HomeMy WebLinkAboutCorrespondence Page 1 of 1
Conn; Angelina V
From: Nicholas Jahn [nrjahn @vsengineering.com]
Sent: Tuesday, October 16, 2007 1:33 PM
To: Conn,Angelina V
Subject: Medical Drive Shops -Revised Dumpster Location
Attachments: 10-16-07 Revised Dumpster Loc to A Conn.pdf
Ms. Conn,
Attached is a drawing showing the original and revised location of the dumpster for the Medical Drive Shops
Project. If you have any questions concerning this matter please feel free to contact me at anytime.
Sincerely,
Nick Jahn
Nicholas R. Jahn, E.I.
Design Engineer •
VS Engineering, Inc.
4275 N. High School Rd.
Indianapolis, IN 46254
www.vsengineering.com
(317)293-3542 Ext. 137
The information contained in this message is private and may be privileged and confidential. If the reader of this
message is not the intended recipient or responsible for the delivery of the message to the intended recipient(s),
any use of the information is strictly prohibited. If you have received the message in error, immediately notify the
sender and delete/destroy the information and message.
A
10/16/2007
Page 1 of 1
Conn, Angelina V
From: Nicholas Jahn [nrjahn @vsengineering.com]
Sent: Tuesday, July 24, 2007 12:44 PM
To: Conn, Angelina V
Cc: Mukesh Patel
Subject: Medical Drive Shops - Brick Change Request
Attachments: 7-24-07 Original Rendering to A Conn.pdf; 7-24-07 Brick Sample to A Conn.JPG
Dear Ms. Conn:
Some time ago we had a conversation concerning changing the color of brick on the Medical Drive Shops from what was
originally proposed. Attached you will find the original rendering presented to the Department of Community Services as
well as a picture of the brick sample that Mr. Mukesh Patel has chosen. If you have any questions or comments
concerning the proposed change please feel free to contact me at anytime.
Sincerely,
Nick Jahn
Nicholas R. Jahn, E.I.
Design Engineer
VS Engineering, Inc.
4275 N. High School Rd.
Indianapolis, IN 46254
www.vsengineering.com
(317)293-3542 Ext. 137
The information contained in this message is private and may be privileged and confidential. If the reader of this message
is not the intended recipient or responsible for the delivery of the message to the intended recipient(s), any use of the
information is strictly prohibited. If you have received the message in error, immediately notify the sender and
delete/destroy the information and message.
7/25/2007
Mr.Nicholas R.Jahn,E.I.T.
March 22,2007
RE:Medical Drive Shoppes, 154 Medical Drive-Project Review#2
Page 2 of 2
All bonds and performance guarantees must be posted prior to Engineering Department approval of
construction plans. Also,Board of Public Works and Safety approvals and any other governing agency
approvals(if required)must be obtained prior to Engineering Department approval.
The Department reserves the right to provide additional comments based on subsequent reviews.
If you have questions,please contact me at 571-2441.
Sincer-
G.,► . %unc. ,Jr., '
Assistant City ngineer
Department o Engineering
Enclosures
cc: Matt Griffm,Department of Community Services
John Duffy,Cannel Utilities
Paul Pace,Cannel Utilities
Paul Arnone,Cannel Utilities
Greg Ilko,Crossroad Engineers
Mukesh Patel,Medical Drive Shoppes(do VS Engineering)
Engineering Department Review/Project File
IlApps2luser datalenglsharedtDHiMPROJREVOTMEDICALDRSHOPPES#2.doc
[i]m
VS ENGINEERING, INC.
Civil · Structural · Transportation · Environmental
March 2, 2007
Mr. Matt Griffin
Planning Administrator
Department of Community Services
One Civic Square
Carmel, IN 46032
RE: Docket # 06080032 DP/ADLS - Medical Drive Shops I TAC Review Comments
Dear Mr. Griffin:
I have addressed the T AC comments that were received from the following agencies/firms for the
above mentioned project:
1. City of Carmel Engineering Department
2. Crossroad Engineers (Stormwater Review)
3. City of Carmel Water-Wastewater Utilities
I am submitting the following items for your information:
1. T AC Review Commentsl Answers & Original Comments Booklet
2. Design Summary Report
3. 1 Set of Half Size Plans
It should also be noted that this project has received approval from the City of Carmel
Plan Commission as well as the Board of Public Works and Safety.
If you have any questions concerning any of the items submitted or responses to any of
the comments, please feel free to contact me at (317) 293-3542 Ext. 137 anytime.
Sincerely,
~~.~
VS Engineering, Inc.
Enclosure
t..,.
f...,..: ',1'"
Cc
Mr. Mukesh Patel, Owner
~". :...:: J,d;
4275 North High School Road Indianapolis, Indiana 46254
(317) 293-3542 Tel (317) 293-4737 Fax
www.vsengineering.com
'"
[iJm
VS ENGINEERING, INC.
Civil · Structural · Transportation · Environmental
November 9, 2006
Mr. Matt Griffin
Planning Administrator
Department of Community Services
One Civic Square
Carmel, IN 46032
Re: Docket No. 06080032 DP/ADLS: Medical Drive Shopps
Dear Mr. Griffin:
Enclosed are the packets for the November 10, 2006 Plan Commission Packet Submittal
deadline. Included in the packets are the necessary documents and plan sheets per the
Special Studies Committee Meeing on November 2, 2006.
If you have any questions concerning any of the items submitted please feel free to contact me
anytime at (317) 293-3542 Ext. 137.
Sincerely,
e::~,~
Design Engineer
VS Engineering, Inc.
Enclosure
Cc: Mukesh Patel, Medical Drive Shopps
4275 North High School Road Indianapolis, Indiana 46254
(317) 293-3542 Tel (317) 293-4737 Fax
www.vsengineering.com
OW Q g 0-0 32_ Ofpot,s
I. fI
CI - a • EL •
I�r• A'°�-e
October 24,2006 .
JAMES BRAINARD, MAYOR ' � -
Cf .
Mr.Nicholas it Jahn,E.I.T.
VS Engineering,Inc. 5'1 c ,
4275 North High School Road
Indianapolis,IN 46254
RE:Medical Drive Shoppes,154 Medical Drive-Project Review#1
Dear Mr.Jahn:
We have reviewed the construction drawings submitted for this project for the September 20,2006
Technical Advisory Committee meeting. We offer the following comments:
GENERAL INFORMATION
1. The project site is currently within current City of Cannel Corporate Limits.
2. Jurisdictions:
• Street and Right of Way—City of Carmel(Medical Drive)
• Water and Sanitary Sewer-City of Carmel Utilities.
• Storm Sewer/Drainage—City of Carmel. The Hamilton County Surveyor's Office has
jurisdiction over legal drains and discharge to legal drains.
3. Board of Public Works and Safety Approval Requirements:
• Water and Sanitary Sewer Availability approval:
- Water and Sanitary Sewer Availability Approval request to the Board is based upon
EDU requirements as determined by the proposed use of the building. Water and
Sanitary Sewer Connection Fees will be based upon EDU calculations.
- If entryway or other irrigation systems are planned,additional Water Availability
Approval from the Board will be required and additional Water Connection Fees will
be assessed based upon the size and usage of the system.
• Commercial Curb Cut-Please provide 8'h x 11 exhibits to accompany the request for
commercial curb cut approval. Include all pertinent data including radii,drive width at throat
and street,opposing drives etc. As you are modifying the existing cut,Board of Public Works
and Safety approval is required.
• Temporary Construction Entrance-Board approval is required if the temporary entrance is
located at a site other than the proposed curb cut. Please provide exhibits as detailed above,if
applicable.
• Open Pavement Cuts in dedicated streets. Any open pavement cut in the Medical Drive
pavement will require separate Board of Public Works and Safety approval. It appears the
construction of water and sanitary sewer service lines has the potential for open pavement
cuts. If it is possible to directional bore these services lines without open cutting the
pavement,that is what will be expected. If open cutting is unavoidable,prepare letter of
requests to the Board accompanied by detailed drawings of the open cut.
• Secondary Plat approval if applicable.
• Dedication of right of way if applicable.
• Consent to Encroach Agreements for any permanent improvement to be installed within
dedicated right of way and/or dedicated easements.
DEPARTMENT OF ENGINEERING
ONE CIVIC SQUARE, CARMEL, IN 46032 OFFICE 317.571.2441 FAX 317.571.2439
EMAIL engineering @carmel.in.gov
I am enclosing a schedule for Board of Public Works and Safety meeting dates and agenda
deadlines for your use. Please use the Engineering Department deadlines for submissions to the
Board.
Any submission to the Board requires prior final approval by the Cannel Clay Plan
Commission and/or the Board of Zoning Appeals and completion of review by the Technical
Advisory Committee. All written requests to be place on the Board's agenda must include the
appropriate Docket Numbers and the date(or dates)of approval by the Plan Commission
and/or BZA.
4. TAC Review/Drawings submitted for approval:
We request that all comments and comment letters generated by this office be answered in writing
and be accompanied by a drawing reflecting requested revisions. Final drawings will not be
approved for construction until all issues have been resolved. The design engineer must certify all
drawings submitted for final approval. This office will require a minimum of five-sets of
approved drawings after all issues have been resolved and the construction drawings have been
approved. The drawings will be stamped as approved and signed by the City Engineer and by the
Director of Carmel Utilities. The Developer/Owner will receive one-set which is to be maintained
on the construction site at all times. Cannel Utilities will receive two sets. The Engineering
Department Construction Manager will receive one-set and one-set will be maintained in the
Department of Engineering. If more than the minimum of five-sets are requested to be approved,
the additional sets(maximum total of two additional)must be submitted with the five required
sets.
5. Please be advised that any installation of signs,walls,irrigation systems,etc.within dedicated
right of way and/or dedicated easements will require a Consent to Encroach Agreement between
the Owner/Developer and the City of Carmel. This Agreement requires Board of Public Works
and Safety approval.
6. Please provide Carmel Utilities with all initial and subsequent drawings submitted for
review. They will provide a separate review regarding these issues. Please submit to:
Paul Pace,Water Distribution Paul Arnone,Wastewater Collection
City of Cannel Water Utility City of Cannel Wastewater Utility
130 1st Avenue SW 901 North Rangeline Road
Cannel,IN 46032 Cannel,IN 46032
7. Carmel Utilities subscribes to"Holey Moley"who should be contacted for water main and
sanitary sewer main locations.
8. The following items are being included with this review. Please share this information with all
appropriate entities to be involved in this project:
• Equivalent Water and Sanitary Sewer User Contribution Multiplier.
• Current Water and Sanitary Sewer Connection and Availability Fees.
• Commercial Project Approval Procedures.
• Performance Release Procedure.
• Permit Data,Contacts,etc.
• Commercial Permitting Procedures.
BONDING REQUIREMENTS
9. Upon initial review,it appears the following bonding requirements may apply to this project:
Performance/Maintenance Guarantees
This project may be required to provide Certified Engineer's Estimates and
Performance/Maintenance Guarantees for the following improvements:
• Right of Way Improvements including demolition activities in the right of way,construction
of the commercial curb cut or cuts,sidewalks and utility service lines in the right of way.
• Erosion Control, Sediment control,and post construction BMP's
Provide detailed/itemized Certified Engineer's Estimates in the amount of 100%of the cost of
labor and materials for the requested improvements. Provide individual Performance Guarantees
in the amount of the Engineer's Estimates. When the improvements have been constructed and
accepted and the Performance Guarantee is released by our BPWS,3-Year Maintenance
Guarantees will be required in the amount of 15%of the Performance amount for streets and curbs
and 10%of the Performance amount for all other improvements.
Street Cut/Right of Way Permit and Bonding Requirements
Any work in the dedicated right of way of Medical Drive will require a Right of Way Permit. If
the work is included in the scope of work of a required Performance Guarantee,a separate License
and Permit Bond will not be required. If the work is not included in a Performance Guarantee,a
License and Permit bond will be required. The bond amount will be determined by the number of
instances of work in the right of way @$2,000.00 per instance. Oxen navement cuts in
dedicated streets require annroval by our Board of Public Works and Safety. Please contact
Fred Glaser,Department of Engineering Right of Way Inspector/Manager for details regarding
this issue.
10. We have engaged Crossroad Engineers,PC to review all drainage plans and drainage calculations
submitted to this office for review. We will share Crossroad's comments as they are received.
When construction plans are submitted for review for this development,please provide a set of
drawings and drainage calculations directly to Crossroad.
Contact Amanda Foley,City of Cannel Storm Water Administrator,regarding bonding
requirements for erosion control.
AVAILABILITY AND CONNECTION FEES
11. Water and Sanitary Sewer Availability(acreage)Fees this site will not be subject to Water and
Sanitary Sewer Availability Fees.
12. Water and Sanitary Sewer Connection Fees are required to be paid after Engineering
Department approval of the project's construction plans and priorr to obtaining a building permit.
Connection Fees are based upon the EDU calculation of the proposed usage of the building at the
current rate of$1,310.00 per EDU for water and$795.00 per EDU for sanitary sewer. Connection
Fees are current as of the date of this review but are subject to future revisions. Please provide this
office with a detailed list of the various uses planned for these buildings. Following are some
retail uses that may or may not apply to this project:
• Bars&Cocktail Lounges—0.10 EDU/Seat
• Retail Space—1.0 EDU/1000 ft2
• Office—0.50 EDU/1000 ft2
• Restaurant—0.10 EDU/Seat
• Barber Shop—0.30 EDU/Chair
• Beauty Shop—0.90 EDU/Chair
If an irrigation system is planned for this development,additional Water Connection Fees will
be assessed based upon the recommendations of the Director of Camel Utilities.
CONSTRUCTION DRAWING COMMENTS
A seven-page Plan Certification Form is enclosed with this letter. This form was created with the desire
and intent to streamline the plan review process. We request that you please complete this form and return
the original of this form along with complete 24"x 36"civil drawings to the Department of Engineering as
soon as possible. Comments will be generated after the Plan Certification form is returned.
Please treat each item on the form as a requirement of the Department of Engineering. Providing a"no"or
"N/A"response to any of the items does not relieve the Developer of the responsibility of meeting the
requirements of the Department of Engineering. The Department of Engineering will make the final
determination as to the acceptability of any"no"or"N/A"responses.
13. Title Page.
• If the double consonant form is used for the work"Shops',a silent"e"must be at the end of
the word. Please revise to either"Shoppes"or"Shops".
• Revise spelling of Racket Club in the location description.
14. Any on-site and off-site easements necessary for installation of utilities,sidewalks and storm
drainage must be secured prior to the Department of Engineering approving the drawings.
15. Be advised that the City of Cannel has a strict ordinance regarding debris and dirt in dedicated
City Streets. Be prepared to minimize tracking of dirt and debris during demolition and
construction activities at the site. The contractor or contractors may be required to clean Medical
Drive daily at a minimum or more often as required.
16. All paving within the existing and proposed City right-of-way shall conform to the requirements
of the Department of Engineering.Please add a note to the drawings that the Contractor shall
contact the Department of Engineering to schedule a pre-construction meeting to review the
Department's construction requirements,staff notification requirements,required inspections for
certain stages of the work and to review the authority of the Department as it relates to work
within the existing and proposed City right-of-way.
17. ADA ramps are required at all locations where the sidewalks or asphalt paths cross the streets or
entrances.
18. Please delineate the curb and pavement removal required for proposed entrances or removal of
existing to be saw cut,removed,and replaced. Curbs shall be removed to the nearest joint.
19. For sidewalk within the right-of-way,please specify the width of the sidewalks to be 5 feet. Do
not reduce the width of the east end of the sidewalk as shown on Sheet C6.0. Instead maintain the
uniform 5-foot width across the entire frontage.
20. Please add the following notes to the sidewalk detail: "SPACING BETWEEN TRANSVERSE
JOINTS SHALL NOT EXCEED 1.25 TIMES WIDTH,""SIDEWALK BUILT WITH
DRIVEWAYS SHALL HAVE MINIMUM THICKNESS OF 6"OR THICKNESS OF
DRIVEWAY,WHICHEVER IS GREATER,"and"JOINTS SHALL BE TOOLED OR SAWED
TO A DEPTH OF'A THE SIDEWALK THICKNESS." •
21. For curbing,the maximum spacing between transverse expansion joints shall be 50 feet. The
maximum spacing between transverse contraction joints shall be 10 feet on tangent segments and
5 feet on radius segments.
22. Please include the City of Cannel straight curb standard and the City of Cannel roll curb standard
in the plans and replace the curb details indicated.
23. Please remove the Sundown Gardens Landscape Plan,Exterior Elevations(color rendering and
Sheet A2.1)and Site Lighting Plans(Sheets E1 and E1.1)from plans submitted to the Department
of Engineering for approval. The Engineering Department does not approve these items and they
should not be included in drawings submitted to Engineering for review and/or approval. Also
remove these items from the Sitework Drawings Index on Sheet C1.0
24. For subsurface drain within the right-of-way,please add the City of Carmel subsurface drain
standard and add the note"ALL SUBSURFACE DRAIN TO BE DOUBLE WALL HANCOR
HI-Q OR EQUNALENT"in the vicinity of the subsurface drain standard.
25. Please indicate dedication of the Right-of-Way prescribed by the City's 20-year Thoroughfare
Plan if the existing Right-of-Way is not of sufficient width.
26. This project is subject to the Cannel Stormwater Management Ordinance,which was adopted
February 6,2006.
27. Please include the note"THERE SHALL BE NO WATER VALVES OR MANHOLES WITHIN
THE PAVEMENT,CURBS,OR SIDEWALKS,OR ASPHALT PATHS OF THE RIGHT-OF-
WAY"on all appropriate sheets.
28. If it will be necessary to relocate existing utility poles,they must be relocated to within one foot of
the proposed right-of-way. The expense of such relocation shall be borne by the Developer.
29. The Department requires that the construction drawings be developed in accordance with the City
of Cannel digital submission standards and that all required submittals for primary plat,secondary
plat,and construction drawings be made. The digital files must be submitted to the Department of
Engineering prior to approval of the construction plans.
30. The City has adopted a new paving policy. Please revise any notes,specifications,and details to
accommodate this policy. The language of this policy must be added to a specification sheet on
the plans.
31. The City has adopted a new curbing policy. Please revise any notes,specifications,and details to
accommodate this policy.The language of this policy must be added to a specification sheet on the
plans.
32. The portions of commercial driveways within the right-of-way shall be constructed of concrete
and shall have a depressed curb along them to maintain drainage.
33. Please designate the type of interior curb provided surrounding the parking areas on the layout
plan.
34. Indicate and label the curb return radii at the entrance. They must be a minimum of 30 feet.
35. We request that you share all comment letters and enclosures with the Owner/Developer and
eventually with any Contractors chosen to work on this project.
36. Please contact Amanda Foley to review storm water quality aspects of this project.
37. Is a drain needed behind the wall?
38. Is there any benefit to storm water quality to provide a high permeability soil as the swale bottom
to allow infiltration into the wall backfill or is this detrimental to the wall/structure system?
39. Does the oil/water separator remove sediment? Where is the oil trapped? Will it come right out of
the 24"riser pipe without the bottom elevation of this pipe being below the inlet drop tee?
40. If structures NO. 11 and NO. 12 cannot be deleted,these structures shall be new inlets/not
doghouses over the existing pipe.
41. The runoff entering structures 10, 11,and 12 is not being detained and is only being treated once
or not at all. Is it possible to delete structure 11 and regrade the swale so a low point is not
necessary? Can structure 10 be connected to the detention system? Can structure 12 be moved
back onto the site and directed to the detention system?
42. It appears from the storm water summary on Sheet C9.0 that both the 10-year and 100-year peak
runoff exceeds the maximum allowable for the 3"orifice. Due to site constraints,is it not possible
to restrict the peak runoff further?
43. The connection to structure 24 must be performed by a contractor bonded with the City and is
•
subject to inspection by the City.
44. Are curb stops being installed where the parking is adjacent to the wall? Typically,spaces in such
locations are 20'with a parking bumper to protect cars and the wall.
45. Please add GENRAL NOTE 22: "No earth disturbing activity shall commence without a proper
storm water management permit being issued."
46. Please add GENERAL NOTE 22: "No work in the right-of-way shall commence without a proper
right-of-way permit."
47. Please revise NOTE 20: "The contractor shall maintain at least one lane open to traffic at all times
with appropriate approval for such lane restrictions being obtained by the Board of Public Works
and Safety."
48. I know that we have discussed this,but please confirm that structure#29 is or is not in an existing
easement.
49. Sheet C4.0—Please indicate removal and replacement of the existing curb and any mainline
pavement as needed for the new entrance or to replace the curb at the existing eastern entrance if it
is damaged.
50. Please indicate replacement of the removed curbing and pavement on Sheet C6.0 and the
correction or repair of any damaged subsurface drain.
51. Please indicate location of construction entrance on C5.0. Refer to comment 3(c)regarding
Board of Public Works and Safety approval.
52. Please indicate City standard depressed curb across the new entrance unless the existing curb is
roll curb. If the existing curb is roll curb and is in a state of poor repair,indicate for removal and
replacement per City standard.
These comments represent the Department of Engineering's initial review of the construction drawings for
this project. We request that all responses to our comments be provided in writing. Failure to provide
written responses may result in the delay of the review process.
It is critical that our office be made aware of all modifications made on the plans being resubmitted,
particularly if any such changes are considered"new"or fall outside of our previous reviews. Please
provide revised plans including all revisions. Please notify us of any changes and specifically state any
changes,including changes resulting from Plan Commission,BZA or other committee meetings.
All bonds and performance guarantees must be posted prior to Engineering Department approval of
construction plans. Also,Board of Public Works and Safety approvals and any other governing agency
approvals(if required)must be obtained prior to Engineering Department approval.
The Department reserves the right to provide additional comments based on subsequent reviews.
If you have questions,please contact me at 571-2441.
S. re , itz9itm
unc ,Jr.,P.E.
Assistant City- ngineer
Department of ngineering
Enclosures
cc: Matt Griffin,Department of Community Services
John Duffy,Cannel Utilities
Paul Pace,Carmel Utilities
Paul Amone,Cannel Utilities
Greg Ilko,Crossroad Engineers
Mukesh Patel,Medical Drive Shoppes(c/o VS Engineering)
Project File
Engineering Department Review
S:\PROJREV06\MEDICALDRSHOPPES
•
Page 1 of2
Brewer, Scott I
From: Nick Jahn [nrjahn@vsengineering.com]
Sent: Tuesday, October 17, 20064:30 PM
To: Brewer, Scott I
Subject: Re: Medical Drive Shopps - landscape plans
Mr. Brewer:
Scott is going to make the planting details more legible, when I get the revised plan I will forward it on to you.
Here is a breakdown on the prices that I recieved from the contractor for the plants that we will not be providing
Shade Tree $615 per tree installed *
Ornam. Tree $420 per tree installed
Total Commitment to Carmel would be $1203
If you have any questions please feel free to contact me at anytime. Thank you for your time.
Nick
Nicholas R. Jahn, E.I.T.
Design Engineer
VS Engineering, Inc.
4275 N. High School Rd.
Indianapolis, IN 46254
www.vsengineering.com
(317) 293-3542 Ext. 137
The information contained in this message is private and may be privileged and confidential. If the
reader of this message is not the intended recipient or responsible for the delivery of the message to the
intended recipient(s), any use of the information is strictly prohibited. If you have received the message
in error, immediately notify the sender and delete/destroy the information and message.
----- Original Message -----
From: 6Ielllle['~Q..QtU
To: NIcKJaJ:111
Cc: Holmes. Christine B ; Griffin. Matt L ; Conn. Angelina V
Sent: Tuesday, October 17, 2006 3:27 PM
Subject: RE: Medical Drive Shopps - landscape plans
Thank you Nick:
I received the plans and could print them. There is a problem with the size and legibility of the graphic planting
details. The whole graphic, which was apparently lifted from elsewhere, is much too small. The contractors will
have to read from this graphic. Perhaps you could make the landscape notes smaller, but still legible, and then
make the whole details graphic larger. Otherwise the graphic should be submitted on a separate sheet.
Also, we need the monetary commitment for the 24 trees that will not be planted but are required. I can figure a
10/17/2006
Page 2 of2
cost based on my knowledge of tree costs and installation costs for that amount of trees, or you can supply the
figures based on the costs from your contractor. Let me know shortly which you chose to do, or I will go ahead
with my estimate.
Scott Brewer, City Forester
Environmental Planner, DOCS
City of Carmel,
One Civic Square
Carmel, IN 46032
PH: 317-571-2478
FAX: 317-571-2426
From: Nick Jahn [mailto:nrjahn@vsengineering.com]
Sent: Tuesday, October 17, 2006 2:21 PM
To: Brewer, Scott I
Subject: Fw: Medical Drive Shopps
Mr. Brewer
Attached is the new black and white version of the landscaping plan for the Medical Drive Shopps project. If you
have any questions feel free to contact me at anytime. Thanks.
Nick
Nicholas R. Jahn, E.I.T.
Design Engineer
VS Engineering, Inc.
4275 N. High School Rd.
Indianapolis, IN 46254
~,Y~.!mgill~enng.CQm
(317) 293-3542 Ext. 137
The information contained in this message is private and may be privileged and confidential. If the
reader of this message is not the intended recipient or responsible for the delivery of the message to the
intended recipient(s), any use ofthe information is strictly prohibited. If you have received the
message in error, immediately notify the sender and delete/destroy the information and message.
---- Original Message -----
From: Scott Levy
To: nrjahn@vsengineering.com
Sent: Tuesday, October 17,20062:18 PM
Subject: re: Medical Drive Shopps
Nick,
See attachment. Thanks.
Scott Levy
Landscape Designer
10/17/2006
<-- (.00goD-.32; /gipLS
September 27,2006
Mr.Nicholas R. Jahn,E.I.T.
VS Engineering,Inc.
4275 North High School Rd.
Indianapolis,IN 46254 •
RE: Medical Drive Shopps
Dear Mr. Jahn:
The following letter represents comments from the Engineering Depaitnient for this project specifically
addressing the areas of storm water quality. We have reviewed the construction drawings submitted for
this project for the September 20, 2006 Technical Advisory Committee meeting and offer the following
comments:
BONDING REQUIREMENTS
1. The following bonding requirements apply to this project:
Performance Guarantees
An Erosion and Sediment Control Performance Guarantee is needed for this project.
STORMWATER QUALITY REVIEW COMMENTS-CONSTRUCTION PLANS
The following items of the storm water pollution prevention plan have not been satisfied:
B2. Sequence describing storm water quality measure implementation relative to land disturbing
activities
Include construction of the building.
All post construction BMPs should be cleaned at the end of construction.
B6. Sediment control measures for storm sewer inlet protection
The straw bales are not adequate for inlet protection. A catch basin insert would be more
appropriate along the existing street and in the inlets surrounded by pavement(in the parking lot).
A basket inlet protection product would be more appropriate around inlets in grassy areas. For all
other inlets, a mat fastened to the top of the grate will be acceptable.
B7. Runoff control measures
Rock check dams should be used instead of straw bale dams in the swale.
B10. Location,dimensions,specifications,and construction details of each stormwater quality
measure
Erosion control blankets are needed in the swales. Include the detail for an erosion control blanket.
Also include the installation of the erosion control blanket in the construction sequence(B2).
B14. Monitoring and maintenance guidelines for each proposed stormwater quality measure
Inlet protection should be cleaned after every rain event or at least once per week. •
C4. Location dimensions,specifications,and construction details of each stormwater quality
measure
Sizing calculations for the stormceptor are needed.
Need specifications for the swale plantings. Chapter 700 of the City of Carmel Stormwater
Technical Standards Manual contains information regarding water quality swale design
requirements. The north swale needs to meet the minimum 1%slope requirement for a water
quality swale.
C5. Description of maintenance guidelines for post construction storm water quality measures
An O&M manual specifying information regarding maintenance of both of the water quality BMPs
is needed. An owner acknowledgement agreement for the BMPs has been included and should be
completed and submitted with the O&M manual.
We request that all responses to our comments be provided in writing. Failure to provide written responses
may result in delay of the review process.
It is critical that this office be made aware of all modification made on the plans being re-submitted,
particularly if any such changes are considered"new"or fall outside of our previous reviews. Please
provide revised plans indicating all revisions. Please notify us of any changes and specifically state any
changes,including changes resulting from Plan Commission, Special Studies or other committee meetings.
All bonds and performance guarantees(if required)must be posted prior to Engineering Depai intent
approval. Also,Board of Public Works and Safety approval and any other governing agency approvals(if
required)must be obtained prior to Engineering Department approval.
The Department of Engineering reserves the right to provide additional comments based on subsequent
reviews.
If you have questions,please contact the Engineering Depaitinent at 571-2441.
Sincerely,
Amanda Foley
Storm Water Administrator
Department of Engineering
cc: Matt Griffin
Project File
September 25,2006
Sanjay B. Patel, P.E.
VS Engineering, INC.
4275 N. High School Road
'':ldianapolis, IN 46254
RE: Medical Drive Shopps - 06080032 DP/ADLS: Medical Drive Shopps
".
Dear Mr. Patel:
The above-mentioned project information has been received and reviewed.
At the present time, I see nothing in the plans that would hamper law
enforcement efforts.
If we can be of any further assistance to you, please contact us.
Respectfully,
~:D -t.pd)
Michael D. Fogarty
Chief of Police
MDF:vb
cc: Dept. of Community Services
(317) 571-2500
A Nationally Accredit
orcement Agency
Fax (317) 571-2512
09/20/2006 16:43
3177769628
HAMILTON CO SURVEYOR
PAGE 01/01
.'Kenton C. 'Ward, Sun'fYor
rPlitll/l" Cj17) 77~-<~4~.t;
'Fax (J1i-' 77G-~c;;!.,~
Sui/e 1 SS
Gill" :J Inrnilrtlll C("II7~l sqTII,rf
)'{obfCSJli(lc, lndia1lll 460~'h!.Z30
September 19, 2006
VS Engineering, Inc.
ATTN: Bhagwan Patel
4275 North High School Road
Indianapolis, IN. 46254
VIA FACSIMILE: 293-4737
RE: 154 Medical Drive - Medical Drive Shopps
Dear Mr. Patel:
We have reviewed the construction plans submitted to the Hamilton County Surveyor's Office
on September 19, 2006 for this project and have the following comments:
1. This project falls within the corporate limits and MS4 jurisdiction of the City of
Cannel.
2. The proposed project DOES NOT fall in a Carmel Wellhead Protection Zone.
3. The proposed project does not fall in a regulated drain watershed.
4. Please direct all storm sewer questions to the City of Carmel Engineering
Department.
Should you have any questions, I can be reached at 317-776-8495.
Sincerely,
~~
Greg Hoyes, AC
Plan Reviewer
cc: Matt Griffin - Carmel DOCO
Amanda Foley - Cannel Engineering
Dick Hill- Cannel Engineering
Greg IIko - Crossroads Engineers
~m
VS ENGINEERING, INC.
Civil · Structural · Transportation · Environmental
September 6, 2006
Mr. Matt Griffin
Planning Administrator
Department of Community Services
One Civic Square
Carmel, IN 46032
Re: Docket No. 06080032 DP/ADLS: Medical Drive Shopps
Dear Mr. Griffin:
Enclosed are the packets for the October 6, 2006 Plan Commission Submittal. Included in the
packets are the necessary documents and plan sheets per our phone conversation on October
5,2006. As was discussed, the packets are not full construction plan sets, but are reduced sets
containing details of the key elements of the project.
If you have any questions concerning any of the items submitted please feel free to contact me
anytime at (317) 293-3542 Ext. 137.
Sincerely,
~~ITI)L
Design Engineer
VS Engineering, Inc.
Enclosure
Cc: Mukesh Patel, Medical Drive Shopps
4275 North High School Road Indianapolis, Indiana 46254
(317) 293-3542 Tel (317) 293-4737 Fax
www.vsengineering.com
\'
V"'"
~7'
A. ...____
(~
liJ1if
VS ENGINEERING, INC.
Civil · Structural · Transportation · Environmental
",- - ---
,. -
'" -
September 6, 2006
/ ~#
~~ ~
~ }b
g3. ~~~C:>
"
Ms. Christine Barton-Holmes
Planning Administrator
Department of Community Services
One Civic Square
Carmel, IN 46032
\
\
/
/-
~~_.
Re: Docket No. 06080032 DP/ADLS: Medical Drive Shopps
Dear Ms. Barton-Holmes:
Enclosed are the necessary documents for the September 6,2006, TAC Submission. The
following items are being submitted at this time:
1. 1 set of full-size plan documents
2. 3 sets of half-size plan documents
3. 4 design summary reports
4. Check for application fee
If you have any questions concerning any of the items submitted please feel free to contact me
anytime at (317) 293-3542 Ext. 117.
Sincerely,
S;;:, d/M;J
san~I, P.E.
Project Manager
VS Engineering, Inc. .
Enclosure
Cc: Mukesh Patel, Medical Drive Shopps
4275 North High School Road Indianapolis, Indiana 46254
(317) 293-3542 Tel (317) 293-4737 Fax
www.vsengineering.com
City of Carmel
Via email: sbpatel@vsengineering.com
Original by mail
August 30, 2006
Sanjay Patel
VS Engineering
301 East Carmel Drive
Carmel, Indiana 46032
COpy
RE: Medical Drive Shoppes (06080032 DP/ADLS)
Dear Mr. Patel:
This letter is in response to your DP/ADLS application for the Medical Drive Shoppes project.
Comments and concerns are as follows:
1. Please extend the false parapet to completely screen any rooftop mechanicals .
2. Please provide additional details on lighting, including the type oflighting to be
installed on the rear fa~ade.
3. Please provide additional detail on the material to be used in the retaining wall,
including a color elevation.
Please wait to submit revised materials until after the Technical Advisory Committee (TAC) has
met on this application. The resubmitted materials should include edits addressing the above
comments along with any requirements that arise from the TAC meeting. Additional comments
may be made after the requested revisions have been submitted.
S~ CJJ ~,(,
Christine Barton-Holmes
Planning Administrator
06080032 DP/ADLS Medical Drive Shoppes
Page 1
ONE CIVIC SQUARE
CARMEL, INDIANA 46032
317/571-2417
~li?
U Q
VS ENGINEERING, INC.
Civil · Structural · Transportation · Environmental
Re: Medical Drive Shopps
b?IA~LS
., ~---l.C,
, >/ ['\ "<(
/ L~ '".
(\\tCt.\\lt.\) \
,} ~\\G \ '"j
.\;"\Jf:J~ //
.;')-~ . ~ .
I'~I'"
....~
August 17,2006
Ms. Christine Barton-Holmes
Planning Administrator
Department of Community Services
One Civic Square
Carmel, IN 46032
Dear Ms. Barton-Holmes:
Enclosed are the necessary documents for the August 18, 2006 filing deadline. The following
items are being submitted at this time: d
, ( .J- 'j(J\J-e.. 2 CS+a. w..p.e /
1. . copies of the Application for ADLS .C \-e.. (D~'flS 6u.t..k +0
2. Ii copies of the Development Plan Application t-tU \Le '&~ . )
3. 2 sets of plan documents - A .c,
4. Check fgr applic:itiQR fee I a+.er
If you have any questions concerning any of the items that were submitted please feel free to
contact me anytime at (317) 293-3542 Ext. 117.