Outside Air Kit
Installation Instructions
Model: AK~MST . cC~US
LISTED
The Outside Air Kit can be Instaiied to lI1e fOllowing
CFM Specially Home Products Series fireplacas to
bring combustion air to the fire chamber.
36/428AY CR36R1L MSF36/42 STR33/36/42
36/42CV CV36 MST36 TF36/42
36/421S CVR36/42 ODSHR42 TL36/42
36/42ST IS36 SC361421A TSH36/42152
BAY36 LST SH36/42 TST42
BC36/42 MR42A SHR36/42/N48/52
BR36142 MRC42A SR36/421A WMC36/42
C36R1L WMC36/421P
The air that is drawn Inlo the nre chamber from
outside the home or unheated area helps relieve the
pressure In the home.
Check Contents of Shipping Carton
campara contents of carton In Figure 1 With. actuel
- - parts received. If any parts are missing, or damaged,
contact Your dealer before starting installation.
NOTE: Four (4) inch Class 1 air duct, material or
metal duct (not suppliad) may be used with AK-MST.
(For Installation in Naw York State. only alumi-
num, noncombustible flexible or type no" metal
duetlng Is permissible.)
Installation Precautions
The duct termination shOUld be located so It Is
exposed to an out-of-<loors opening at least 100
square inches. II tha duct termination must be localed
in a crewl space or basement. be sure the termina-
tion area has 100 square inches of ventilation open..
ing to outside air.
The duct termination must be located So it does not
compete for air flow with exhaust fans, gas vent
hoods or other aIr consuming devices or appliances.
It must not be obstructed by rafters, insulation
materials Of other obstructions. The less restrictIve
the air supply, the better the AK-MST will perform.
It is a good practice to protect your hands and eyas
during InstallatiOn by wearing work gloves and safety
glassas.
p. 001
Inlet Collar
RaIn
Cap
Fig. 1 Carton contents.
CAUTION: Do noflnstall tenminalion info a garage
or other area that could contain flammable liquids
or fumes, or into an attic space.
Installation Instructions
Determine lI1e location 01 the firaplace as described In
the fireplace Installation Manual. Than plan locetion
of the duct termination and the route of the duct rUn
between tha fireplaca and the duct terminetion.
Duct run must ba limited to a maximum distance 0140
leet from the fireplace pipe collar to duct terminalion.
This will provida tfia least restriCtion to air flow. No
more than four (4) 90. elbows can be used. Duct run *
may be horizont",!.,y,e.rtical, inclined or any comb.i,,~.-..
tlD. n 01 tJ}~P.c8;;;Y:..WfJ.~ }.) iijil.i1l;. iWfiJtlKm.t!ir,1W.::,\~j.t J!1~.. ilq~rije..:;;)."
!?l!~;~~~~~~:~~~:;C~~~~~~1~1~~~:ir~-
Kit.
1. Remove and discard the outsida air knockout (or
cover plata) locatad at the center left side Or
bottom right side of the fireplace. Use cara not to
rub ageinst the sharp edges of this opening to
avoid cuts.
2. Attach the Inlet collar with four (4) #10 screws to
the side or bottom of the fireplace. Slide the duct
over the collar and attach the duct to the collar
USing the plastic tie straps or three (3) screws
(screws not provided). Continue attaching the
dueling together using three (3) screws et each
joint until you have installed sufficient duct to arrive
at your duct termination location.
3. At the termination end, Install the duct termination.
This should be installed Irom the outside of the
home. Cut a hole in the desired location approxi-
mately 411" in diameter, C@/k around the hole, and
slide Ihe termination through the opening Irom
outside the home. The ierrninationlrain cap should
btl' ~QuIKetl i::lJuund h:;j fJtlIdlllt:ller [Q Bssure e tIght.
seal. The rain cap opening should be positioned
downward. (Fig. 3) .
7412:280 3/04 Rov.2
Extend panel sheathing
(Interior and exterIOr) full
height.
2. Double-2x4 Bloc~ng at
sheathing panel JOint.
Nail together With 3-1 Gd
nails.
~ III
~
'"
Header er Plan
ID
~ Double-2x4 Blocking at
mld-helqht and top of door
opening. Nail together
v.1th 3-1 Gd nails.
4 Structural Brace sheathing
by Ludlow Coated Products
on extenor surface.~'
gypsum board on Intenor
surface. Attach to framing
and bloc~ng per notes.
+I
~
NOTES:
@ I. Attach Structural Brace sheathlnq to framing and bloc~ng v.1th
7/1 G' crown staples v.1th 1 1/4' leq (I G qage) spaced at 3' o.c. at
panel edges and G' o.c. at Intermediate supports. Attach drywall
to framing and blocking v.1th IG x I 1/4'Iong screws (f ype W or S
Drywall Screws) at 4' o.c. at panel edges and I G' o.c. at
Intermedlilte supports.
@ 2. Shear Panel as shown IS re<iulred at both garage leqs (two
shear panels per home).
@ 3. NI constnJctlon not addressed by thiS detail shall stncty
comp~ v.1th local and current bUilding codes.
I'-<ll/Z' (MN)
(1)
<V
~>>." """" .
IG'-3'
Opening Width
I~'-<l'!
Overall Width
Garage Slab
Final Grade
Garage Leg - Elevation View
Scale: 1/2' - 1'-0'
GARAGE LEG REINFORCEMENT FOR
MODELS IN THE INDIANAPOLIS METROPOLITAN AREA
Estridge Companies
Cannel, Indiana
@ CopYrltjht 200(; by Schwarz Entjlneenntj Group
John D. Schwarz, r.E. Schwarz En':jlneerln':j Group
13023 Lockburn rlace, Fishers, Indiana 4G038 317.579.8927