HomeMy WebLinkAboutSheet A121ELNS N SNSNSNS N
SNSNSNS N
SNDELNELN
REFLECTED
CEILING PLAN
A121
PROVIDE NEW CEILING GRID AND TILE TO MATCH AND ALIGN
WITH EXISTING SUCH THAT NEW AND EXISTING CEILINGS APPEAR
CONTINUOUS.
CONTROL ENTRY 101 AND BREAK + COPY 112 LIGHTING WITH
SWITCH AT THIS LOCATION
PLAN NOTES
LIGHT CIRCUIT
LIGHT SWITCH, DIMMER
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
ND
N
N3
D
3
EXIT LIGHT FIXTURE, DUAL
LITE LX EVE SERIES; LED
LIGHT FIXTURE,
PENDANT, LIGHTOLOGY
LITHIUM PENDANT
#TWO901729
LIGHT FIXTURE, 2'x4',
METALUX 24 CZ 4000K
RELOCATED DIFFUSER,
LAY-IN, 2'x2'
ARMSTRONG SILHOUETTE 1
4"
REVEAL CEILING GRID, 9
16"
SUSPENSION SYSTEM, 2'x2'
NIGHT LIGHT
NEW OR RELOCATED EXISTING TO REMAIN
LIGHT FIXTURE, 6"x8', LED,
SURFACE MOUNTED WALL
WASH, 8'-0" LENGTH
LIGHT FIXTURE,
PENDANT
EXIT LIGHT FIXTURE
LIGHT CIRCUIT
LIGHT SWITCH, DIMMER
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
CEILING GRID,
SUSPENDED, 2'x2'
DIFFUSER,
LAY-IN, 2'x2'
LIGHT FIXTURE, 2'x4'
LEGEND
REFLECTED CEILING PLANAREA NOT IN CONTRACT
AREA OF WORK
DESCRIPTIONDATE
ISSUE
12.16.22 REVIEW SET
02.21.23 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.8888 Keystone Crossing, Suite 100Indianapolis, IN 46240p: 317.387.1700www.schottdesign.comPROJECT NUMBER
DRAWN BYPROJ. MGR ELITE HOME REHABAND HEALTHCARELAKESIDE GREEN BUSINESS CENTER, SUITE 115645 W. CARMEL DRIVE, CARMEL, IN 46032BMEH
2022.242
1ST FLOOR
N0 2' 4' 8' 16'
EMERGENCY LIGHT FIXTURE,
BUILDING STANDARD
EMERGENCY LIGHT FIXTURE
MECHANICAL DIFFUSER RELOCATION
A121
1
*REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION
EXISTING VAV BOXES OR
HEAT PUMP AND MAIN SUPPLY
DUCTS TO REMAIN
RELOCATE DIFFUSERS &
FLEXDUCT IF REQUIRED
VAV /
HEAT PUMP
A121
1
1. INSTALL NEW CEILING GRID 2X2 AT 8'-6". PROVIDE NEW CEILING
TILES THROUGHOUT. 2X2 ARMSTRONG GEORGIAN #1753B TEGULAR
BEVELED EDGE LAY IN.
2. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED
PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED
IF THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN
ON PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN
SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY
SDI OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY
RESULT IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR
EXPENSE.
3. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI. OVER 50% OF THE LIGHTING WILL
BE REPLACED WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS
WILL NEED TO BE MET.
4. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS, PROVIDE
COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED
TECHNOLOGY WITH A ONE BUTTON OVERRIDE. OCCUPANCY
SENSORS ARE TO BE LOCATED SUCH THAT OCCUPANCY WITHIN
ANY PORTION OF INCLUDED AREA IS DETECTED. PROVIDE CEILING
MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
5. NEW DEVICES AND FACE PLATES TO BE WHITE. WHERE POSSIBLE,
GANG MULTIPLE SWITCHES TO ACCOMMODATE MULTI-SWITCH
PLATE WHEN SWITCHES ARE SHOWN ADJACENT ON PLAN.
6. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED
TO ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES
AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE
EXISTING ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL
CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL
WORK IS REQUIRED SO THAT ADDITIONAL PLANS CAN BE FILED AND
MUST COMPLY WITH ALL APPLICABLE CODES.
7. LIGHTING VENDOR TO PROVIDE PHOTOMETRIC STUDY TO CONFIRM
ALL REQUIRED FIXTURE QUANTITIES PRIOR TO ORDERING. LIGHTING
VENDOR TO COORDINATE WITH SCHOTT DESIGN AS REQUIRED TO
ENSURE PROPER LIGHTING LEVELS.
GENERAL NOTES
1. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. NO NEW MAIN MECHANICAL
APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED. ALL
MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND
FLEX DUCT PER NEW WALL LAYOUT. IF IN GOOD CONDITION, EXISTING
H.V.A.C. DIFFUSERS SALVAGED FROM DECONSTRUCTION MAY BE
SUBSTITUTED FOR NEW. NO NEW HARD DUCTWORK OR EQUIPMENT IS
BEING ADDED; MECHANICAL CONTRACTOR IS TO NOTIFY
APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT
ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE
INDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES.
MECHANICAL NOTES
03/08/23