CONSTRUCTION DESIGN RELEASE
Stale Form 41191 (R915-98)
Report Printed on: June 14, 2006
To: Owner I Architect f Engineer
Simmons Architects LLC
Frederick A Simmons AlA 3135
305 E. New York Street
Indianapolis IN 46204
SUPPORT HOOSIER SAFETY
Scope of release
ARCH ELEC FDN MECH
PLUM STR
Type of release
Standard
Project name
Meridian Corporate Plaza Three
Street address
501 Pennsylvania Pkwy
ax & e-mail: 3176563501.ccartwright@simmonsarchitects.net
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below.-THIS'IS'NOTABUILDING PERMIT.'AIt'required'local permits and licenses must be obtained prior to beginning construction work.. All
construction work. must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications' must be filed with
and released by this Office before any work is altered. This"'release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based o'n incorrect or insuffident [nfclImation. This release shall expire by limitation, arid become null and
void, if the work. authorized is not commenced within one (1) year from:the aboVe date. '
CONDITIONS:
City
CARMEL
County
HAMILTON
Note :(A1A & A 1 B): In accordance with !the affidavit swom under penalties of pe~ury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission, Providing false information constitutes an act of pe~ury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
In accordance with Section 19 of the General Administrative Rules (675 fAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design thafwas released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design.release. .
The Mechanical, Electrical and Plumbing Release includes the Common Areas/Rooms only, IE, Equipment,
Electrlcai, St~irway~,;Elevator and Wash rooms,
4G0603AA - ~ ;-his~p'roject release is for the building shell only and does not include the finish of one or more
. ,tenant spaces. Tenant space finish may be filed as a new project in accordance with 675:IAC 12-6-6
.or as one or more addenda to released systems in accordance with 675 lAC 12-6-18 before
commencing work.
4G0603AE Detailed plans and specifications of the fire suppression system shall be filed with t~e required
application and appropriate fees in accordance with 675 lAC 12-6-3(a) and 675 lAC 13-1-8.
(NFPA 13)
A2 An elevator installation permit shall be obtained from the Elevator Safety Division in accordance with
IESC (675 lAC 21-1-1). (2 passenger, 1 freight)
3B0505A The design and construction of a mezzanine shall be in accordance with Section 505, IBC (675 lAC
13-2.4).
5E25024A 1 A premises wiring system supplied by a grounded ac service shall have a grounding electrode
conductor connected to the grounded service conductor, at each service, in accordance with
Sections 250.24(A), IEC (675 lAC 17-1.7).
5E25024Cl Where an ac system operating at less than 1000 volts is grounded at any point, the grounded
conductor(s) shall be run to each service disconnect and shall be bonded to each disconnect
enciosure in accordance with Section 250.24(C), IEC (675 lAC 17-1.7).
3B0715C Duct penetrations of fire barrier walls shall be protected by fire dampers in accordance with Section
715.5, IBC (675 lAC 13-2.4).
3B0803A Interior finish flame-spread ratings shall comply with Section 803, Table 803.4 IBC (675 lAC 13-2,4).
Page 1/2
3809078
Would you like to reduce your turnaround time?
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA AT
efile24-7@dhs.state.in.us, Or VISIT OUR WEB SITE AT www.in.gov/dhs/osbc
A manual fire alarm system shall be installed in Group 8 occupancies in accordance with Section
907.2.2, 18C (675 lAC 13-2.4).
Please be advised that if an administrative review of this action is desired, a written petition for review must be filed at the above address with the
Fire Prevention and Building Safety Commission identifying the matter for which a review is sought no later than eighteen (1 B) days from the above -
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Building SelVices is closed during normal business hours. In the latter case, the filing deadline will be the first working day thereafter. If you
choose to petition, and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission. If a petition for review is not filed, this Order will
be final, and you must comply with its requirements.
Filed By Code review official Code Enforcement & Plan Review Branch Director
MARY FROSCH U~///S~
Address (name,title of local official,street,city,state and ZIP code
DEPT OF COMMUNITY SERVICE State Fire Marshal V1?,O~
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL, IN 46032
Fax & e-mail: 3175712499, iblanchard@carmel.in.aov
Page 2/2