DIVISION OF FIRE SAFETY / PLAN
402 W. Washington St., Room E
Indianapolis, IN 46204
To: Owner I Architect I Engineer
Keeler Webb Associates
James P McCann 860332
486 Gradle Dr
Carmie IN 46032
I
I
fax & e-mail: 3175741269. ghare@
"-
The pians, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS-NOT'A>BUILDING PERMIT-All required local permits and licenses must be obtained-prior to'beginningconstruction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
New Fees Schedule will be effective from September 30,2006 CLICK TO VIEW NEW RATES
Note :(A 1A & A 1 B): In accordance with the affidavit sworn under penalties of pe~ury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false;information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a fine up to $10,000.
In accordance with Section 19 of the General Administrative Rules (675 lAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
4G0412AF
3B0302B
3B 1 004G
3B1004E
3B100401
3B1004F
3B111.2
4G0411AA
3C0501A
No addition, alteration, or repair shall reduce existing exit capacities to less than that required under
the provisions of the rules of the Indiana Fire and Building Safety Commission for new construction
in accordance with 675 lAC 12-4-12(d).
The required fire barrier shall have a minimum fire-resistive construction as specified in Section
302.3.3 and Table 302.3.3, IBC (675 lAC 13-2.4).
Fire-reslstance-rated corridors shall be continuous from the point of entry and shall not be
interrupted by intervening rooms in accordance with Section 1004.3.2.5, IBC (675 lAC 13-2.4).
Where more than one exit or exit access doorway is required, the exit access shall be arranged
such that there are no dead ends in corridors more than 20 feet in length in accordance with Section
1004.3.2.3, IBC (675 lAC 13-2.4).
Exit corridors shall be fire-resistance rated In accordance with Section 1004.3.2.1 and Table
1004.3.2.1, IBC (675 lAC 13-2.4).
Corridors shall not serve as suppiy, return, exhaust, relief, or ventilation air ducts or plenums in
accordance with Section 1004.3.2.4, IBC (675 lAC 13-2.4).
Buildings shall be accessible to persons with disabilities in accordance with Section 1.2 (1 through
5) and (2), Part 1, Chapter 11, IBC (675 lAC 13-2.4).
No change in the character or use of any building or structure shall be permitted which shall cause
the building or structure to be c1assiifed within a different occupancy group or within a different
division of the same occupancy group, unless such building or structure complies with or is made to
comply with the current rules of the Indiana Fire Prevention and Building Safety Commission for new
construction for the proposed revised use of the building in accordance with 675 lAC 12-4-11 (c).
Buildings that are heated or mechanically cooled shall be constructed so as to provide the required
thermal performance of the various componenis in accordance with Section 501.1, IECC (675 lAC
Page 1/2
Would you like to reduce your turnaround time?
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA AT
efile24-7@dhs.state.in.us, Or VISIT OUR WEB SITE AT www.in.gov/dhs/osbc
19-3-1).
3B0602
Exterior walls shall have fire-resistance ratings in accordance with Table 602, IBC (675 lAC 13-2.4).
9P0412A Except in dwelling units, a fioor drain shall be installed in a toilet room containing two or more water
closets or a combination of one water closet and one urinal in accordance with Section 412, IPC
(675 lAC 16-1.3).
3B0715C Duct penetrations of fire barrier walls shall be protected by fire dampers in accordance with Section
715.5, IBC (675 lAC 13-2.4).
Please be advised that if an administrative review of this action is desired, a written petition for review must be filed at the above address with the
Fire Prevention and Building Safety Commission identifying the matter for which a review is sought no later than eighteen (18) days from the above-
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Building Services is closed during normal business hours. In the latter case, the filing deadline will be the first working day thereafter. If you
choose to petition, and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission. If a petition for review is not filed, this Order will
be final, and you must comply with its requirements.
Filed By Code review official Code Enforcement & Plan Review Branch Director
ERIK KASSIG v~d/S~
Address (~~!TI~~ti~le ~f 10c,:,1 offici~.I,street,city,state and ZIP code
DEPT OF COMMUNITY SERVICE State Fire Marshal Vl~O~
JIM BLANCHARD
'ONE CIVIC SQUARE
.CARMEL. IN 46032
Fax & e~mail: 3175712499,jblanchard@carmel.in.gov
Page 2/2