HomeMy WebLinkAboutE-401 - ELECTRICAL RISER DIAGRAMTRANSFORMER
#2
M
125A-2P
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M M
400A-3P
M
200A-3P
M
200A-3P
M
200A-3P
M
200A-3P
PANEL
C1
120/208
3P, 4W
400A
MLO
PANEL
C2
120/208
3P, 4W
200A
MLO
PANEL
C3
120/208
3P, 4W
200A
MLO
PANEL
C4
120/208
3P, 4W
200A
MLO
PANEL
C5
120/208
3P, 4W
200A
MLO
M
400A-3P
M
200A-3P
M
200A-3P
M
200A-3P
PANEL
C6
120/208
3P, 4W
400A
MLO
PANEL
C7
120/208
3P, 4W
200A
MLO
PANEL
C9
120/208
3P, 4W
200A
MLO
PANEL
C11
120/208
3P, 4W
200A
MLO
COMMERCIAL 1 COMMERCIAL 2 COMMERCIAL 3 COMMERCIAL 4 COMMERCIAL 5 COMMERCIAL 6
COMMERCIAL 7 COMMERCIAL 9 COMMERCIAL 11
PANEL
C8
120/208
3P, 4W
400A
MLO
HOUSE 2 CT CABINET
800A
PANEL
C10
120/208
3P, 4W
400A
MLO
HOUSE 1 CT CABIENT
800A
TRANSFORMER
#1
1000A
MAIN
CIRCUIT
BREAKER
120/208V
3P-4W
65K AIC
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
1000-3N
1000-3N
1200-3N
800-3N
800-3N
1200-3N
800-3NG
800-3NG
M
400A-3P
COMMERCIAL 8
PANEL
H1A
120/208
3P, 4W
800A
MLO
PANEL
H2A
120/208
3P, 4W
800A
MLO
UTILITY
UTILITY
125A-2P
125A-2P
125A-2P
125A-2P 125A-2P 125A-2P 125A-2P 125A-2P
125A-2P 125A-2P 125A-2P 125A-2P
125A-2P 125A-2P 125A-2P 125A-2P
125A-2P 125A-2P 125A-2P 125A-2P
125A-2P 125A-2P 125A-2P 125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
125A-2P
TYPICAL 2/0-2/0-2/0-1 ALUMINUM SER CABLE
TO CABLE TO EACH APARTMENT PANL. INCREASE
WIRE SIZE TO KEEP VOLTAGE DROP BELOW 2% FOR
FEEDERS OVER 100'-0" IN LENGTH.
TYPICAL 2/0-2/0-2/0-1 ALUMINUM SER CABLE
TO CABLE TO EACH APARTMENT PANL. INCREASE
WIRE SIZE TO KEEP VOLTAGE DROP BELOW 2% FOR
FEEDERS OVER 100'-0" IN LENGTH.
TYPICAL 2/0-2/0-2/0-1 ALUMINUM SER CABLE
TO CABLE TO EACH APARTMENT PANL. INCREASE
WIRE SIZE TO KEEP VOLTAGE DROP BELOW 2% FOR
FEEDERS OVER 100'-0" IN LENGTH.
TYPICAL 2/0-2/0-2/0-1 ALUMINUM SER CABLE
TO CABLE TO EACH APARTMENT PANL. INCREASE
WIRE SIZE TO KEEP VOLTAGE DROP BELOW 2% FOR
FEEDERS OVER 100'-0" IN LENGTH.
SOUTH
SOUTH
1200A
MAIN
CIRCUIT
BREAKER
120/208V
3P-4W
65K AIC
1000A
MAIN
CIRCUIT
BREAKER
120/208V
3P-4W
65K AIC
1200A
MAIN
CIRCUIT
BREAKER
120/208V
3P-4W
65K AIC
PV SYSTEM
M
M
M
125A-2P
125A-2P
125A-2P
M
125A-2P
M
125A-2P
M
M
M
M
125A-2P
125A-2P
125A-2P
125A-2P
M
125A-2P
M
M
M
125A-2P
125A-2P
125A-2P
UTILITY TRANSFORMER NOTES
OWNERS NAME:THE CONCOURSE CONTACT #:(???)???-????
ADDRESS:?????EXST SRVC METER #: ?????
CITY, STATE ZIP CODE
NEW SRVC METER #: ?????
UTILITY SERVICE PROVIDER:DUKE
CONTACT NAME: BILL FERRELL CONTACT #: (317)776-5351
EMAIL:Bill.Ferrell@duke-energy.com
MOUNTING TYPE:PAD FEED TYPE: UNDERGROUND
POWER RATING:500 KVA
PRIMARY SECONDARY
CONFIGURATION:DELTA CONFIGURATION:WYE
VOLTAGE: MEDIUM VOLTAGE: 208V
UTILITY RESPONSIBILITIES CONTRACTOR RESPONSIBILITIES
PRIMARY CONDUCTORS, INSTALLATION &
TERMINATION OF SECONDARY CABLES AT
TRANSFORMER, METER BOX/CT CABINET
ORDER INSTALLATION/COORDINATE WITH
UTILITY
INSTALLATION MUST COMPLY WITH UTILITY
STANDARDS/REQUIREMENTS
PRIMARY CONDUITS & INSTALLATION
SECONDARY CONDUITS, FEEDERS,
INSTALLATION & TERMINATION AT MDP OR
MSWBD
METER BOX/CT CABINET INSTALLATION
TRANSFORMER PAD INSTALLATION
UTILITY TRANSFORMER NOTES
OWNERS NAME: THE CONCOURSE CONTACT #: (???)???-????
ADDRESS: ????? EXST SRVC METER #: ?????
CITY, STATE ZIP CODE
NEW SRVC METER #: ?????
UTILITY SERVICE PROVIDER: DUKE
CONTACT NAME: BILL FERRELL CONTACT #: (317)776-5351
EMAIL:Bill.Ferrell@duke-energy.com
MOUNTING TYPE:PAD FEED TYPE: UNDERGROUND
POWER RATING: 750 KVA
PRIMARY SECONDARY
CONFIGURATION: DELTA CONFIGURATION:WYE
VOLTAGE: MEDIUM VOLTAGE: 208V
UTILITY RESPONSIBILITIES CONTRACTOR RESPONSIBILITIES
PRIMARY CONDUCTORS, INSTALLATION &
TERMINATION OF SECONDARY CABLES AT
TRANSFORMER, METER BOX/CT CABINET
ORDER INSTALLATION/COORDINATE WITH
UTILITY
INSTALLATION MUST COMPLY WITH UTILITY
STANDARDS/REQUIREMENTS
PRIMARY CONDUITS & INSTALLATION
SECONDARY CONDUITS, FEEDERS,
INSTALLATION & TERMINATION AT MDP OR
MSWBD
METER BOX/CT CABINET INSTALLATION
TRANSFORMER PAD INSTALLATION
M
125A-2P
MUSEUM
150KVA
XFMR
'T1'
150KVA
XFMR
'T2'
SERV. ELEV. 1 PUB. ELEV. 3
PUB. ELEV. 2PUB. ELEV. 1
PANEL
E1
480/277
3P, 4W
100A
MLO
PANEL
E2
480/277
3P, 4W
100A
MLO
M
400A-3P
COMMERCIAL 10 100-3NG
100-3NG
200-3NG
200-3NG
50-3NG
PANEL
H1B
120/208
3P, 4W
100A
MLO
PANEL
H2B
120/208
3P, 4W
100A
MLO
200-3NG
200-3NG
FEEDER SCHEDULE
NOMINAL
OCP
AMPS
20-#
30-#
40-#
COPPER FEEDERS AND COPPER GROUND
GROUND
SETS
1
1
1
CONDUCTOR
AMPACITY
20A
30A
40A
COPPER
WIRE SIZE
#12
#10
#8
CONDUCTOR
PER CONDUIT
COPPER WIRE
#12
#10
#10
MINIMUM
CONDUIT
SIZE
3/4"
3/4"
3/4"
ALUMINUM FEEDERS AND COPPER GROUND
GROUND
SETS CONDUCTOR
AMPACITY
ALUMINUM
WIRE SIZE
CONDUCTOR
PER CONDUIT
COPPER WIRE
MINIMUM
CONDUIT
SIZE
60-#
70-#
80-#
1
1
1
55A
70A
80A
#6
#4
#3
#10
#8
#8
1"
1 1/4"
1 1/4"
100-#
130-#
150-#
175-#
200-#
225-#
250-#
300-#
350-#
400-#
500-#
600-#
800-#
1000-#
1200-#
1600-#
2000-#
2500-#
3000-#
1
1
1
1
1
1
1
1
1
1
2
2
2
3
4
5
6
7
8
95A
130A
150A
175A
200A
230A
255A
310A
350A
380A
510A
620A
760A
1140A
1240A
1900A
2300A
2660A
3040A
#2
#1
#1/0
#2/0
#3/0
#4/0
250 KCMIL
350 KCMIL
500 KCMIL
500 KCMIL
250 KCMIL
350 KCMIL
500 KCMIL
500 KCMIL
350 KCMIL
500 KCMIL
500 KCMIL
500 KCMIL
500 KCMIL
#8
#6
#6
#6
#6
#4
#4
#4
#3
#2
#2
#1
#1/0
#2/0
#3/0
#4/0
250
KCMIL
350
KCMIL
400
KCMIL
1 1/4"
1 1/2"
2"
2"
2"
2 1/2"
2 1/2"
3"
3"
3 1/2"
3"
3"
3 1/2"
3 1/2"
3"
3 1/2"
3 1/2"
4"
4"
1
1
1
1
1
1
1
1
1
2
2
2
3
4
5
6
7
8
135A
155A
180A
205A
230A
270A
310A
350A
385A
500A
620A
770A
1155A
1240A
1925A
2310A
2695A
3080A
#2/0
#3/0
#4/0
300 KCMIL
250 KCMIL
400 KCMIL
500 KCMIL
750 KCMIL
750 KCMIL
350 KCMIL
500 KCMIL
750 KCMIL
750 KCMIL
500 KCMIL
750 KCMIL
750 KCMIL
750 KCMIL
750 KCMIL
#6
#6
#6
#6
#4
#4
#4
#3
#3
#2
#1
#1/0
#2/0
#3/0
#4/0
250
KCMIL
350
KCMIL
400
KCMIL
2"
2"
2"
2"
2"
2 1/2"
3"
3"
4"
3"
3 1/2"
4"
4"
3 1/2"
4"
4"
4"
4"
-- - - - - - - - - -
NOTES:
1. WIRING SHALL BE PROVIDED IN ACCORDANCE WITH NEC, UNLESS LARGER SIZES ARE SHOWN TO ACCOMMODATE FUTURE LOADS OR VOLTAGE DROP.
2. THE NUMBER OF PHASE WIRES ARE DESIGNATED BY '#' IN SCHEDULE. REFER TO RISER DIAGRAM FOR EXACT AMOUNT.
3. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR IN EVERY FEEDER AND BRANCH CIRCUIT.
4. BASED ON THWN/THHN COPPER CONDUCTORS IN 30C AMBIENT.
5. DO NOT USE THIS TABLE FOR SCHEDULE 80 PVC OR ENT (WHEN PERMITTED BY SPECIFICATIONS), REFER TO NEC CHAPTER 9.
6. KEY: AMPREAGE - PHASE/NEUTRAL/GROUND. EXAMPLE "300-3NG = 300 AMP FEEDER, 3 PHASE, 4 WIRE WITH GROUND", "90-3G = 90 AMP FEEDER, 3 PHASE, 3 WIRE WITH GROUND".
7. ALUMINUM NOT UTILIZED BELOW 100 AMPS DUE TO ISSUES CONCERNS WITH EQUIPMENT SUPPLIES AND LUG COMPATABILITY ISSUES.
21071
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateTHE CONCOURSECarmel, IN 46032Carmel Review
GRJK550 Monon BlvdNOT FOR CONSTRUCTIONE-401
ELECTRICAL RISER
DIAGRAM
02/03/202302/03/2023
NOT TO SCALE
E-RISER DIAGRAM1
EC SHALL PROVIDE PROPOSED ROUTING OF SERVICE AND
APARTMENT FEEDERS FOR ARCHITECTURAL AND ENGINEERING
REVIEW PRIOR TO INSTALLATION.
FEEDER ROUTING NOTE