HomeMy WebLinkAboutAddition G-002 Site Plan pg. 4Hazel Dell Christian Church Existing Building
Building Area:
33, 400 SF
Construction Type:
Type II -N Construction
Area Separation Walls:
Existing area separation wall indicated on the drawing.
Boiler Room Separation:
No Bolier Room serves the building.
Electrical Room Separation:
None required.
Automatic Sprinklers:
Provided throughout to permit nonrated corridor construction.
Corridors:
Corridors are permitted to be nonrated throughout, based upon automatic sprinkler
protection [1004.3.4.3, exc. 5]
log
EXIST TWO —HOUR AREA
SEPARATION WALL
C OVERALL FLOOR PLAN
1/16" 1,_0"
Building Code Summary-Hazel Dell Christian Church
Education Wing Addition
Applicable Code: 2003 Indiana Building Code
Occupancy Classifications:
Church Use- Group A -3 Occupancy [303.1]
Construction Type:
Type II -N Construction [603]
Allowable Area:
Unlimited area permitted for a Group A -3 Occupancy building that is one story, type II -N
construction, without a legitimate stage, and automatic sprinkler protection with 60 feet of
separation [507.9].
Area Separation Walls:
Not required, based upon unlimited area provisions[507.9]
Building Elements Fire resistive Requirements:
Structural frame, roof, and interior partitions are nonrated [Table 6 -A]
Exterior Walls:
Exterior nonbearing walls are nonrated, since at least 40 feet of separation.
Boiler Room Separation:
No Bolier Room serves the building.
Electrical Room Separation:
None required.
Corridors:
Corridors are permitted to be nonrated throughout, based upon automatic sprinkler
protection [1004.3.4.3, exc. 5]
Exit Travel Distance:
110 feet maximum permitted to a corridor or an exit 225 feet maximum permitted to an exit
an additional 100 feet permitted if the last portion of travel is within a corridor[1007.3.3]
Occu ant Load Factors and Occu ant Load Re uirin 2 Exits:
Assembly: Concentrated Use (Youth Room): 7 sf per person, 50 or more occupants.
Assembly: Less Concentrated Use (Classrooms Platform): 15 sf per person, 50 or more
occupants.
Storage: 300 sf per person 30 or more occupants
Youth Room:
3 exits required based upon calculated occupant load of 446. [1004.2.3.4]
Panic Hardware:
Exit doors serving an occupant load of 50 or more, and which are locking or latching, are
required to have panic hardware [1007.3.10].
Automatic Sprinklers:
Provided throughout to permit unlimited area, and to permit nonrated corridor construction.
[904.2.4, 505.2, 1004.3.4.3, exc. 5]
Fire Alarm System:
Required throughout [305.9, 303.9]
STAGE PREP
PLATFORM
ECHANICAL
ELECTRICAL
A105 C
EQUIP. STORAGE
PANTRY
STORAGE
CORRIDOR
CORRID
KITCHEN
WORSHIP
HALLWAY
GATHERING SPACE
1
CORRIDOR
STIBULE
MULTI— PURPOSE
CONFERENCE
ANTS CRAWLERS
OFFICE AREA
8103
FIRST GRADE
2ND GRADE
3RD GRADE
CORRID
CORRIDOR
CHECK —IN
fr) ;I
FOURS
CORRIDOR
TODDLERS WALKERS
EXISTING BUILDING NEW CONSTRUCTION
s
Buildina Size
Existing Building: 33,613 SF
New Addition: 13, 514
SCHMIDT
WW1/ Mr
l ir //A :1'1,4 1
ASSOCIATES
2000 -036
February 26, 2003
Project No
Project Date
Produced
Revision Date
QC REVIEW
CONSTRUCTION DOCUMENTS
NOT FOR CONSTRUCTION
These Drawings and Specifications, and all copies thereof are and
shall remain the property and copyright of the Architect. They shall
be used only with respect to this Project and are not to be used on
any other Project or Work without prior written permission from
the Architect.
Hazel Dell
Christian Church
Education Wing
Addition
OVERALL
FLOOR PLAN
G -002