HomeMy WebLinkAboutC602 STORM PLANS - ROSIES GARDENSSECTION A-A
CONC. PIPE TOE ANCHOR
GROOVED ON
OUTLET END,
TONGUE END
ON INLET
END.
GROOVE (OR TONGUE)
TO BE THE SAME AS ON
STANDARD
REINFORCED
CONCRETE PIPE, ASTM
DESIGNATION C-76.
CLASS "A"
CONCRETE
NOTE:
METAL PIPE END
SECTIONS MAY BE USED
WITH CONCRETE PIPE,
PROVIDING THE METHOD
OF CONNECTION IS
APPROVED BY THE
ENGINEER PRIOR TO
INSTALLATION OF PIPE.
(EXCEPT IN INDIANAPOLIS)
CONCRETE IN THESE END SECTIONS SHALL BE THE SAME GRADE AND STRENGTH
AS SPECIFIED FOR REINFORCED CONCRETE PIPE, A.S.T.M. DESIGNATION C-76 CLASS
III, (AS SET OUT IN INDOT STANDARD SPECIFICATIONS).
REINFORCEMENT IN THE "C" PORTION SHALL BE THE SAME AS SPECIFIED FOR
REINFORCED CONCRETE, A.S.T.M. DESIGNATION C-76 CLASS III, FOR THE SIZE OF
CONNECTING PIPE.
REINFORCEMENT IN THE "B" PORTION SHALL HAVE A CROSS SECTIONAL AREA
EQUAL TO THAT OF ONE LAYER OF STEEL IN THE "C" PORTION.
THE END OF THE PIPE CULVERT SHALL BE PLACED IN THE CONCRETE END SECTION
SO THAT THE FLOW LINES ARE FLUSH. THE JOINT SHALL BE COMPLETELY FILLED
WITH MORTAR.
IN 3:1 OR 4:1 FILL SLOPE, CHANGE TO THE SLOPE OF THE END SECTION IN A
SMOOTH, PLEASING TRANSITION APPROXIMATELY 10'-0" IN LENGTH.
VARIATIONS IN DIMENSIONS - THE THICKNESS OF THE CONCRETE, THE POSITION OF
STEEL, AND THE INTERNAL DIAMETER OF THE PIPE SHALL CONFORM WITH THE
VARIATIONS IN DIMENSIONS AS PROVIDED IN THE SPECIFICATIONS FOR
REINFORCED CONCRETE CULVERT, STORM DRAIN, AND SEWER PIPE, A.S.T.M.
DESIGNATION C-76
WHERE VITRIFIED CLAY CULVERT OR CAST IRON CULVERT PIPE IS USED, A "PIPE
END SECTION" COMPARABLE TO THAT AS SHOWN FOR METAL OR CONCRETE SHALL
BE FURNISHED AND SHALL BE AS APPROVED BY THE ENGINEER, EXCEPT IN AREAS
OF ACID OR MINE WATER THEN THE USE OF METAL END SECTION IS PROHIBITED.
END SECTIONS WILL BE PAID FOR AT THE CONTRACT UNIT PRICE EACH FOR "PIPE
END SECTION" COMPLETE.
CONCRETE PIPE TOE ANCHORS SHALL BE REQUIRED ON ALL CONCRETE PIPE END
SECTIONS. THE COST THEREOF SHALL BE INCLUDED IN THE CONTRACT UNIT PRICE
PER EACH FOR "PIPE END SECTION."
RIP-RAP TO BE
PLACED ON SIDE
SLOPE WHEN
CALLED FOR ON
PLANS.
COMPUTED LENGTH
OF CULVERT
PIPE CULVERT
HOOK
BOLTS
LONGITUDINAL
SECTION
MANHOLE (DIA. "F")
PIPES ENTERING/
LEAVING AT
0-45 DEGREES
FINISH GRADE OR PAVEMENT
MANHOLE (DIA. "F")
PIPES ENTERING/
LEAVING AT
45-90 DEGREES
PIPE SIZE
(DIA. "G")
CASTING FRAME & COVER AS SPECIFIED
ASPHALTIC MASTIC OR BUTYL
RUBBER SEAL BETWEEN ALL
JOINTS.
STANDARD PRECAST
MANHOLE CAP OR ECCENTRIC
CONE. (UP TO 24" PIPE.)
FULL HEIGHT MANHOLE
STEPS AS REQUIRED.
CONCRETE REDUCER CAP
PRECAST CONC.
ADJUSTER RINGS, IF
NEEDED (12 MAX.)
BENCHWALLS AT MINIMUM 1
2" PERFOOT
SLOPE. BENCHWALLS TO BE
CONSTRUCTED TO SPRINGLINE OF PIPE.
INVERT ELEVATION
BASE SHALL BE POURED IN
PLACE OR PRECAST. BOTH
SHALL HAVE #4 BARS-12"
O.C. BOTH WAYS.
BASE SET ON 6"
OF #8 OR #2
STONE
PREFORMED HOLE TO
MAX OF PIPE O.D. + 6"
WITH NON-SHRINK
CEMENT GROUT
NOTE
MANHOLE STEPS SHALL BE POLYPROPYLENE, POLYPROPYLENE COATED STEEL
REINFORCING OR AN APPROVED NON-CORROSIVE FIBERGLASS MATERIAL. THE COPOLYMER
POLYPROPYLENE SHALL MEET THE REQUIREMENTS OF ASTM D-4101 REINFORCED WITH
DEFORMED 3
8" MIN. DIAMETER REINFORCED STEEL CONFORMING TO THE REQUIREMENTS OF
ASTM A-615, GRADE 60. NON-COATED CAST IRON STEPS ARE NOT ACCEPTABLE.
UP TO
60 DEGREES
(NO SCALE)
1 1/2"R.1 1/2"R.
Y
Y
4:1 FILL S
L
O
P
E
3:
1
F
I
L
L
S
L
O
P
E
CLASS "A" CONC.
NOTE
·MANHOLE CONFORMS TO
ASTM C-478
·NO BRICK OR BLOCK WILL BE
ALLOWED IN MANHOLE
·O-RING GASKET ASPHALTIC
MASTIC OR BUTYL RUBBER
SEAL BETWEEN MANHOLE
JOINTS
(NO SCALE)
STANDARD STORM MANHOLE
SLOPE DETAIL
PLAN VIEW SECTION Y-Y
PRECAST CONCRETE END SECTION DETAIL
12"-21"
24"
27"-30"
33"-36"
42"
48"
54"
60"
66"N/A
N/A
N/A
84"
72"
60"
60"
48"
48"48"
60"
60"
72"
84"
96"
N/A
N/A
N/A 96"
96"
96"
N/A
N/A
N/A
N/A
N/A
N/A
REQUIREMENTS FOR ALL STORM SEWER BENCHWALLS
BENCH WALLS SHALL BE SHAPED AND FORMED FOR A CLEAN TRANSITION WITH PROPER
HYDRAULICS TO ALLOW THE SMOOTH CONVEYANCE OF FLOWS THROUGH THE MANHOLE
OR BOX INLET. THE BENCH WALL SHALL FORM A DEFINED CHANNEL, TO A MINIMUM
HEIGHT OF 80-PERCENT OF THE INSIDE DIAMETER OF THE INLET AND OUTLET PIPES TO
FORM A "U" SHAPED CHANNEL, CONSTRUCTED AT A MINIMUM ½-INCH PER FOOT SLOPE
TO THE MANHOLE WALL.
WHERE A FLOW CHANNEL IS CONSTRUCTED AS AN INTEGRAL PART OF THE PRE-CAST
BASE, IT SHALL BE SHAPED AND FORMED AS DESCRIBED ABOVE, WITH THE EXCEPTION
THAT THE BOTTOM OF THE FLOW CHANNEL MAY BE FORMED FROM THE BOTTOM OF
INLET AND OUTLET PIPES IF THE PIPE WALL THICKNESS IS NOT GREATER THAN ONE (1)
INCH.
FOR CAST-IN-PLACE FLOW CHANNELS, THE BOTTOM INVERT OF ALL PIPES ENTERING A
MANHOLE SHALL BE AT LEAST THREE (3) INCHES ABOVE THE TOP OF THE BASE SLAB TO
THE OUTLET INVERT SO THE FINISHED SEWER CHANNEL MAY BE INSTALLED AND
SHAPED.
FOR CONNECTIONS TO EXISTING STORM SEWER STRUCTURES, FLOW CHANNELS SHALL
BE SHAPED, AS SPECIFIED HEREIN, AS IF IT WERE A NEW MANHOLE OR BOX INLET
STRUCTURE.
SPECIFICATIONS FOR ALL STORM SEWER CASTINGS
ALL STORM WATER INLETS AND CATCH BASINS SHALL HAVE THE WORDS "NO DUMPING,
DRAINS TO STREAM", OR SIMILARLY APPROVED MESSAGE, CAST IN RAISED OR
RECESSED LETTERS AT A MINIMUM OF 1" IN HEIGHT. IN ADDITION, A SYMBOL OF A FISH
SHALL ALSO BE CAST WITH THE LETTERS.
(NO SCALE)
Bc
d(MIN.)
66" & LARGER
30" TO 60"
27" & SMALLER
D
6
4
3
GREATER THAN 5' (1)
LESS THAN 5' (2)
B = OUTSIDE DIAMETER
D = INSIDE DIAMETER
d = DEPTH OF BEDDING
MATERIAL BELOW PIPE
TYPICAL BEDDING SECTION - RCP PIPE
MIN. 6" TOPSOIL TO ENSURE
GRASS GROWTH IF NOT UNDER
PAVEMENT.
(1) MIN. 1.25 Bc
(2) 1.25 Bc + 12" (MIN.)
EDGE OF
PAVEMENT, CURB,
GUTTER OR
SIMILAR
STRUCTURE.
(1) REGULAR
BACKFILL
(2) "B" BORROW OR EQUIV.
GRANULAR MATERIAL
COMPACTED TO 95% STANDARD
PROCTOR DENSITY.
"B" BORROW OR EQUIV.
GRANULAR MATERIAL
COMPACTED TO 95% STANDARD
PROCTOR DENSITY.
NOTE:
1) ALL BEDDING & INITIAL
BACKFILL SHALL BE INSTALLED
IN 6" TO 12" BALANCED LIFTS.
2) A MIN. OF 9" CLEARANCE
SHALL BE PROVIDED ON EACH
SIDE OF THE INSTALLED PIPE.
(2) "B" BORROW OR EQUIV.
GRANULAR MATERIAL
COMPACTED TO 95%
STANDARD PROCTOR DENSITY
#8 CRUSHED STONE OR
APPROVED EQUIV. CLASS I
BEDDING MATERIAL HAND
TAMPED OR WALKED INTO
PLACE
TYPICAL BEDDING SECTION - PVC & HDPE
(NO SCALE)
Bc = OUTSIDE DIAMETER
D = INSIDE DIAMETER
D = DEPTH OF BEDDING
MATERIAL BELOW PIPE
(1) REGULAR BACKFILL
EDGE OF PAVEMENT, CURB,
GUTTER OR SIMILAR
STRUCTURE
IN THE PUBLIC RIGHT-OF-WAY
MIN. 6" TOPSOIL
TO ENSURE GRASS
GROWTH IF NOT
UNDER PAVEMENT
Bc
TRASH GUARDS FOR CONC. END SECTIONS
TOP VIEW
SIDE VIEW
842.25843.00 843.00
18" DEEP RIPRAP (1/3 CU.
FT. MIN. SIZE)
3:1 S
L
O
P
E
EMERGENCY OVERFLOW
100 YEAR
ELEV.= 841.28
3:1 SL
O
P
E
EMERGENCY SPILLWAY
(NO SCALE)
NOTES:
1. ALL BEDDING & INITIAL BACKFILL SHALL BE INSTALLED IN 6" TO 12"
BALANCED LIFTS
2. A MIN. 9" CLEARANCE SHALL BE PROVIDED ON EACH SIDE OF THE
INSTALLED PIPE
PAVED AREA INLET TYPE "E"
(NO SCALE)
"DUMP NO WASTE-DRAINS TO WATERWAY"SLOPESLOPE SLOPESLOPE6" CONCRETE
CL
CL
TOP OF CASTING ELEVATION E.J. 5250
NEENAH R-3405
OR EQUAL PAVEMENT
E.J. 5250
NEENAH R-3405
OR EQUAL
CLASS "A" CONCRETE
SECTION A-A
INLET SET ON 6" BASE OF #8 STONE
NOTES:
1. 6" CONCRETE PRECAST OR POURED IN PLACE.
2. REFER TO BEDDING DETAIL AS REQUIRED
3. VAR. PIPE SIZE
21" MAX STRAIGHT CONNECTIONS
15" MAX SKEW CORNER CONNECTIONS
4. MIN. 6" FLAT TOP WITH 24" SQUARE OPENING
5. PIPE CONNECTION TO BE SEALED WITH NON-SHRINK GROUT.
6. STRAIGHT-OUT CONNECTIONS SHOULD NOT BE MADE TO EITHER PRECAST BOX OR INLET WALL TOUCHED
BY A SKEW/CORNER CONNECTION UNLESS SUFFICIENT BOX INLET WALL AREA REMAINS ON EACH SIDE OF
THE CONNECTING PIPE TO ENSURE STRUCTURAL INTEGRITY OF THE PRECAST BOX.
7. A MAXIMUM OF TWO (2) SKEW/CORNER CONNECTIONS WILL BE ALLOWED FOR EACH PRECAST BOX INLET.
8. REFER TO PRECAST CONCRETE ADJUSTING RING DETAIL AS REQUIRED
2 REBAR #5
3.5' EA. WALL
ADJUSTING RING AS
REQUIRED
MIN. 4000 PSI
SAWCUT JOINT
(TYPICAL)C602 STORM DETAILS - ROSIES GARDENSC602STORM DETAILSW22.0156SSRW22.015604/06/2023EACSSRROSIE'S GARDENS10402 N. College Avenue, Carmel, IN 46280"DUMP NO WASTE-DRAINS TO WATERWAY"
10 9abcd 8 7 6efgh109876
5 4 3 2 Part of the NE/4 of Section 11, Township 17 North, Range 3 East, Clay Township, Hamilton County, Indiana1 PREPARED FOR:PROJECT NO.
SHEET NO.abcd5 4 3 2
e1
fhAPPROVAL PENDINGNOT FOR CONSTRUCTIONREVISIONS PER SECOND ROUND OF COMMENTS 08.21.2023SMB1gALLAN H. WEIHE, P.E., L.S. - FOUNDER10505 N. College AvenueIndianapolis, Indiana 46280weihe.netBuild with confidence.SMENGINEERS317 | 846 - 6611800 | 452 - 6408317 | 843 - 0546 faxWEIHELand Surveying | Civil EngineeringLandscape ArchitecturePROJECT NO.:REVISIONS AND ISSUESDATEBYDWG NAME:DESIGNED BY:DRAWN BY:CHECKED BY:DATE:STEVEN SCOTT RUCKER P.E. 11300279