Scope of release
Indiana Department of Homeland Security
DIVISION OF FIRE SAFETY I PLAN REVIEW
402 W. Washington St., Room E245
Indianapolis, IN 46204
joI[g,DO
ARCH ELEC
sm
Type of release
Standard
MECH
Available At Your local Ucence Branch Project name
To: Owner J Architect I Engineer
Aria Group Architects Inc.
James R Lencioni 910057
830 North Blvd. 6
Oak Park IL 60301
SUPPORT HOOSIER SAFETY
Kana Grill
Street address
14395 Clay Terrace Dr
Fax & e~all: 7084451788, jlencionl@arialnc.com
I
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed'below.-THIS'IS NOTABUILDINGPERMIT.-AII required local pe011itS and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable State rules. Any changes in the released plans and/or specifications\must be filed with
and released by this Office before any work is altered. This release m~y be, suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
City
CARMEL
I County
HAMILTON
Note :(A1A & A1B): In accordance with the affidavit sworn under penalties of perjury in the application. for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class 0 felony punishable by a prison te011 and a fine up to $10,000.
..
In accordance with Section 19 of the General Administrative Rules (675 lAC 12-6-19) a complete set of plans and specifications that confo011
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
4G0603AF Plans and specifications for the revised fire suppression system shall be filed with the required
.application, fees,-and complete details in accordance with 675 lAC 12-6- 3(a), 7(h)17 and 675 lAC
13-1-8. (N.F.P.A. #13)
4G0412AF No addition, alteration, or repair shall reduce existing exit capacities to less than that required under
the provisions of the nules of the Indiana Fire and Building Safety Commission for new constnuction
in accordance with 675 lAC 12-4-12(d).
3B111.2 Buildings shall be accessible to persons with disabilities in accordance with Section 1.2 (1 through
5) and (2), Part 1, Chapter 11, IBC (675 lAC 13-2.4).
3C0501A Buildings that are heated or mechanically cooled shall be constnucted so as to provide the required
thermal performance of the various components in accordance with Section 501.1, IECC (675 lAC
19-3-1).
3B0602 Exterior walls shall have fire-resistance ratings in accordance with Table 602, IBC (675 lAC 13-2.4).
3B 1 003H Exit doors from Group A occupancies shall not be provided with a latch or lock unless it is panic
hardware in accordance with Section 1003.3.1.9, IBC (675 lAC 13-2.4).
3B0907A1 The fire alarm system shall be designed as specified in Section 907, IFC (675 lAC 22-2.3) and
N.F.PA 72 (675 lAC 22-2.2-17) in accordance with Section 907, IBC (675 lAC 13-2.4).
3W0907A2 Upon completion of the installation of the fire alarm system, a satisfactory test of the entire system
shall be made. All functions of the system or alteration shall be tested in accordance with Section
907.17, IFPC (675 lAC 22-2.3).
4G0412AC No addition or alteration shall cause an existing building, stnucture, or any part of the permanent
heating, ventilating, air conditioning, electrical, plumbing, sanitary, emergency detection, emergency
communication, or fire or explosion suppression systems to become unsafe or ovel1oaded under
Page 1/2
-:4
Would you like to reduce your turnaround time?
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA AT
efile24-7@dhs..in.gov, Or VISIT OUR WEB SITE AT www.ln.gov/dhslbranchesJplanreview/index.html
the provisions of the rules of the Commission for new construction in accordance with 675 lAC 12-4-
12(c). Note Section 2902, IBC (675 lAC 13-2.4).
Please be advised that if an administrative review of this action is desired, a written petition for review must be filed at the above address with the
Fire Prevention and Building Safety Commission identifying the matter for which a review is sought no later than eighteen (18) days from the above -
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Building Services is closed during nannal business hours. In the latter case, the filing deadline will be the first \M)rking day thereafter. If you
choose to petition, and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission. If a petition for review is not filed, this Order will
be final, and you must comply with its requirements.
Filed By Code review official Code Enforcement & Plan Review Branch Director
ERIK KASSIG
Address (name,title of local official,street,city,state and ZIP code
OEPT OF COMMUNITY SERVICE State Fire Marshal V1~O~
JIM BLANCHARD
ONE CIVIC SQUARE
CARMEL, IN 46032
Fax & e-mail: ~1?5712499,jblanchard@carmel.in.gov