HomeMy WebLinkAboutEP102 - ROOF ELECTRICAL PLANRTU-1
EF-1
SSCU-1
L1- 2,4,6
L1- 8
G4- 28,30
1
2 3 ARCHITECTCLIENTCONSULTANTPROJECTDRAWING TITLESEALSHEETPROJECT INFOREVISIONS2 WEST MAIN STREET O: 317.810.1502CARMEL, IN 460322101
10-26-2022
BID DOCUMENTS
EP102ROOF ELECTRICALPLANCLAY TOWNSHIPCENTER10701 North CollegeAvenueCarmel, INN
1/8" = 1'-0"
ROOF ELECTRICAL PLAN1
# DESCRIPTION DATE
SHEET KEYNOTES
1 PROVIDE 60A/3P/NEMA 3R NON-FUSED DISSCONECT FOR MECHANICAL
EQUIPMENT AS LOCAL MEANS OF DISCONNECT. CIRCUIT FOR MECHANICAL
EQUIPMENT SHALL BE BY (3) #6, #10 GROUND IN 1” CONDUIT.
2 PROVIDE 30A/2P/NEMA 3R NON-FUSED DISSCONECT FOR MECHANICAL
EQUIPMENT AS LOCAL MEANS OF DISCONNECT. CIRCUIT FOR MECHANICAL
EQUIPMENT SHALL BE BY (3) #12, #12 GROUND IN 3/4” CONDUIT.
3 MECHANICAL EQUIPMENT TO BE PROVIDED WITH INTEGRAL DISSCONNECTING
MEANS. CIRCUIT FOR MECHANICAL EQUIPMENT SHALL BE BY (2) #12, #12
GROUND IN 3/4” CONDUIT. MECHANICAL EQUIPMENT SHALL BE CONTROLLED
BY TOGGLE SWITCH WITHIN ASSOCIATED ROOM.
GENERAL NOTES
A REFER TO SHEET E-000 FOR GENERAL ELECTRICAL NOTES, SYMBOLS AND
ABBREVIATIONS.
03/10/23