBLIC
CAMPUS -
PARKING
GARAGE
12195 N. Meridian St.
Carmel, Indiana
46032
1 FOUNDATION PERMIT 07/08/22
07/08/22
08/09/22