Loading...
HomeMy WebLinkAbout0187.01 Correspondence CARMEL FIRE DEPARTMENT Fire Prevention Bureau 2 CIVIC SQUARE CARMEL, IN 46032 Phone: (317) 571-2600 Fax: (317) 571-2615 Date Of Notice: 08/31/2006 Inspection Date: 08/30/2006 Inspection Number: 2000010667 MAJESTIC PLAZA 9660 N. AUGUSTA RD. BLDG. # 3 CARMEL, IN 46032- Inspected By: HOYT, GARY A. Notice of fire and lor safety violations: You are hereby notified that a Fire Inspection of your premises has been made. The following Fire Prevention Code Violations are listed on the attached page. Order to comply: The violation(s) could be a peril to the life and safety to the occcupants andlor property. You are hereby notified to have the violation(s) eliminated within Thirty (30) days receipt ofthis notice. Compliance: NotifY this office when violation(s) have been complied to so a reinspection can be made. Right of appeal: You have specific rights including: (I) The right to file a written petition for review ofviolation(s) or order(s) issued within eighteen (18) working days of the above date, to the State Fire Marshal, Department of Building Services, 402 West Washington Street, Suite E241, Indianapolis, Indiana, 46204. (2) The right to request an informal discussion of the violation(s) prior to filing a petition for review. Failure to comply with order: Failure to comply with this order by the time set may result in the following: (I) Institution ofa mandatory and injunctive relief in the enforcement of Indiana Code Chapter 22-14 (2) Revocation or denial of a permit to operate your business. l>~ . # OIO\8"1B HOYT, GARY A, FIRE MARSHAL CARMEL FIRE DEPARTMENT ",f.M.llt) 8'''-1333 SA VE LIVES THROUGH FIRE PREVENTION -. Date Of Notice: 08/31/2006 Inspection Date: 08/30/2006 Inspection Number:200001 0667 MAJESTIC PLAZA 9660 N. AUGUSTA RD. BLDG. # 3 CARMEL IN. 46032- Violation(s) 1000 013 CERTIFY HV AC !MC Chapter I---Section 101.2---Page I of the Indiana Mechnical Code amendments The HV AC units shall be installed in accordance with the Indiana Mechanical Code and all local codes and a letter of certification shall be sent to the Cannel Fire Department. 1000 014 CERTIFY ELECTRICAL !FC Chapter 6---Section 601---Page 43 The electrical installation shall be in conformance with the National Electrical Code, all State and local codes and a letter of certification shall be sent to the Cannel Fire Department Prevention Bureau. 10000 452 ELECTRICAL HAZARDS !FC Chapter 6---Section 605.1---Page 47 Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the Cannel Fire Prevention Bureau, who is responsible for the enforcement of the Indiana Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. (See Notes) 13000 601 MAINTAIN F.R. CONSTRUCTION !FC Chapter 7---Section 703.1---Page 53 The required fire-resistive rating of fire- resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repqired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for passage of pipes, electrical conduit, wires, ducts, air transferopenings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Opening through the fire-resistance-rated assemblies shall be protected by self-closing or automatic-closing doors approved construction meeting the fire protection requirements for the assembly. 7000 331 OPENING PROTECTIVES Unresloved Violation(s) From Previous Inspections Inspection II Code Description There are no unresolved violations Inspector's Remarks: 7000 331 CHAPTER 10; SECTION 1005.3.5 .2; PAGE 120 n FIRE DOORS IN HORIZONTAL EXITS SHALL BE SELF CLOSING OR AUTOMATIC CLOSING WHEN ACTIVATED BY A SMOKE DETECTOR INSTALLED IN ACCORDANCE WITH SECTION 907.11. - INSTALL SELF CLOSING SAVE LIVES THROUGH FIRE PREVENTION ,. Date Of Notice: 08/31/2006 Inspection Date: 08/30/2006 Inspection Number:20000 I 0667 MAJESTIC PLAZA 9660 N. AUGUSTA RD. BLDG. # 3 CARMEL IN. 46032- Violation(s) DEVl CES ON ALL FIRE DOORS. 10000 452 ALL TEMPORARY LIGHTING NEEDS TO BE REMOVED AND PERMENENT LiGHTING FIXTURES INSTALLED IN ACCORDANCE TO THE INDIANA ELECTRiCAL CODE.