E108 - E203 - Kitchen Ventilation Details
COOKING APPLIANCE TYPE I INTERLOCK 1. REMOTE SWITCH ON - POWER TO KFCC 2. KFCC CONTROLS: a. PRV-2 (GRILL) & PRV-3 (FRYERS) ARE STARTED. b. OPENS OUTSIDE AIR INTAKE ON RTU-1 & RTU-2 TO MINIMUM FRESH AIR OPENING. c. POWER TO OUTLETS #51 (GRILL) AND #60 (FRYERS) 3. GRILL AND FRYER CAN BE STARTED 4. IN CASE OF FIRE: a. SHUNT TRIP FOR GRILL & FRYER OUTLET TRIPS b. ANSUL SYSTEM IS ACTIVATED c. THE MECHANICAL GAS VALVE CLOSES d. SHUT DOWN RTU-1 & RTU-2 & CLOSE OUTSIDE AIR e. PRV-2 & PRV-3 CONTINUE TO RUN 2. PRESS THE UP/DOWN ARROW BUTTON TO CHANGE THE SET POINT. 3. PRESS THE SET BUTTON TO VIEW THE CURRENT TEMPERATURE. 4. CHECK SYSTEM OPERATION BEFORE MAKING ADDITIONAL ADJUSTMENTS FOR TECHINCAL SUPPORT ON THE KFCC (KITCHEN FAN CONTROL CENTER) CALL EITHER: AARON VAN KREY 715.841.8521 TYLER SCHILLING 715.841.8749 ST1 C1 13 14 D3 ST2 NO1 NC1BR R1 A1 R1 D1 R12 A2 WH WH D2 YW OR H1 S1H S1-1 S1 OR 96 A1 OR A2 ST WHOL 95 96 A1 OR A2 ST WHOL 95 S1N WH N1 DPST TOGGLE SWITCH (BY DIV. 16) S1-2 STB C3 RD 11 12 R2 BK NO3 R2C NO NC FS1 C NO NC FS2 L2 L3 L3 L1 L2 L1 ST T3T3 FAN T1 T2 T1 T2 OL L2 L3 L3 L1 L2 L1 ST T3T3 FAN T1 T2 T1 T2 OL T1-A T1-B T2-A T2-B TS1 TS2 TC1RD68 7 1 2 WH 1513 TC1 2119 TC1 TEMPERATURE INTERLOCK CALIBRATION 1. PRESS THE SET BUTTON TO SEE THE FIRST SET POINT. (PRESS THE SET BUTTON TWICE, SLOWLY TO SEE THE SECOND SET POINT) 2. PRESS THE UP/DOWN ARROW BUTTON TO CHANGE THE SET POINT. 3. PRESS THE SET BUTTON TO VIEW THE CURRENT TEMPERATURE. 4. CHECK SYSTEM OPERATION BEFORE MAKING ADDITIONAL ADJUSTMENTS 11 12 R1 1411 R1 A1 A2 A1 A2 RD RD RD RD CONTROL INPUT: 120VAC, 15AMPS FROM BREAKERL1 N G C4 RD 21 22 R2 BK NO4 R1 BL 11 14 R12 BL G1 R2 BL 21 24 R12 BL G2 13 14 21 24 closed w/power at H1/N1 & fire system armed open w/power at H1/N1 & fire system armed (can be used for shunt trip, alarms, etc.) Spare Relay Contacts closed on fire or no power open on fire or no power 12 14NC3BK C3 NO3 RD BR NO4 NC4 A BR211 C4 22 BK 21 24 RD BR R2 (activated by FS1) CULVER'S CULVER'S ELECTRICAL FIELD CONNECTION INSTALLATION INSTRUCTIONS FRYER AND GRIDDLE RECEPTACLES FED DIRECT FROM BUILDING BREAKER 115/1 20A FROM MAIN BREAKER PANEL (BREAKER SHUNTED FROM CONTROL CENTER TERMINALS NO1 AND N1) 115/1 20A TO FRYER & GRIDDLE RECEPTACLES (RECEPTACLES IN PARALLEL) 115/1 15A POWER FROM MAIN BREAKER PANEL (BLACK), NON SHUNTED 115/1 NEUTRAL FROM MAIN BREAKER PANEL (WHITE) USER INTERFACE (SHIP LOOSE) PROVIDED WITH 50FT CAT5 CABLE ATTACH TO J15 PORT ON MAIN BOARD C NC NO C NC NO ACCUREX CONTROL PANEL CONNECTIONS - CONTROL AND POWER WIRING WIRE NORMALLY-CLOSED CONTACTS ON FIRE MICRO-SWITCHES IN EACH FIRE SUPPRESSION SYSTEM IN SERIES AND CONNECT TO FS-C AND FS-NC IN CONTROL PANEL FIRE MICRO-SWITCH IN GRIDDLE FIRE SUPPRESSION RELEASE FIRE MICRO-SWITCH IN FRYER FIRE SUPPRESSION RELEASE TO RTU 1 SHUTDOWN IN FIRE (CONTACT WILL OPEN IN FIRE) TO RTU 1 SHUTDOWN IN FIRE (CONTACT WILL OPEN IN FIRE) TO RTU 1 OUTSIDE AIR DAMPER (CONTACT WILL CLOSE WHEN EXHAUST FANS ARE RUNNING) TO RTU 1 OUTSIDE AIR DAMPER (CONTACT WILL CLOSE WHEN EXHAUST FANS ARE RUNNING) TO RTU 2 OUTSIDE AIR DAMPER (CONTACT WILL CLOSE WHEN EXHAUST FANS ARE RUNNING) TO RTU 2 OUTSIDE AIR DAMPER (CONTACT WILL CLOSE WHEN EXHAUST FANS ARE RUNNING) TO GRIDDLE & FRYER SHUNT TRIP BREAKER COIL (115VAC) AT MAIN PANEL H1 N1 C1 NO1 NC1 C2 NO2 NC2 TO RTU 2 SHUTDOWN IN FIRE (CONTACT WILL OPEN IN FIRE) TO RTU 2 SHUTDOWN IN FIRE (CONTACT WILL OPEN IN FIRE) C3 NO3 NC3 S1-R S1-G S2-R S2-G J15 RJ45 PORT FS-C FS-NC (JUMP 115VAC TO C1 TERMINAL) TS-1A TO TEMP SENSOR 1 IN FRYER HOOD TO TEMP SENSOR 1 IN FRYER HOOD TO TEMP SENSOR 2 IN GRIDDLE HOOD TO TEMP SENSOR 2 IN GRIDDLE HOOD TS-1B TS-2A TS-2B (LOW VOLTAGE - USE 18/2) (LOW VOLTAGE - USE 18/2) (LOW VOLTAGE - USE 18/2) MAIN PCB BOARD (MB) 50FT CAT5 CABLE ACCUREX CONTROL PANEL TORQUE MAIN CONTROL TERMINAL BLOCKS TO 8 LBS IN. TORQUE MAIN PCB BOARD SCREW TERMINALS TO 3.5 LBS IN. L1 L2 L3 L1 L2 L3 MOTOR STARTER (CN-E1 & OL-E1) MOTOR STARTER (CN-E2 & OL-E2) T1T2 T3 T1T2 T3 208/3 15A POWER FROM MAIN BREAKER (POWER FOR FRYER FAN) 208/3 15A POWER FROM MAIN BREAKER (POWER FOR GRIDDLE FAN) 208/3 15A POWER TO FRYER FAN DISCONNECT 208/3 15A POWER TO GRIDDLE FAN DISCONNECT ACCUREX CONTROL PANEL ACCUREX CONTROL PANEL CONNECTIONS - EXHAUST FAN CONNECTIONS KEY DESIGNATES FIELD CONNECTION CULVER'S INSTALLATION AND OPERATION GUIDE Mechanical Scope of Work 1) Mechanical Contractor to mount Accurex Control Panel (Model XKC, 18" W x 20" H x 6" D) in specified location above drop ceiling. 2) Assuming all electrical has been completed by Electrical Contractor, Mechanical Contractor to start up fans by pressing "Fans" button on user interface. Verify power to exhaust fans. Electrical Scope of Work 1) Electrical Contractor shall provide one 115VAC 20A circuit with shunt trip breaker (115VAC trip coil) for fryer and griddle receptacles. This circuit will have thee receptacles, two for the fryers and one for the griddle. Circuit to be powered directly from circuit breaker. 2) Electrical Contractor to install Accurex user interface on wall (user interface provided by Accurex, recess into wall). Connect user interface back to Accurex control panel using factory-provided CAT5 cable (connect to J15 port on main board in Accurex control panel). 3) Electrical Contractor to run a separate 115VAC 15A circuit (from non-shunted breaker) to Accurex control panel terminal blocks H1 and N1 to power controls. 4) Electrical Contractor to run two 208/60/3 15A circuits from main breaker panel to each motor starter in the Accurex control panel (L1, L2, L3). Run power from T1, T2, T3 on each motor starter in Accurex control panel to kitchen exhaust fan disconnects. 5) Electrical Contractor to connect jumper wire from terminal block H1 to terminal block C1 in Accurex control panel, and then run wires from NO1 and N1 in Accurex control panel back to 115VAC shunt-trip breaker coil for fryer and griddle receptacles. 6) Electrical Contractor to wire a normally-closed contact off of a micro-switch in each fire suppression system release (one FS for fryer hood, and one FS for griddle hood) in series, and tie this series circuit loop back to FS-C and FS-NC on the main control board (MB) in the Accurex control panel. 7) Electrical Contractor to wire RTU 1 & 2 damper control to Accurex control panel terminal blocks S1-R / S1 - G and S2-R / S2-G as indicated on wiring diagram. 8) Electrical Contractor to wire RTU 1 & 2 control (8 amp max) circuits to Accurex control panel terminal blocks C2 and NC2 for RTU1 and C3 and NC3 for RTU 2 to shut down units in a fire. 9) Electrical Contractor to wire temp sensor in fryer hood collar back to Accurex control panel and land on TS-1A / TS-1B on main PCB board (use 18 to 22ga plenum rated cable) 10) Electrical Contractor to wire temp sensor in griddle hood collar back to Accurex control panel and land on TS-2A / TS-2B on main PCB board (use 18 to 22ga plenum rated cable) Sequence of Operation 1) Make sure fryer and griddle receptacles are receiving power (breaker feeding appliance outlets is on). 2) Make sure RTU 1 & RTU 2 are both receiving power (breaker feeding RTUs are on and RTU disconnects are on). 3) Turn fans on via "Fans" button on user interface. Both fryer and griddle fans should turn on, and RTU 1 & 2 outside air dampers should open/adjust to bring in design OA. 4) Before fire system agent tanks are installed, manually trigger fire system while fan switch is on. This should accomplish the following: - Display on user interface should stated "FIRE DETECTED" - Shunt trip breaker will trip causing a loss of pwoer to fryer and griddle receptacles - Gas valve will close shutting gas off to the fryer and griddle - Exhaust fans will remain on - RTU 1 & 2 will shut down 5) Put fire system in the "cocked" position and reset shunt trip breaker. Breakers feeding appliance outlets should be able to be reset manually, and RTU's power should be restored. 6) Press "Fans" button on the user interface to turn the fans off. This will shut down power to the fans. RTU outside air dampers will close. RTUs will remain operational providing 100% return air only. Accurex Control Panel, Fans, Appliance Receptacles 22 1 EXH 2 EXH 11 2 2 1 1 KITCHEN VENTILATIONWIRING DETAILSE203NEW CULVER'S RESTAURANT431 E Carmel DriveCarmel, IN 46032County of HamiltonDate:Revision:5-25-2022OLLMANN ASSOCIATES ARCHITECTS, P.C.200 South State StreetBelvidere, Illinois 61008815-544-7790 Phone© 2022K&J INVESTMENTS XVI, LLC1448 Conner StreetNoblesville, IN 46060Bob Goins: bgoins@indyculvers.com317-770-4656OWNER:Culver Franchising System, Inc.1240 Water StreetPrairie du Sac, WI 53578608-643-7980®2020-159 © OAA All rights reserved; any copying, transmittal or disclosure subject to OAA written approval. 01/13/23