HomeMy WebLinkAboutElectrical Symbols and Details - E7.01Switch leg or Go-between All conductors #12 AWG Circuit No. designation All conduit 3/4" unless may be in 1/2" size, others as noted. 1. #12 AWG is min. conductor size except as noted. 2. 3/4" conduit is min. Size except as capacity permitting 24 volt control conductors and switchlegs 3. 1/2" is min. Flexsteel, Greenfield and Sealite size. Notes: AL1-1,3,5 otherwise noted otherwise noted Ground conductor(s) (if used) Panel designation Phase conductor(s) Neutral conductor(s) 1 E7.01 Key to Electrical Circuit Wiring No Scale 2 E7.01 Light Fixture with Battery Backup Wiring Schematic No ScaleEM/NL - Emergency / Night Light(Non-Switched)Hot Common Wall Switch Emergency Ballast AC Ballast Test Switch (Primary circuit only. Lamp leads not shown.) Hot Common Emergency Ballast AC Ballast Test Switch (Primary circuit only. Lamp leads not shown.)EM - Emergency(Switched)Electrical Symbols Legend Lighting Switches Power Fire and Communication Circuiting Note Conduit system concealed above ceiling Conduit system under floor Homerun. Conduit system to panel as noted on drawings Junction box Conduit up Conduit down Surface mounted conduit system Single pole switch Single pole key operated switch Dimmer switch Fusible switch Switch with thermal overloads Three-way switch Keyed push button kill switch Disconnect switch Motor starter Combination motor starter/disconnect Duplex receptacle Quad receptacle Ground fault interupt receptacle Weatherproof, ground fault interupt receptacle Single plex receptacle Floor mounted duplex receptacle Fire alarm pull station Combination fire alarm pull station/horn/strobe Combination fire alarm horn/strobe Fire alarm strobe light Fire alarm smoke detector Fire alarm duct detector Fire Alarm Control Panel Telephone Terminal Board Duplex receptacle mounted above counter or sink. Coordinate with furniture prior to installation Plug strip Dry-type transformer Kitchen rough-in Motor connection 480/277v. Panel board 208/120v. Panel board Power pole Special purpose receptacle as noted on drawings Wall mounted emergency lighting unit Wall mounted exit sign Ceiling mounted exit sign LED downlight with emergency battery backup (switched) LED downlight Wall mounted light fixture 2'x2' LED light fixture (volumetric) Linear LED light fixture (lensed) 2'x4' LED light fixture (lensed) with emergency battery backup (switched) 2'x4' LED light fixture (lensed) Linear LED light fixture (lensed) with emergency battery backup (switched) 2'x2' LED light fixture (volumetric) with emergency battery backup (switched) Not all symbols listed above are shown on plans. The symbol legend is used for reference of symbols shown on plans. See specifications for information related to symbols. WP EM EM EM EM LED pendant Linear LED pendant Ceiling mounted, omni-directional type dual technology occupancy sensor (standard range). Refer to Manufacturer's instructions for exact installation requirements prior to rough-in. Ceiling mounted, omni-directional type dual technology occupancy sensor (extended range). Refer to Manufacturer's instructions for exact installation requirements prior to rough-in. Wall/corner mounted dual technology occupancy sensor. Refer to Manufacturer's instructions for exact installation requirements prior to rough-in. Wall switch type dual technology occupancy sensor. Refer to Manufacturer's instructions for exact installation requirements prior to rough-in. Wall switch type dual technology occupancy sensor with minimum fan run-time (controls lighting load and exhaust fan). Refer to Manufacturer's instructions for exact installation requirements prior to rough-in. Camera location. Provide rough-in with 1" conduit to accessible location. DL P Nurse call panic pull cord. Nurse call dome light. PB Panic button by others. Location shown for coordination purposes. Note: Where receptacles and voice/data rough-ins are shown, keep locations close as allowed. ADA Door operation push pad by others. Location shown for coordination purposes. Telephone outlet location, 1" conduit with pullwire to above accessible ceiling Note: Daisy chaining conduits for low voltage rough-in is NOT acceptable. Telephone/data outlet location, 1" conduit with pullwire to above accessible ceiling Note: Daisy chaining conduits for low voltage rough-in is NOT acceptable. Data outlet location, 1" conduit with pullwire to above accessible ceiling Note: Daisy chaining conduits for low voltage rough-in is NOT acceptable. 4 E7.01 Typical Lay-In Fixture Support Detail No Scale Ceiling T-bar fixture by E.C. Lay-in type Ceiling by E.C. conduit Flexible Structure above Outlet box and support rod by E.C. Plan View Ceiling T-bar Support clips (4 per fixture). Like Caddy® lay-in and troffer light fixture support clips Lay-in type light fixture Notes: 1.Lighting fixtures must be supported independently of ceiling system. Upon written request to the engineer, other means of support will be considered for approval. 2.Light fixture shown may not depict specific attributes of fixture being utilized in this project. Refer to Fixture Legend on Architectural Reflected Ceiling Plan for fixture information. } Note: E.C. shall follow this detail for proper grounding connections. 3/0 CU shunt around water meter (Typ. for 3 or 4 rod grounding field) 3/0 CU 10' Min. Disc. Link Equipment ground bus Neutral bus At Main Distribution Panel (MDP) To concrete encased electrode (in min. of 2" concrete within or near bottom of foundation/footing with min. of 20'-0" of bare copper conductor not smaller than #4 AWG.) Connection to cold water system 3/0 CUConnection to structural steel of building 3/0 CU 3/0 CU 3/0 CU3/0 CU (3) 3/4" copperweld 10' long ground rods 3/0 CU to water meter Water meter Cold water pipe Surge arrestor 3/0 CUTo dry transformer(s) 3 E7.01 Grounding Detail No Scale Nurse call duty station. Provide connections to nurse call system per manufacturer requirements.DS 2'x2' LED light fixture (lensed) with emergency battery backup (switched) 2'x2' LED light fixture (lensed) EM Speaker location. Provide rough-in with 1" conduit to accessible location. E7.01 SJW SLH A B C D E F G H J K L 151413121110987654321 151413121110987654321 A B C D E F G H J K L 1100 Sycamore Street, Suite 200 Cincinnati, Ohio 45202 - Ph: 513.984.1070 702 N. Capitol Avenue Indianapolis, Indiana 46204 Ph: 317.636.3980 www.luminaut.com As NotedPROF E SSIONA L E N G NIEERSA M U E L L.HU R TINDIA N A 0 N EP1 6 .o 01087 ATS FOET R E TEGIS D ER Clay Terrace Building "D" Demise 14390 Clay Terrace Blvd., Ste 165, Carmel, IN 46032 IN23057 01/10/24 CONSTRUCTION DOCUMENTSGNIBMULP·LACITCELE·LACINAHCEM R2410 Executive Drive - Suite 100 Indianapolis, Indiana 46241 317.636.3941 www.TEC-MEP.com THEENGINEERING C O L L A B ORA T I VEMEP CLARIFICATION 01/18/2024 ELECTRICAL SYMBOLS & DETAILS