HomeMy WebLinkAboutE901 - ELECTRICAL DIAGRAMS AND DETAILSM G 200 KW NATURAL GAS GENERATOR BASE 3 POLE ATS 225A 277/480V GENERATOR ANNUNCIATOR DISTUBUTION PANEL MDP 600A MLO, 277/480V 400A 3P 60A 3P SPACE SPACE DISTUBUTION PANEL MDP 400A MCB, 277/480V 400A 3P 200A 3P SPACESPACE SPARE 100A 3P 90A 3P 200A 3P 75KVA XFMR 480∆ 208Y PANEL F4 200A 120/208V 3PH, 4W PANEL F6 200A 277/480V 3PH, 4W PANEL F5 200A 120/208V 3PH, 4W UTILITY CT CABINET 45KVA XFMR 480∆ 208Y AIR STATION ECB 100A/3PJ 175A 3P 75KVA XFMR 480∆ 208Y PANEL F2 200A 120/208V 3PH, 4W PANEL F1 200A 120/208V 3PH, 4W PANEL F3 125A 120/208V 3PH, 4W 75KVA XFMR 480∆ 208Y PANEL G2 125A 120/208V 3PH, 4W PANEL G1 175A 120/208V 3PH, 4W PANEL G5 100A 120/208V 3PH, 4W 30KVA XFMR 480∆ 208Y PANEL G4 100A 120/208V 3PH, 4W PANEL G3 80A 120/208V 3PH, 4W 30KVA XFMR 480∆ 208Y PANEL EM1 100A 120/208V 3PH, 4W FIRE STATION GOVERMENT CENTER M G 200 KW NATURAL GAS GENERATOR BASE 3 POLE ATS 225A 277/480V DISTUBUTION PANEL MDP 600A MLO, 277/480V 400A 3P 60A 3P SPACE DISTUBUTION PANEL MDP 400A MCB, 277/480V 400A 3P 200A 3P SPACESPACE SPARE 100A 3P 90A 3P 200A 3P 75KVA XFMR 480∆ 208Y PANEL F4 200A 120/208V 3PH, 4W PANEL F6 200A 277/480V 3PH, 4W UTILITY CT CABINET J 175A 3P PANEL F1 200A 120/208V 3PH, 4W 75KVA XFMR 480∆ 208Y PANEL G2 125A 120/208V 3PH, 4W PANEL G1 175A 277/480V 3PH, 4W PANEL G5 100A 120/208V 3PH, 4W 30KVA XFMR 480∆ 208Y PANEL G4 100A 120/208V 3PH, 4W PANEL G3 80A 277/480V 3PH, 4W 30KVA XFMR 480∆ 208Y PANEL EM1 100A 120/208V 3PH, 4W FIRE STATION GOVERMENT CENTER PANEL L1 250A 120/208V 3PH, 4W PANEL H1 75KVA XFMR 480∆ 208Y NEW 150A 3P M NEW 200A SUB METER FOR ADDITION (4) #4/0, #4 G. IN 2-1/2" C. (3) #1, #6 G. IN 1-1/2" C. #2 G. (4) 250KCMIL, #2 G. IN 2-1/2" C. PBB BY TELECOMMUNICATIONS CONTRACTOR N G EQUIPMENT GROUND - SIZE AS SHOWN ON ONE-LINE DIAGRAM G NEUTRAL BUS GROUND BUS EXISTING SERVICE EQUIPMENT ENCLOSURE (MDP) PANELBOARD TO UTILITY TRANSFORMER TYPICAL DATA CABINET SUPPLEMENTARY BONDING GRID UNDER RAISED FLOOR 3/0 GND BY TELECOMMUNICATIONS CONTRACTOR EXIT NOTES: 1. EQUIPMENT MOUNTING HEIGHTS SHALL BE AS INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS. 2. WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COURSING SO THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED. CEILING F H S E VC IC F SYMBOLS: FLOOR W C S M 96"96"72"48"96"96"96"72"48"16"48"48"84"TOP OF BOX TO BE NO MORE THAN +48" AFF BOTTOM OF BOX TO BE NO LESS THAN +16" AFF OPEN BOX MOUNTING BRACKET TO BE USED WHEN BOX LARGER THAN 2- GANG IS REQUIRED WALL STUD (TYP) TYPICAL BOX MOUNTING BRACKET NOTES: 1. BOX MOUNTING BRACKETS ARE TO BE USED WHEN MOUNTING MULTIPLE BOXES WITHIN THE SAME STUD SPACE. 2. WHEN RECEPTACLES ARE SHOWN BELOW SWITCHES ALIGN VERTICALLY.ARCHITECTCLIENTCONSULTANTPROJECTDRAWING TITLESEALSHEETPROJECT INFOREVISIONS2 WEST MAIN STREET O: 317.810.1502CARMEL, IN 460322101 10-26-2022 BID DOCUMENTS E901ELECTRICALDIAGRAMS ANDDETAILSCLAY TOWNSHIPCENTER10701 North CollegeAvenueCarmel, INNOT TO SCALE EXISTING RISER DIAGRAM1 NOT TO SCALE RENOVATION/ADDITION RISER DIAGRAM2 # DESCRIPTION DATE NOT TO SCALE GROUNDING ONE-LINE3 NOT TO SCALE TYPICAL ELECTRICAL ELEVATION5 NOT TO SCALE TYPICAL BOX SUPPORT DETAIL4 03/10/23