Project Name: PZ-2023-00282 ADLS Amend - Capital Group Solar Canopies
Workflow Started: 12/6/2023 11:00:11 AM
Report Generated: 02/26/2024 09:12 AM
REF #CYCLE REVIEWED BY TYPE FILENAME DISCUSSION STATUS
1 1 Vectren Energy
Chad Miller
12/19/23 11:49 AM
Comment
Please locate the existing gas service to 12811 N Meridian Street to avoid
any conflicts with the proposed light poles.
Info Only
2 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
ADA parking
Please provide why the ADA parking is being removed from this area
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:42 PM
No change to ADA parking will be made; incorrect site
plan was used.
Resolved
3 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
New parking - missing parking island
Please remove this proposed parking and put the existing parking island
back
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:42 PM
No changes to parking; incorrect site plan was used.
Resolved
4 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
New parking - missing bump out landscaping area
Please remove this proposed parking and put the existing bump out
landscaping area back with ADA parking spcaes
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:43 PM
No changes to parking; incorrect site plan was used.
Plan has been revised to reflect the existing landscaping
island.
Resolved
5 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
New parking - missing bump out landscaping area and parking island
extension
Please remove this proposed parking and put the existing bump out
landscaping area/parking island extension back.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:43 PM
No changes are intended; incorrect site plan was used.
Resolved
8 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
Carmel Drive setback
Please label the setback distance from the nearest point of the canopy to the
nearest point of the southern property line along Carmel Drive.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:44 PM
Setbacks have been labeled on revised site plan - please
enlarge plan when viewing so setbacks become legible.
Resolved
9 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
US-31 setback
Please label the setback distance from the nearest point of the canopy to the
nearest point of the western property line along US-31.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:44 PM
Approximately 300 feet.
Resolved
REVIEW COMMENTS
Plan Review - Review Comments Report
Project Name: PZ-2023-00282 ADLS Amend - Capital Group Solar Canopies
Workflow Started: 12/6/2023 11:00:11 AM
Report Generated: 02/26/2024 09:12 AM
REF #CYCLE REVIEWED BY TYPE FILENAME DISCUSSION STATUS
10 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
Property line label
Please label the property line that splits these two parcels on the site plan
Capital Group Carmel Solar Site Plan v3
-1.pdf
Reviewer Response: Christina Jesse - 1/12/24 10:26 AM
----------------------------------------------------------
Responsed by: Aaron Wilson - 1/9/24 5:25 PM
See revised site plan shows property line in orange
color.
Resolved
11 1 Planning & Zoning
Christina Jesse
12/19/23 11:57 AM
Changemark
Canopies over shared property line
Please provide context on why these canopies are spanning over the
property line.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 3:46 PM
The canopies will have a separation at the property line.
Resolved
12 1 Planning & Zoning
Christina Jesse
12/19/23 12:02 PM
Changemark
Setback to principal building
Please label the setback distance from the nearest point of the canopy to the
nearest point of the principal building.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 6:04 PM
See revised site plan - please enlarge plan when viewing
so setbacks become legible
Resolved
13 1 Planning & Zoning
Christina Jesse
12/19/23 12:02 PM
Changemark
Setback to principal building
Please label the setback distance from the nearest point of the canopy to the
nearest point of the principal building.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 4:28 PM
See revised site plan - please enlarge plan when viewing
so setbacks become legible
Resolved
14 1 Planning & Zoning
Christina Jesse
12/19/23 2:04 PM
Changemark
Dimensions of canopies
Please label the width and lengths of each canopy on the site plan
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 4:28 PM
Arrays have different width based on spacing between
islands; depth is 48.6 feet on the dual arrays and 24.3
feet on the single array.
Resolved
15 1 Planning & Zoning
Christina Jesse
12/19/23 2:19 PM
Changemark
Canopy sizes
Redesign the canopy structures to meet the minimum 9' distance between
canopies and parking islands for future tree canopy growth.
Capital Group Carmel Solar Site Plan v3
-1.pdf
Responsed by: Aaron Wilson - 1/9/24 4:10 PM
Distance measurements from edge of canopy to tree
trunk have been reviewed and approved by Mr.
Mindham via Email.
Resolved
16 1 Planning & Zoning
Christina Jesse
12/19/23 3:53 PM
Changemark
Tree preservation
Why are we removing and relocating healthy trees? Please adjust the plans
to preserve healthy trees and install replacements for the stumps per the
Urban Forester.
L010.4 Proposed Landscape Plans.pdf Responsed by: Aaron Wilson - 1/9/24 4:06 PM
See Ref. 18, Mr. Mindham has provided his
recommendations on which trees to preserve which we
will adhere to.
Resolved
Plan Review - Review Comments Report
Project Name: PZ-2023-00282 ADLS Amend - Capital Group Solar Canopies
Workflow Started: 12/6/2023 11:00:11 AM
Report Generated: 02/26/2024 09:12 AM
REF #CYCLE REVIEWED BY TYPE FILENAME DISCUSSION STATUS
17 1 Transportation
Systems
David Littlejohn
12/21/23 2:32 PM
Comment
Please ensure that both of the sidewalks connections in the parking lot
comply with ADA standards to provide an ADA compliant accessible route
from the path along Pennsylvania to the building entrances.
Responsed by: Aaron Wilson - 1/31/24 3:49 PM
The curbs for the sidewalk at 12911 N Meridian will be
converted to ADA compliant ramps to provide an
accessible route from our building to Pennsylvania
Street. A proposal has been obtained from Howard
Companies to install 10 ramps.
----------------------------------------------------------
Reviewer Response: David Littlejohn - 1/24/24 11:47 AM
The northern (diagonal) sidewalk through the parking
lot has curbs on the edges of each island that do not
provide an accessible route from the path along
Pennsylvania to the building. Converting the curbs to
ADA ramps would provide an ADA compliant accessible
route. Please revise the plans to convert this sidewalk
so it is accessible.
----------------------------------------------------------
Responsed by: Aaron Wilson - 1/9/24 3:49 PM
Existing sidewalks from Pennsylvania to the buildings
will not be changed as part of this project. Please
indicate what changes are needed in case the existing
sidewalks currently do not meet ADA compliance.
Resolved
18 1 Urban Forestry
Daren Mindham
12/22/23 9:01 AM
Changemark
Per email sent 12.22.23
I have provided three options for landscaping changes via email - also see
below. I have a pdf in the correspondence folder noting these options.
Option 1: Remove noted islands and pave over for solar and parking. Parking
lot island space will be added to other parking lot islands as noted,
essentially doubling of some islands, and removing others for a net zero
change. Option 2: Remove noted islands and pave over for solar and
parking. Parking lot island spaces will need to be relocated along both sides
of entrance where existing parking spaces will be removed. Option 3:
Remove all island landscaping as proposed (except the existing trees on the
6 islands where there is a current walkway and replace with landscaping as
proposed. *Solar panels must be placed at least a 9â (1 parking space) from
each island in all options.
L010.4 Proposed Landscape Plans.pdf Responsed by: Aaron Wilson - 1/9/24 4:25 PM
Will be implementing option 3 in addition we will also
keep few other trees as discussed during the site walk.
Updated plans were provided and approved via E-mail.
Resolved
Plan Review - Review Comments Report
Project Name: PZ-2023-00282 ADLS Amend - Capital Group Solar Canopies
Workflow Started: 12/6/2023 11:00:11 AM
Report Generated: 02/26/2024 09:12 AM
REF #CYCLE REVIEWED BY TYPE FILENAME DISCUSSION STATUS
19 1 Planning & Zoning
Christina Jesse
12/22/23 10:17 AM
Comment
Please upload a photometric plan showing the illumination levels across
both parcels beyond the property lines in foot-candles for both the new
proposed canopy lights as well as the parking lot pole lights to remain on
site.
Responsed by: Aaron Wilson - 2/20/24 9:42 AM
Updated plans have been submitted.
----------------------------------------------------------
Responsed by: Aaron Wilson - 1/31/24 3:56 PM
Noted, will update plan.
----------------------------------------------------------
Reviewer Response: Christina Jesse - 1/12/24 10:22 AM
Please provide foot-candle levels at property lines.
----------------------------------------------------------
Responsed by: Aaron Wilson - 1/9/24 3:48 PM
Plan will be part of the permit submittal. Will this
suffice?
Resolved
20 1 Engineering
Alex Jordan
12/22/23 11:45 AM
Comment
We will require a right-of-way permit application and $5,000 license and
permit bond for this project. Please apply for this here:
https://cw.carmel.in.gov/PublicAccess/login
Responsed by: Aaron Wilson - 1/9/24 3:40 PM
Noted. We will apply for right-of-way permit prior to
start of construction.
Info Only
21 1 Building & Code
Services
Mike Sheeks
12/22/23 2:57 PM
Comment
Please see parking spot comments. Thank you!
Responsed by: Aaron Wilson - 1/9/24 3:37 PM
See notes below.
Resolved
22 1 Hamilton County
Surveyor
Samuel Clark
12/29/23 12:19 PM
Comment
PLEASE PROVIDE DRAINAGE CALCULATIONS THAT DETAIL THE IMPACT ON
VOLUME OF WATER LEAVING THE SITE AS A RESULT OF SOLAR PANELS.
WILL THERE BE AN INCREASED RELEASE RATE OR INCREASED AMOUNT OF
IMPERVIOUS SURFACE? BE SURE TO VERIFY THAT THE OUTLET POINTS
HAVE ADEQUATE CAPACITY. CONTACT OUR OFFICE IF YOU NEED ANY
DRAINAGE CALCULATIONS FOR THE PARKWOODS CROSSING ARM OF THE
CLARA KNOTTS REGULATED DRAIN
Responsed by: Aaron Wilson - 1/9/24 4:02 PM
We will not be adding impervious surfaces or modifying
the existing drain paths; down spouts from the canopies
will be implemented every 27 feet which will drain into
the existing drainage path.
Resolved
23 1 Fire
Carmel Fire
1/3/24 10:41 AM
Comment
Indiana fire Code 503.2.1 Dimensions. Fire apparatus access roads shall have
an unobstructed width of not less than 20 feet (6096 mm), exclusive of
shoulders and an unobstructed vertical clearance of not less than 13 feet 6
in. Provide confirmation the drive lanes in the parking lot between solar
structures will comply with this IFC rule.
Responsed by: Aaron Wilson - 1/9/24 5:31 PM
Smallest width is 21 feet. Vertical clearance is above
13'6".
Resolved
Plan Review - Review Comments Report
Project Name: PZ-2023-00282 ADLS Amend - Capital Group Solar Canopies
Workflow Started: 12/6/2023 11:00:11 AM
Report Generated: 02/26/2024 09:12 AM
REF #CYCLE REVIEWED BY TYPE FILENAME DISCUSSION STATUS
24 1 Fire
Carmel Fire
1/3/24 10:43 AM
Comment
507.5.4 Obstruction. Unobstructed access to fire hydrants shall be
maintained at all times. The fire department shall not be deterred or
hindered from gaining immediate access to fire protection equipment or fire
hydrants. This project shall not cause any fire hydrant or fire department
connection to become obstructed.
Responsed by: Aaron Wilson - 1/9/24 4:01 PM
Fire hydrant access will not be impacted.
Resolved