HomeMy WebLinkAboutElectrical Symbols and Details - E7.01Switch leg or Go-between
All conductors #12 AWG
Circuit No. designation
All conduit 3/4" unless
may be in 1/2" size, others as noted.
1. #12 AWG is min. conductor size except as noted.
2. 3/4" conduit is min. Size except as capacity
permitting 24 volt control conductors and switchlegs
3. 1/2" is min. Flexsteel, Greenfield and Sealite size.
Notes:
AL1-1,3,5 otherwise noted
otherwise noted
Ground conductor(s) (if used)
Panel designation
Phase conductor(s)
Neutral conductor(s)
1
E7.01
Key to Electrical Circuit Wiring
No Scale
2
E7.01
Light Fixture with Battery Backup Wiring Schematic
No ScaleEM/NL - Emergency / Night Light(Non-Switched)Hot
Common
Wall
Switch
Emergency
Ballast
AC
Ballast
Test
Switch
(Primary circuit only. Lamp leads not shown.)
Hot
Common
Emergency
Ballast
AC
Ballast
Test
Switch
(Primary circuit only. Lamp leads not shown.)EM - Emergency(Switched)Electrical Symbols Legend
Lighting
Switches
Power
Fire and Communication
Circuiting
Note
Conduit system concealed above ceiling
Conduit system under floor
Homerun. Conduit system to panel as noted on drawings
Junction box
Conduit up
Conduit down
Surface mounted conduit system
Single pole switch
Single pole key operated switch
Dimmer switch
Fusible switch
Switch with thermal overloads
Three-way switch
Keyed push button kill switch
Disconnect switch
Motor starter
Combination motor starter/disconnect
Duplex receptacle
Quad receptacle
Ground fault interupt receptacle
Weatherproof, ground fault interupt receptacle
Single plex receptacle
Floor mounted duplex receptacle
Fire alarm pull station
Combination fire alarm pull station/horn/strobe
Combination fire alarm horn/strobe
Fire alarm strobe light
Fire alarm smoke detector
Fire alarm duct detector
Fire Alarm Control Panel
Telephone Terminal Board
Duplex receptacle mounted above counter or sink. Coordinate with furniture prior to
installation
Plug strip
Dry-type transformer
Kitchen rough-in
Motor connection
480/277v. Panel board
208/120v. Panel board
Power pole
Special purpose receptacle as noted on drawings
Wall mounted emergency lighting unit
Wall mounted exit sign
Ceiling mounted exit sign
LED downlight with emergency battery backup (switched)
LED downlight
Wall mounted light fixture
2'x2' LED light fixture (volumetric)
Linear LED light fixture (lensed)
2'x4' LED light fixture (lensed) with emergency battery backup (switched)
2'x4' LED light fixture (lensed)
Linear LED light fixture (lensed) with emergency battery backup (switched)
2'x2' LED light fixture (volumetric) with emergency battery backup (switched)
Not all symbols listed above are shown on plans.
The symbol legend is used for reference of
symbols shown on plans. See specifications for
information related to symbols.
WP
EM
EM
EM
EM
LED pendant
Linear LED pendant
Ceiling mounted, omni-directional type dual technology occupancy sensor (standard
range). Refer to Manufacturer's instructions for exact installation requirements prior
to rough-in.
Ceiling mounted, omni-directional type dual technology occupancy sensor (extended
range). Refer to Manufacturer's instructions for exact installation requirements prior
to rough-in.
Wall/corner mounted dual technology occupancy sensor. Refer to Manufacturer's
instructions for exact installation requirements prior to rough-in.
Wall switch type dual technology occupancy sensor. Refer to Manufacturer's
instructions for exact installation requirements prior to rough-in.
Wall switch type dual technology occupancy sensor with minimum fan run-time
(controls lighting load and exhaust fan). Refer to Manufacturer's instructions for
exact installation requirements prior to rough-in.
Camera location. Provide rough-in with 1" conduit to accessible location.
DL
P Nurse call panic pull cord.
Nurse call dome light.
PB Panic button by others. Location shown for coordination purposes.
Note: Where receptacles and voice/data rough-ins are shown, keep locations close
as allowed.
ADA Door operation push pad by others. Location shown for coordination purposes.
Telephone outlet location, 1" conduit with pullwire to above accessible ceiling
Note: Daisy chaining conduits for low voltage rough-in is NOT acceptable.
Telephone/data outlet location, 1" conduit with pullwire to above accessible ceiling
Note: Daisy chaining conduits for low voltage rough-in is NOT acceptable.
Data outlet location, 1" conduit with pullwire to above accessible ceiling
Note: Daisy chaining conduits for low voltage rough-in is NOT acceptable.
4
E7.01
Typical Lay-In Fixture Support Detail
No Scale
Ceiling T-bar
fixture by E.C.
Lay-in type
Ceiling
by E.C.
conduit
Flexible
Structure above
Outlet box
and support
rod by E.C.
Plan View
Ceiling T-bar
Support clips (4 per fixture).
Like Caddy® lay-in and troffer
light fixture support clips
Lay-in type
light fixture
Notes:
1.Lighting fixtures must be supported
independently of ceiling system.
Upon written request to the
engineer, other means of support
will be considered for approval.
2.Light fixture shown may not depict
specific attributes of fixture being
utilized in this project. Refer to
Fixture Legend on Architectural
Reflected Ceiling Plan for fixture
information.
}
Note:
E.C. shall follow this detail for proper
grounding connections.
3/0 CU shunt around water
meter
(Typ. for 3 or 4 rod grounding field)
3/0 CU
10' Min.
Disc. Link
Equipment ground bus
Neutral bus
At Main Distribution Panel (MDP)
To concrete encased electrode (in min. of 2" concrete
within or near bottom of foundation/footing with min. of
20'-0" of bare copper conductor not smaller than #4 AWG.)
Connection to cold
water system
3/0 CUConnection to structural
steel of building
3/0 CU
3/0 CU
3/0 CU3/0 CU
(3) 3/4" copperweld 10' long
ground rods
3/0 CU to water meter
Water meter Cold water pipe
Surge arrestor
3/0 CUTo dry transformer(s)
3
E7.01
Grounding Detail
No Scale
Nurse call duty station. Provide connections to nurse call system per manufacturer
requirements.DS
2'x2' LED light fixture (lensed) with emergency battery backup (switched)
2'x2' LED light fixture (lensed)
EM
Speaker location. Provide rough-in with 1" conduit to accessible location.
E7.01
SJW
SLH
A
B
C
D
E
F
G
H
J
K
L
151413121110987654321
151413121110987654321
A
B
C
D
E
F
G
H
J
K
L
1100 Sycamore Street, Suite 200
Cincinnati, Ohio 45202 - Ph: 513.984.1070
702 N. Capitol Avenue
Indianapolis, Indiana 46204
Ph: 317.636.3980
www.luminaut.com
As NotedPROF
E
SSIONA L E N G NIEERSA M U E L L.HU
R
TINDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
Clay Terrace
Building "D" Demise
14390 Clay Terrace Blvd., Ste 165,
Carmel, IN 46032
IN23057
01/10/24
CONSTRUCTION DOCUMENTSGNIBMULP·LACITCELE·LACINAHCEM R2410 Executive Drive - Suite 100
Indianapolis, Indiana 46241
317.636.3941
www.TEC-MEP.com
THEENGINEERING
C O L L A B ORA
T
I
VEMEP CLARIFICATION 01/18/2024
ELECTRICAL SYMBOLS &
DETAILS