HomeMy WebLinkAbout06060178 Correspondence
ENGINEERING GROUP
13023 lOCkburn PI.ce
Fishers. Indiana 46038
scnwe "eng! nee~n ggrou p. com
October 18, 2006
(),o(ooo~
,-re.... ;'.J \J.---
'Ssr
Mr. Ruben Hinners
Estridge Companies
14300 Clay Terrace Boulevard, Suite 200
Carmel, IN 46032
Re; Grandin Hall Lot 37
Dear Mr. Hinners,
On October 17, 2006 I visited the site referenced above io determine if the framed pilaster in the east wall
of the garage was installed per my design provided to you on August 17, 2006.
This pilaster was specifically designed for this model to resist the wind loading on the garage wall.
The framed pilaster was installed according to design and no other action is required.
I appreciate the opportunity to be of service. Please contact me with any further questions or comments.
Regards,
Schwarz Engineering Group, Inc.
cw dJ~
a~h~ Schwarz, PE
Structural Engineer
.
J
r
~