NOT ALL NOTES, DESIGNATORS, SYMBOLS OR ABBREVIATIONS MAY APPLY TO THIS PROJECTA. DRAWINGS ARE DIAGRAMMATIC. ALL DIMENSIONS SHOWN ARE APPROXIMATE. ALL LOCATIONS
SHALL BE FIELD VERIFIED.
B. CONTRACT DOCUMENTS CONSIST OF BOTH THE PROJECT MANUAL AND DRAWINGS, AND BOTH
ARE INTENDED TO BE COMPLEMENTARY. ANYTHING APPEARING ON EITHER MUST BE EXECUTED
THE SAME AS IF SHOWN ON BOTH.
C. THE CONTRACTOR SHALL INCLUDE IN BID PROPOSAL ALL COSTS REQUIRED TO COMPLETELY AND
PROPERLY INSTALL ALL WORK REQUIRED FOR THE PROJECT, AND SHALL EXAMINE THE SCOPE
OF WORK OF OTHER TRADES PRIOR TO SUBMITTING A BID PROPOSAL.
D. CONSTRUCTION DOCUMENTS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE, HOWEVER,
SYSTEMS HAVE BEEN SHOWN DIAGRAMMATICALLY AND IN SOME CASES, ENLARGED FOR
CLARITY. ANY OFFSETS, ADDITIONAL FITTINGS, AND/OR APPURTENANCES REQUIRED TO PROVIDE
A COMPLETE AND COORDINATED SYSTEM SHALL BE BORNE BY THE CONTRACTOR.
E. THE TECHNOLOGY DRAWINGS ARE OF EQUAL IMPORTANCE WITH THE ARCHITECTURAL AND
ENGINEERING DRAWINGS IN DEFINING THE WORK OF THE CONTRACT DOCUMENTS. IT SHALL BE
THE RESPONSIBILITY OF THE CONTRACTOR TO CHECK WITH THE ARCHITECTURAL AND
ENGINEERING DRAWINGS BEFORE THE INSTALLATION OF ENGINEERING WORK. SHOULD THERE
BE A DISCREPANCY BETWEEN THE ARCHITECTURAL AND ENGINEERING DRAWINGS AND THE
TECHNOLOGY DRAWINGS THAT WOULD CAUSE AN AWKWARD OR IMPROPER INSTALLATION, THE
DISCREPANCY SHALL BE BROUGHT TO THE ARCHITECTS/ENGINEERS ATTENTION FOR
CLARIFICATION PRIOR TO INSTALLATION OF SAID WORK. ANY WORK INSTALLED IN CONFLICT
WITH THE ARCHITECTURAL AND ENGINEERING DRAWINGS SHALL BE CORRECTED BY THE
CONTRACTOR AT HIS EXPENSE AND AT NO ADDITIONAL COST TO THE OWNER OR
ARCHITECT/ENGINEER.
F. DO NOT SCALE THE DRAWINGS. THE DRAWINGS ARE NOT NECESSARILY TO SCALE. THE
CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS AT THE JOB SITE PRIOR TO THE
START OF CONSTRUCTION. IF DISCREPANCIES ARE FOUND, THE ARCHITECT/ENGINEER SHALL BE
NOTIFIED FOR CLARIFICATION BEFORE COMMENCING THE WORK. EXPLICIT DIMENSIONS SHALL
HAVE PRECEDENCE OVER SCALE.
G. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BIDDING OR BEGINNING
WORK ON THIS PROJECT.
H. DETAILS NOT SHOWN ARE SIMILAR IN CHARACTER TO THOSE SHOWN. WHERE SPECIFIC
DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BE DETERMINED, CONSULT THE
ARCHITECT/ENGINEER BEFORE PROCEEDING WITH THE WORK.
I. ANY DETAILS, SYSTEMS AND/OR MATERIALS WHICH ARE PROPOSED TO BE CHANGED MUST FIRST
BE REVIEWED BY THE OWNER AND ARCHITECT/ENGINEER PRIOR TO THE PREPARATION OF SHOP
DRAWINGS.
J. ALL WORK SHALL BE IN CONFORMANCE WITH THE NATIONAL ELECTRICAL CODE -LATEST EDITION
ADOPTED BY STATE HAVING JURISDICTION, AND THE STATE HAVING JURISDICTION ELECTRICAL
CODE AMENDMENTS, LOCAL/MUNICIPAL CODES, AND THE AUTHORITY HAVING JURISDICTION.
K. CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES. NO ADDITIONAL COMPENSATION
WILL BE ALLOWED FOR INCORRECT WORK, OR FOR INFRINGEMENT UPON OTHERS WORK, DUE
TO A LACK OF COORDINATION.
L. COORDINATE LOCATION OF ALL DEVICES TO BE INSTALLED IN CEILINGS WITH THE
ARCHITECTURAL REFLECTED CEILING PLANS. NOTIFY ENGINEER OF AN CONFLICTS PRIOR TO
INSTALLATION.
M. CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANING THEIR AREAS OF CONSTRUCTION.
PROJECT AREAS SHALL BE THOROUGHLY CLEANED AND TRASH DISPOSED OF AT THE END OF
EACH WORK DAY. THE OWNER'S FACILITIES SHALL NOT BE USED FOR TRASH DISPOSAL.
N. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING THEIR WORK FROM DUST AND DEBRIS.
CONTRACTOR SHALL PROVIDE DUST BARRIERS FOR ALL TECHNOLOGY EQUIPMENT AS REQUIRED
TO PROTECT THE TECHNOLOGY EQUIPMENT.
O. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ALL SURFACES AND FINISHED OF
THE CONSTRUCTION SITE DURING THE INSTALLATION OF THE TECHNOLOGY SYSTEMS. DAMAGED
SURFACES OR FINISHES RESULTING FROM THE PERFORMANCE OF THE WORK OR NEGLIGENCE
SHALL BE REPAIRED AT NO COST TO THE OWNER BY THE RESPONSIBLE CONTRACTOR. FINISHES
AND SURFACES SHALL BE MADE TO MATCH THE EXISTING FINISHES OR SURFACES TO THE
SATISFACTION OF THE OWNER AND ARCHITECT/CONSTRUCTION MANAGER.
TELECOMMUNICATIONS OUTLET. WHEN INDICATED WITH xD, x INDICATES THE
QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL CABLE. WHEN INDICATED
WITH xV, x INDICATES THE QUANTITY OF COMMUNICATIONS COAXIAL CABLE.
TECHNOLOGY SYMBOLS LEGEND
SECTION INDICATOR: REFERENCE SECTION LOCATION THROUGH AN AREA
FOR ADDITIONAL INFORMATION.
KEYNOTE INDICATOR:REFERENCE SHEET KEYNOTE LOCATION FOR
ADDITIONAL INFORMATION.
DETAIL INDICATOR: REFERENCE DETAIL LOCATION FOR ADDITIONAL
INFORMATION.
DRAWING BLOCK TITLE
INDICATOR:
REFERENCE DRAWING MODULE LOCATION FOR
ADDITIONAL INFORMATION.
MATCH LINE INDICATOR: REFERENCE SHEET LOCATION FOR ADDITIONAL
INFORMATION.
REVISION INDICATOR:REFERENCE TITLE BLOCK LOCATION FOR ADDITIONAL
INFORMATION.
EQUIPMENT INDICATOR:REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
DIFFUSER, GRILLE,
REGISTER INDICATOR:
REFERENCE SCHEDULE LOCATION FOR ADDITIONAL
INFORMATION.
TU-XL.##
REFERENCE SYMBOLS
DRAWING BLOCK TITLE
SECTION LOCATION
IN DRAWING MODULE
SECTION LOCATION AT SUBSET SHEET
DETAIL LOCATION IN
DRAWING MODULE
DETAIL LOCATION AT
SUBSET SHEET
LARGE SCALE VIEW
LOCATION IN DRAWING
MODULE
LARGE SCALE VIEW
LOCATION AT SUBSET SHEET
KEYNOTE INDICATORS
EQUIPMENT TYPE
NUMERIC CHARACTER RELATES TO ITEM
ALPHANUMERIC CHARACTER RELATES
TO ASSOCIATED AIR HANDLER (OPTIONAL)
AREA LEADER
LINE LEADER
POINT LEADER
DRAWING MODULE LOCATION
(IDENTIFYING LOWER LEFT OF MULTIPLE MODULES)
REVISION CLOUD
REVISION INDICATOR
NUMERIC SCALE
SEE XXXX
REFER TO ADDITIONAL
SHEET FOR CONTINUATION
FLOOR PLAN OVERLAP BEYOND AREA
EXTENSION
PLAN
PLAN
NUMERIC CHARACTER
RELATES TO ITEM
NORTH ARROW
BEYOND AREA
EXTENSION
ALPHANUMERIC CHARACTER RELATES TO
BUILDING LEVEL (OPTIONAL)
SCALE: 1/8" = 1'-0"
X
XX X X
X
X
X
X
X X
N
SCHEDULE TYPE AIRFLOW (CUBIC FEET PER MINUTE)
XXX-XXX
TECHNOLOGY PATHWAY NOTES
1. ALL HORIZONTAL CABLING RUNS SHALL BE SUPPORTED NEATLY WITH CABLE TRAY, CONDUITS,
OR J-HOOKS. ALL HORIZONTAL CABLING THAT IS NOT INSTALLED IN CABLE TRAY OR CONDUIT
SHALL BE SUPPORTED WITH J-HOOKS. CABLES SHALL NOT LIE ON THE STRUCTURAL STEEL OR
SYSTEMS OF THE FACILITY.
2. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE CONDUIT SEALING MATERIAL
AND SHALL MATCH FIRE RATING OF BARRIER BEING PENETRATED.
3. FIELD VERIFY LOCATIONS OF BUILDING EXPANSION JOINTS WHEN ROUTING CONDUIT. ALL
CONDUITS CROSSING EXPANSION JOINTS SHALL BE INSTALLED WITH EXPANSION FITTINGS.
EXPANSION FITTINGS SHALL BE INSTALLED IN ACCORDANCE WITH THE NEC, AND
MANUFACTURER'S WRITTEN RECOMMENDATIONS.
4. WHEN CABLE TRAY IS SHOWN ON THE PLANS AND PORTIONS OF CABLE TRAY CANNOT BE
INSTALLED DUE TO CONFLICT WITH STRUCTURE, THE CONTRACTOR SHALL PROVIDE (2) 4" C.
WITH INSULATED BUSHINGS THAT OVERLAP 1" INTO THE TRAY.
5. CONDUITS 2" AND LARGER THAT PENETRATE EXTERIOR WALLS SHALL USE LINK-SEALS.
6. DEVICES IN GENERAL SHALL BE CENTERED IN WALL SPACE IN WHICH THEY ARE INSTALLED OR
THEY SHALL BE SPACED SYMMETRICALLY (FOR EXAMPLE, CENTER DEVICES WHEN MOUNTED ON
FACE OF COLUMNS).
7. COORDINATE AND VERIFY LOCATIONS OF DEVICES WITH BLOCK COURSING, FINISH MATERIALS,
CASEWORK, ETC. PRIOR TO ROUGH-IN.
8. ALL DEVICE BOXES SHALL BE FLUSH MOUNTED AND ALL RACEWAYS SHALL BE CONCEALED
UNLESS NOTED OTHERWISE. CONTRACTOR SHALL CUT AND PATCH EXISTING WALLS WITH
EXTREME CAUTION, SO AS TO MINIMIZE INVASIVENESS OF INSTALLATION. ROUTE RACEWAYS SO
AS TO MINIMIZE THE AMOUNT OF CUTTING AND PATCHING REQUIRE. PATCHING SHALL COMPLY
WITH ALL BID DOCUMENT REQUIREMENTS.
9. CONDUIT RUNS SHALL HAVE NO MORE THAN 180 DEGREES OF BENDS WITHOUT A PULL BOX.
WHERE CONDUIT IS SHOWN AND/OR SPECIFIED, CONTRACTOR SHALL PROVIDE ALL PULL BOXES
SHOWN ON THE DRAWINGS AND ADDITIONAL PULL BOXES AS FOLLOWS:
A. EVERY 180 DEGREES OF CONDUIT BEND
B. EVERY 100 FEET OF CONDUIT PATH
10. PROVIDE PLASTIC INSULATED BUSHINGS ON ALL CONDUIT STUB'S. BUSHINGS SHALL ALSO BE
PROVIDED FOR ALL CONDUITS WHETHER ABOVE OR BELOW CEILING OR AT FLOOR LEVEL. IT IS
THE COMMUNICATIONS CABLING CONTRACTORS RESPONSIBILITY TO ENSURE BUSHINGS HAVE
BEEN PROVIDED ON ALL CONDUITS PRIOR TO PULLING CABLES. IF CONDUITS ARE FOUND TO BE
WITHOUT BUSHINGS, COMMUNICATIONS CABLING CONTRACTOR SHALL REMOVE CABLING,
PROVIDE BUSHINGS AND REPLACE WITH NEW CABLING.
FIRESTOPPING NOTES
1. THE CONTRACTOR SHALL FIRESTOP ALL PENETRATIONS OF ALL FLOORS AND ALL WALLS WHICH
EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK ABOVE.FIRESTOPPING SHALL BE
ACCOMPLISHED AFTER ALL CABLES ARE PULLED (ALL SYSTEMS) USING UL CLASSIFIED SYSTEMS
WITH FIRE RATING EQUAL TO OR GREATER THAN THE FIRE RATING OF THE FLOOR OR WALL
ASSEMBLY PENETRATED. INSTALL IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED
INSTRUCTIONS. THE CONTRACTOR SHALL SUBMIT A MANUFACTURER'S STANDARD DETAIL FOR
EACH TYPE OF FLOOR AND WALL PENETRATION REQUIRED FOR THIS PROJECT. ALL OTHER
PENETRATIONS OR OPENINGS IN NON-FIRE RATED WALLS SHALL BE REPAIRED AND SEALED WITH
MATERIALS TO MATCH THE EXISTING CONSTRUCTION.
SYMBOL DESCRIPTION ROUGH-IN
REQUIREMENTS
MOUNTING
HEIGHT (UNO)
ROUGH-IN
DETAIL
TECHNOLOGY
DETAIL
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG OR DOUBLE GANG MUD RING. PROVIDE
TWO (2) 1" C.'S STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL
STRINGS.
xD +18"1, 2, & 3/T501 1/T503
VIDEO OUTPUT LOCATION. WHEN INDICATED WITH xD, x INDICATES THE
QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL CABLE. INSTALL JACKS
IN SURFACE MOUNT BISCUIT. WHEN INDICATED WITH xV, x INDICATES THE
QUANTITY OF COMMUNICATIONS COAXIAL CABLE.
xD
+60" 5/T501 1/T503VO
xD TELECOMMUNICATIONS OUTLET WITH WALL PLATE. WHEN INDICATED WITH xD, x
INDICATES THE QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL CABLE.
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
+44"
PROVIDE CHIEF PAC525W WALL BOX. PROVIDE ONE (1) 1-1/4" CONDUIT STUBBED ABOVE
ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
FLOORBOX DATA LOCATION. WHEN INDICATED WITH xD, x INDICATES THE
QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL CABLE.
xD PROVIDE FLOORBOX WITH TWO (2) 1-1/4"C'S STUBBED ABOVE ACCESSIBLE CEILING WITH
PLASTIC BUSHING AND PULL STRINGS. REFER TO ROUGH-IN DETAILS FOR MORE INFORMATION -6/T501 -
CEILING MOUNTED WIRELESS ACCESS POINT LOCATION. WHEN INDICATED WITH
xD, x INDICATES THE QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL
CABLE.
PROVIDE 4" SQUARE BOX WITH BLANK METAL COVER PLATE. METAL BOX SHALL BE
SUPPORTED FROM WALL ABOVE ACCESSIBLE CEILING), OR STRUCTURE, OR UNISTRUT. METAL
BOX SHALL NOT BE INSTALLED LOOSE ON CEILING TILES.
---xD
xD
WALL MOUNTED WIRELESS ACCESS POINT LOCATION. WHEN INDICATED WITH
xD, x INDICATES THE QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL
CABLE.
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
+96"
CARD READER. CARD READER PROVIDED BY OWNER'S PREFERRED
CONTRACTOR.
SECURITY SYMBOLS LEGEND
SYMBOL DESCRIPTION ROUGH-IN
REQUIREMENTS
MOUNTING
HEIGHT (UNO)
ROUGH-IN
DETAIL
TECHNOLOGY
DETAIL
+42"1 & 2/T502
ELECTRONIC STRIKE.-
DOOR CONTACT.-
ELECTRONIC LATCH.-
-
WALL MOUNTED IP VIDEO SURVEILLANCE CAMERA LOCATION. WHEN INDICATED
WITH xD, x INDICATES THE QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL
CABLE. CAMERA PROVIDED BY OWNER'S PREFERRED CONTRACTOR.
PROVIDE 4" SQUARE BOX WITH BLANK METAL COVER PLATE. METAL BOX SHALL BE
SUPPORTED FROM WALL ABOVE ACCESSIBLE CEILING), OR STRUCTURE, OR UNISTRUT. METAL
BOX SHALL NOT BE INSTALLED LOOSE ON CEILING TILES.
+96"
COORDINATE ROUGH-IN AND CONDUIT INTO DOOR FRAME WITH DOOR HARDWARE
MANUFACTURER.
CEILING MOUNTED IP VIDEO SURVEILLANCE CAMERA LOCATION. WHEN
INDICATED WITH xD, x INDICATES THE QUANTITY OF COMMUNICATIONS COPPER
HORIZONTAL CABLE. CAMERA PROVIDED BY OWNER'S PREFERRED CONTRACTOR.
xD
xD
COORDINATE ROUGH-IN AND CONDUIT INTO DOOR FRAME WITH DOOR HARDWARE
MANUFACTURER.
COORDINATE ROUGH-IN AND CONDUIT INTO DOOR FRAME WITH DOOR HARDWARE
MANUFACTURER.
TECHNOLOGY ADDITIONAL CABLING
NOTE
A. PROVIDE TEN (10) ADDITIONAL 200 FOOT COPPER COMMUNICATIONS COPPER HORIZONTAL
CABLING RUNS. INCLUDE JACKS AT BOTH ENDS, LABELING, AND TESTING. THE ADDITIONAL
DROPS ARE TO BE INSTALLED AS DIRECTED BY THE ENGINEER.
-
--
-
-
-
-
1 & 5/T501
& AND
EMT ELECTRICAL METALLIC TUBING
ETR EXISTING TO REMAIN
OD OUTSIDE DIAMETER
°F DEGREES FAHRENHEIT
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
EX EXISTING
FLR FLOOR
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
FT FOOT, FEET
AFG ABOVE FINISHED GRADE
G GROUND
PVC POLYVINYL CHLORIDE CONDUIT/PIPE
GC GENERAL CONTRACTOR
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
RGS RIGID GALVANIZED CONDUIT
ARCH ARCHITECT
GRD GROUND
RM ROOM
GND GROUND
AVG AVERAGE
BAS BUILDING AUTOMATION SYSTEM
HORIZ HORIZONTAL
SF SQUARE FOOT
SPEC SPECIFICATION
BLDG BUILDING
HR HOUR(S)
SQ SQUARE
BMS BUILDING MANAGEMENT SYSTEM
BSMT BASEMENT
Hz HERTZ
STD STANDARD
C CONDUIT
ID INSIDE DIAMETER
TBD TO BE DETERMINED
IN INCH, INCHES
TBI TO BE INSTALLED
INT INTERIOR
TBR TO BE REMOVED
TC TEMPERATURE CONTROLS
TCC TEMPERATURE CONTROLS CONTRACTOR
CLG CEILING
TEMP TEMPERATURE
LBS POUNDS
TYP TYPICAL
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
UON UNLESS OTHERWISE NOTED
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
VERT VERTICAL
MTD MOUNTED
DWG DRAWING
NA NOT APPLICABLE
WP WEATHERPROOF
EA EACH
NEC NATIONAL ELECTRIC CODE
W/ WITH
EC ELECTRICAL CONTRACTOR
NIC NOT IN CONTRACT
W/O WITHOUT
NOM NOMINAL
EL ELEVATION
NTS NOT TO SCALE
ABBREVIATIONS AND TERMS
WAP
EL
CR
ES
DC
WAP
PANIC BUTTON. PANIC BUTTON PROVIDED BY OWNER'S PREFERRED
CONTRACTOR.+44"--PB PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
J
xD
JUNCTION BOX FOR FURNITURE FEED REFER TO FURNITURE FEED ROUGH-IN DETAILS FOR MORE INFORMATION ON EXACT ROUGH-
IN REQUIREMENTS. PROVIDE PLASTIC BUSHING AND PULL STRINGS IN ALL CONDUITS.-4/T501 -
HORIZONTAL DATA CABLING COLOR LEGEND
SYSTEM TERMINATION (RJ-45) CABLE
GRAYDATAORANGE
PATCH CABLE
BLACK
GRAYWIRELESSORANGE PURPLE
GRAYIP CAMERA ORANGE YELLOW
1 & 3/T501
1 & 3/T501
1/T503
-
RS ROOM SCHEDULE LOCATION. WHEN INDICATED WITH xD, x INDICATES THE
QUANTITY OF COMMUNICATIONS COPPER HORIZONTAL CABLE. COORDINATE
TERMINATION REQUIREMENTS WITH AV CONTRACTOR.
xD
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
COORDINATE EXACT ROUGH-IN LOCATION AND REQUIREMENTS WITH OWNER'S AV VENDOR
PRIOR TO INSTALLATION.
+44"1 & 3/T501 -
W
xDWP
TELECOMMUNICATIONS OUTLET WITH WEATHER PROOF COVER. WHEN
INDICATED WITH xD, x INDICATES THE QUANTITY OF COMMUNICATIONS COPPER
HORIZONTAL CABLE.
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG OR DOUBLE GANG MUD RING. PROVIDE
TWO (2) 1" C.'S STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL
STRINGS.
+18"1, 2, & 3/T501 1/T503
GRAYAVGREEN GREEN
TELECOMMUNICATIONS CONDUIT SLEEVE. CONDUIT SIZE SHALL BE 2" UNLESS
NOTED OTHERWISE.----
SP
WALL MOUNTED VOLUME CONTROL. VOLUME CONTROL PROVIDED BY OWNER'S
PREFERRED CONTRACTOR.
SPEAKER SYMBOLS LEGEND
SYMBOL DESCRIPTION ROUGH-IN
REQUIREMENTS
MOUNTING
HEIGHT (UNO)
ROUGH-IN
DETAIL
+44"
WALL MOUNTED SPEAKER. SPEAKER PROVIDED BY OWNER'S PREFERRED
CONTRACTOR.+96"PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
TECHNOLOGY
DETAIL
-
-
xV
xV
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.
1 & 2/T502
1 & 2/T502
1 & 2/T502
PROVIDE 2-GANG, 3.5" DEEP BOX WITH SINGLE GANG MUD RING. PROVIDE ONE (1) 1" C.
STUBBED ABOVE ACCESSIBLE CEILING WITH PLASTIC BUSHING AND PULL STRINGS.1 & 3/T501VC
1 & 3/T501 ARCHITECTCLIENTCONSULTANTPROJECTDRAWING TITLESEALSHEETPROJECT INFOREVISIONS2 WEST MAIN STREET O: 317.810.1502CARMEL, IN 460322101
10-26-2022
BID DOCUMENTS
T000SYMBOLS ANDABBREVIATIONSCLAY TOWNSHIPCENTER10701 North CollegeAvenueCarmel, IN# DESCRIPTION DATE