HomeMy WebLinkAbout05090231 Misc. (I"', V (, c1' (J ~l ~-T(' v ! v 7" ( l\UI / -...,.-. ) Matthew D. Holbrook STRUCTURAL ENGINEER GI30 Carrofltol1 Avenue, !ndianapohs. lthli:m;l .:~CJ:?20 P1Hllle:(317) 257.67 JO Field Report OATE I JOB',,;) Fehruary 2, 2006 PHOJEcr ~TE~9Ltt2~-~?~9nJb_~_~?n,:,,~~ C2!~.ClQ!!~~.~~~~L~~~ildi~~... iDeATION Mr, Kevin Brand Cenlex Homes 8440 Allison Poinle Blvd. #200 Indianapolis. IN 46250 40 8.30 elM IN Matthew Holhrook Kevin Brand THE FOllOWING WAS NOTED: 1. The purpose of the site visit was to observe the condition of the rapalr to the fire rated separation In building 3 2. The repair to the rated panes was performed adequately by Installlng2x lumber blocking below the top chord of the end truss, then Installing 2 layers of 518" type X gyp-board to the sides of the gable trusses and turning the 2 layers In a horizontal cap that Is tight to the rated liner panel. With this additional gyp-board Installed the assembly will provide the necessary fire separation. See sketch below. This detail may be used for all futura Instances of this problem. l/ .... (~~ ~~-~ _._~.L"--.. ~~rJl<1 ~<=- "TfZ..U $S"E. <; 1 , I I \ I I, ___Nw 'Z~ Be k" .,c" ~-n.~,., "tQJ,.~ ~'i. 1..w..;.+.iJL,S t>P" ,,~. n" )( {"-,(f ~MtP I 1 I A.l- ~D?~ . _ -,;,-/; ;)I/I/Jl.l7d/j/ ! f/L{J(J/I' Matthew D. Holbrook P.E.. S.E.