HomeMy WebLinkAboutEP105B - 5TH FLOOR POWER PLAN - AREA BCAMGA GB GC
G1
G4
G5
G8
GE
G3
G7.5
GH GJGGB.2 C.3 D D.5 E F H KJ M
6
7
8
9
10
11
G7
G2
D.2 D.7 GF
G6
G2.3
G6.7
G.9A B.3 C.4
G1.5
G7.6
GA.9
GI
G7.9
G1.1
E.6
1
2
H2A- 16
H2A- 60
H2A- 60
H2A- 60
H2A- 60
H2A- 60
E1- 2,4,6E1- 1,3,5
H2A- 60
H2A- 16
H2A- 16
A. SEE SHEET E-000 FOR SYMBOLS AND ABBREVIATIONS.
B. SEE SHEET E-502 FOR MECHANICAL EQUIPMENT POWER SCHEDULE.
C. SEE SHEETS E-503 THROUGH E-505 FOR PANEL SCHEDULES.
D. SEE SHEETS E-601 FOR ELECTRICAL DETAILS.
E. WIRING SYSTEM SHALL BE CONDUIT AND CONDUCTOR UNLESS NOTED
OTHERWISE. USE SOLID CONDUCTOR FOR SIZE #10 AWG AND SMALLER.
USE STRANDED CONDUCTOR FOR LARGER SIZES.
F. ALL COVER PLATES FOR ELECTRICAL DEVICES SHALL BE OF A COLOR TO
MATCH THE AREA COLOR SCHEME AS DIRECTED BY THE INTERIOR
DESIGNER.
G. ALL WORK SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL CODES
AND ORDINANCES PERTAINING TO THE WORK IN THIS PROJECT.
H. EXPOSED CONDUIT SHALL BE RUN PARALLEL TO AND AT RIGHT ANGLES TO
BUILDING LINES.
I. REFER TO ARCHITECTURAL DRAWINGS FOR DESIGNATION AND LISTING OF
FIRE RATED ASSEMBLIES. COORDINATE ALL DESIGN EFFORTS WITH FIRE
RESISTANCE OF MATERIALS AND CONSTRUCTION.
J. ALL EXTERIOR EQUIPMENT AND DEVICES SHALL BE WEATHER PROOF AND
RAIN TIGHT.
K. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL
INTERCONNECT WIRING FOR MECHANICAL AND PLUMBING EQUIPMENT
FURNISHED BY OTHERS.
GENERAL SHEET NOTES
21071
Project:
Developer:
Sheet Number:
Engineer:
By:
Sheet Title:
CDG Number:
Last Revision Date:
Set Issue Date
Drawn By Checked By
Sheet Issue DateTHE CONCOURSECarmel, IN 46032Carmel Review
GRJK550 Monon BlvdNOT FOR CONSTRUCTIONEP105B
5TH FLOOR POWER
PLAN - AREA B
02/03/202302/03/2023
1/8" = 1'-0"
5TH FLOOR POWER PLAN - AREA B1016'8'4'
N
SHEET PLAN NOTES
1 CEILING UNDER SOALR AREA TO BE USED AS ACCESS HATCH FOR SOLAR
PANELS. COORDINATE WITH ARCHITECTURAL DRAWINGS.
2 SOLAR POWER TO BE TIED INTO PANEL 'H1' PROVIDE FUSED DISCONNECT
ADJACENT TO INVERTER LOCATION, CONDUIT AND WIRE. ALL ROOF
PENETRATIONS TO BE WATER TIGHT AND FIRE STOPPED AS REQUIRED BY
BUILDING CODES.