April 3, 2007
Mr. Greg Arnold
BLS CONSTRUCTION
5201 Freyn Drive
Indianapolis, IN 46254
f;1' .
(] (S''*'' -t.
r{,fo.~ .
Re: Rooney Residence
Basement Foundation Modification Inspection
1037 Laurelwood
Carmel, Indiana
Carmel Permit Number: 07010005
McComas File No.: TM27034
Dear Mr. Arnold:
The soil conditions, found at the time of excavation, warranted the modification of the soil
underlying the north and west footings of the above referenced residential addition project.
Due to the severely deteriorated condition of the soil under the north and west footings,
excavating and removing the material was, in our engineering opinion, required. In ortlerto
preserve the load carrying ability of the underlying soil, restrained compacted stone was
substituted for the underlying "muck" conditions found upon preparing for the installation of
the new footing.
At our direction the muck conditions were removed directly under the new footings.
Compacted #53's were placed, under the footing, in 6-inch lifts. The Clay soil, surrounding
the stone, restrains the underlying material to provide excellent load carrying capacities,
usually exceeding the capabilities of in-situ materials.
In addition to the modified foundation condition the undermined footing at the front wall of
the home was examined. The undermined conditioned occurred due to the basement
excavation over-dig. The existing footing acts much like an industry standard, precast
concrete lintel. in supporting the four;lding loads above. It Is our opinion that the
undermined footing is adequate to support the loads intended. Care should be taken atthe
time of backfill to replace as much support as can pe, by compacting the fill located under
this footing.
TM27034
Rooney ReSidence Footing Modification Inspection
page 1012
APR-03-2007 08:42 From:
. -
To: 95712499
P.3/3
The above stated opinions are based on the physical evidence present at the time of our
inspection.
Unless further technical assistance is required, the writer considers the above as complete
and sufficient per the scope of engineering work requested, and will provide no further
technical assistance.
Respectfully submitted;
McCOMAS ENGINEERING, INC.
1:-1UJ$
~""'l'Illlltlllll
;to{' ~,~'!..J!o;;"'''''.
# .....Sf:,;;i}\5T€ii".?'J ~
Ii -y~" N ~6',< \
::... ( o. \ .. ~
!!~i 870090 }"" s
~~\ $TP,TEOF ;~!i
~ ~'\. / I_""t;..~ ~
"S:. (('o"o,;?"OIAl'll',.I,.~ >l
..~ \?S .................a \-..;> ~
";;';,/ON-Al 'i..~~#
"II/IIII1l'''\\'
Tim Moehl, P.E.
Registered Engineer
State of Indiana
Registration No: 870090
TM27034
Rooney Residence Fooling Modification Inspection
page 2 01 2
APR-03-2e07 08:42 From:
To: 95712499
P.1/3
"
FAX TRANSM~TT AL
McCOMAS
ENGINEERING
Date: 4.3.07
\'
~ttf'
Structural Engineers
Forensic Engineers
National Consultants
To: Mr. William Hohlt
Company: City of Carmel
Fax No.: 571.2499
1717 East 116'" Street
Suite 200
Carmel. Indiana 46032
From: Tim Moehl. P,E.
Phone: 317-580-0402
Fax: 317-582-0766
www.mccomaseng.com
Project: Rooney Residence Home Addition
Project No.: F27034
Copy:
Number of pages transmitted (including this sheet):
3
Notice: The contents of this faceimile document are personal and confidential and are
intended for review by the Individual listed above only.
Comments;
Mr. Holht;
I am the consultant working with BLS on the above referenced home addition
project. Please find my documentation of our direction of the soil condition repair
in preparation for the footings. If there are any questions, please do not hesitate
to contact me.
Tim