HomeMy WebLinkAboutA-F201 - FIRE SUPPRESSION PLANSM
M
M
M M
PROVIDE ALTERNATE PRICING FOR ARCHIVE SCOPE
Foyer
Entry
Gallery
Water
UP
Mercantile
Gallery Bookstore
UP
ADA
Restroom
Janitor's
Closet
Restroom
Archive M
M
M M
M M M
MDN
White Box Space
Future Gallery
UP
DN
UP
Mech.
ADA
Restroom
Restroom
Break Room
Archive
PROVIDE ALTERNATE PRICING FOR ARCHIVE SCOPE
M
M
M M
M
M
M M
M M M
M
M
M
M
Lift
Depot
Elec.Mech.
Restroom
UP
UP
+828.10
+828.10 +830.10
C
D E.3 K
E J
4
2
5
6
G H
D.2 F
A G.8 H.8
J.8
C.2A.9A.5A.1
1
3
H.2D.8
4
5
4
5
9 FP
CONTROLLER
JP
CONTROLLER
FP-1
JP-1
12
FDC
TEST
HEADERBID PACKAGE 2 BID PACKAGE 1
C
D E.3 K
E J
4
2
5
6
G H
D.2 F
A G.8 H.8
J.8
C.2A.9A.5A.1
1
3
H.2D.8
4
5 4
5
6
FM-200
TANK
FM-200
CONTROLLER
9BID PACKAGE 2 BID PACKAGE 1
C
D E.3 K
E J
4
2
5
6
G H
D.2 F
A G.8 H.8
J.8
C.2A.9A.5A.1
1
3
H.2D.8
4
5 4
5
6
BID PACKAGE 2 BID PACKAGE 1
K L
4
2
5
6
M NJ.8
1
3
10
11
P
BID PACKAGE 2 ARCHITECTOWNERCONSULTANTPROJECTDRAWING TITLESEALSHEETPROJECT INFOREVISIONS1344 S RANGELINE RD SUITE 202 CARMEL, IN 46032317-344-8044Carmel Clay History MuseumDepot Renovation and Archives Building03/02/202320081
March 2, 2023
Bid Documents
F201FIRE SUPPRESSIONPLANS211 1st St SWCarmel, IN 460231/8" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN1
1/8" = 1'-0"
SECOND FLOOR FIRE SUPPRESSION PLAN2
1/8" = 1'-0"
THIRD FLOOR FIRE SUPPRESSION PLAN3
GENERAL NOTES
A FIRE PROTECTION CONTRACTOR SHALL DESIGN A COMPLETE SPRINKLER
SYSTEM ACCORDING TO THE CRITERIA OUTLINED ON THE DRAWINGS AND
NFPA13, 13R, 14, 20, 24. AND INDIANA FIRE CODE.
B REFER TO SHEET A-P000 FOR FIRE PROTECTION GENERAL NOTES.
C PROVIDE CHROME PLATED SEMI-RECESSED SPRINKLER HEADS IN AREAS
WITH FINISHED CEILINGS (I.E. GYP BOARD OR ACOUSTICAL CEILING TILE).
D PROVIDE BRASS UPRIGHT SPRINKLER HEADS IN AREAS WITH NO CEILINGS
(EXPOSED TO STRUCTURE).
E PROVIDE CHROME PLATED SIDEWALL SPRINKLER HEADS IN AREAS WHERE IT
IS IMPRACTICAL TO PROVIDE CEILING MOUNTED SPRINKLERS.
F REFER TO PLAN NOTE 9 FOR ALTERNATE BID SCOPE FOR ARCHIVE SPACE.
ALTERNATE BID FOR CLEAN AGENT FM-200 SYSTEM TO INCLUDE THE
FOLLOWING PROVISIONS: FULLY SEAL AND FIRE CAULK ALL PENETRATIONS
IN/OUT OF ROOM, ALL DRYWALL JOINS SHOULD BE CAULKED AT JOINTS OF
WALLS, FLOOR, AND STRUCTURE ABOVE, SEALS ON DOOR JAMS AND
THRESHOLDS, FLOOR DRAINS IN ARCHIVES TO HAVE TRAP PRIMERS, AND
MOTORIZED DAMPERS ARE REQUIRED IN SUPPLY & EXHAUST DUCTWORK ON
EACH FLOOR FOR SHUTTING OFF AIRFLOW (4 TOTAL).
SHEET KEYNOTES
1 6" F DOWN THROUGH SLAB.
2 4" F TO FDC.
3 REFER TO CIVIL ENGINEERING DRAWINGS FOR CONTINUATION.
4 STANDPIPE RISER.
5 HOSE VALVE, CAP & CHAIN AT 42" ABOVE INTERMEDIATE STAIR LANDING.
6 FLOOR CONTROL VALVE, FLOW SWITCH, TEST, AND DRAIN.
7 HOUSEKEEPING PAD. REFER TO STRUCTURAL DRAWINGS.
8 PROVIDE DRAIN PAN ABOVE FP CONTROLLER AND PUMP TO PROTECT FROM
ANY WATER LEAKS.
9 BASE BID FOR ARCHIVE TO BE WET FIRE SPRINKLER SYSTEM. ALTERNATE BID
FOR ARCHIVE TO BE PROTECTED BY A COMPLETE WATERLESS CLEAN AGENT
FIRE SUPPRESSION SYSTEM CONSISTING OF CLEAN AGENT TANK(S),
CONTROL PANEL, BATTERY BACKUP, AUXILIARY ALARM FOR CONNECTION TO
BAS, VENTILATION/PURGING SYSTEM, SMOKE/HEAT DETECTORS,
AUDIBLE/VISUAL ALARMS & STROBES, BOTTLE SOLENOID VALVES, PRESSURE
MONITORS OF BOTTLES, ABORT SWITCH, HOLD OFF SWITCH, REMOTE STATUS
SWITCH, SIGNAGE, PIPING, NOZZLES, ETC. BY FIRE PROTECTION
CONTRACTOR. DETECTORS, WIRING, WIRING TO FIRE ALARM PANEL BY THE
FIRE ALARM CONTRACTOR.
10 DEPOT WILL NOT HAVE FIRE SUPPRESSION. FIRE PROTECTION CONTRACTOR
TO PROVIDE A ROW OF SPRINKLER HEADS AT 6 FT MAXIMUM SPACING IN
CEILING OF CONNECTOR ADJACENT TO EXISTING WALL OF DEPOT.
11 CONNECTOR TO HAVE FIRE SUPPRESSION FROM MAIN BUILDING.
12 TO FIRST FLOOR SPRINKLERS.
1/8" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN DEPOT4
#DESCRIPTION DATE