HomeMy WebLinkAboutControl SummaryAll new lighting is removed
from this project. Courts as
submitted with this project can
be open during daylight hours.
Control System Summary
Project Information
Project #:224190
Project Name:Woodland Country Club
Date:12/12/22
Project Engineer:Joe Seda
Sales Representative:Brent Castle
Control System Type:Control-LinkTM Control and Monitoring System
Communication Type:PowerLine-ST
Scan:224190A
Document ID:224190P1V2-1212153019
Distribution Panel Location or ID:Service 1
Total # of Distribution Panel Locations for Project:1
Design Voltage/Hertz/Phase:208/60/3
Control Voltage:120
Equipment Listing
DESCRIPTION APPROXIMATE SIZE
1.Control and Monitoring Cabinet 24 X 48
QTY SIZE (AMPS)
Total Contactors 4 30 AMP
Total Off/On/Auto Switches: 2
Project Specific Notes:
This service includes a pushbutton/strobe
assembly for (NORTH COURTS ZONE 1).
This summary accounts for future product
for the south courts.
Materials Checklist
Contractor/Customer Supplied:
A dedicated control circuit must be supplied
per distribution panel location
If the control voltage is NOT available,
a control transformer is required
Electrical distribution panel to provide
overcurrent protection for circuits
HID rated or D-curve circuit breaker sized
per full load amps on Circuit Summary by
Zone Chart
Wiring
See chart on page 2 for wiring requirements
Equipment grounding conductor and splices
must be insulated (per circuit)
Lightning ground protection (per pole), if
not Musco supplied
Electrical conduit wireway system
Entrance hubs rated NEMA 4, must be
die-cast zinc, PVC, or copper-free
die-cast aluminum
Mounting hardware for cabinets
Breaker lock-on device to prevent
unauthorized power interruption to control
power and powerline connection (if present)
Anti-corrosion compound to apply to ends of
wire, if necessary
Call Control-Link CentralTM operations center
at 877/347-3319 to schedule activation of the
control system upon completion of the installation.
Note: Activation may take up to 1 1/2 hours.
IMPORTANT NOTES
1. Please confirm that the design voltage listed above is accurate for this
facility. Design voltage/phase is defined as the voltage/phase being connected
and utilized at each lighting pole's electrical components enclosure disconnect.
Inaccurate design voltage/phase can result in additional costs and delays.
Contact your Musco sales representative to confirm this item.
2. In a 3 phase design, all 3 phases are to be run to each pole. When a 3 phase
design is used Musco's single phase luminaires come pre-wired to utilize all 3
phases across the entire facility.
3. One contactor is required for each pole. When a pole has multiple circuits, one
contactor is required for each circuit. All contactors are 100% rated for the
published continuous load. All contactors are 3 pole.
4. If the lighting system will be fed from more than one distribution location,
additional equipment may be required. Contact your Musco sales representative.
5. A single control circuit must be supplied per control system.
6. Size overcurrent devices using the full load amps column of the Circuit Summary
By Zone chart- Minimum power factor is 0.9.
NOTE: Refer to Installation Instructions for more details on
equipment information and the installation requirements.
C 1999,2022 Musco Sports Lighting,LLC
Form: T-5030-1T:\224\224190P1V2-1212153019.pdf
Control System Summary
Woodland Country Club / 224190 - 224190A
Service 1 - Page 2 of 4
T:\224\224190P1V2-1212153019.pdf
Control System Summary
Woodland Country Club / 224190 - 224190A
Service 1 - Page 3 of 4
T:\224\224190P1V2-1212153019.pdf
CONTROL POWER CONSUMPTION
120V Single Phase
VA loading
of Musco
Supplied
Equipment
INRUSH: 980.0
SEALED: 104.0
SWITCHING SCHEDULE
Field/Zone Description Zones
Pickleball 1
Tennis 1 1
Tennis 2-3 2
CIRCUIT SUMMARY BY ZONE
POLE CIRCUIT DESCRIPTION # OF
FIXTURES
# OF
DRIVERS
*FULL
LOAD
AMPS
CONTACTOR
SIZE (AMPS)
CONTACTOR
ID
ZONE
T1 North Courts 3 3 10.6 30 C1 1
T2 North Courts 3 3 10.6 30 C2 1
T2 South Courts 3 3 10.6 30 C3 2
T3 South Courts 3 3 10.6 30 C4 2
*Full Load Amps based on amps per driver.
Control System Summary
Woodland Country Club / 224190 - 224190A
Service 1 - Page 4 of 4
T:\224\224190P1V2-1212153019.pdf
PANEL SUMMARY
CABINET
#
CONTROL
MODULE
LOCATION
CONTACTOR
ID
CIRCUIT DESCRIPTION FULL
LOAD
AMPS
DISTRIBUTION
PANEL ID (BY
OTHERS)
CIRCUIT
BREAKER
POSITION (BY
OTHERS)
1 1 C1 Pole T1 10.63
1 1 C2 Pole T2 10.63
1 1 C3 Pole T2 10.63
1 1 C4 Pole T3 10.63
ZONE SCHEDULE
CIRCUIT DESCRIPTION
ZONE SELECTOR
SWITCH
ZONE DESCRIPTION POLE ID CONTACTOR
ID
Zone 1 1 North Courts T1 C1
T2 C2
Zone 2 2 South Courts T2 C3
T3 C4