HomeMy WebLinkAboutEP101A - LEVEL 01 ELECTRICAL PLAN-AREA AF
S
S
S
FA
C
P
J J J J J J J J J
F
F F F
F
F
F
FFF
F
F
F
F
J S
S
S
S
F
S
F
S
S
S
S
S
S
S
J
J
F
J
J J
1 1 1 1 1 1 1 1 1
SPRINKLER
111
DOG WASH
110
OFFICE
109
RESTROOM
107
JAN.
108
MAINTENANCE
SHOP
101
MDF
104
VEST
105
Elec & Data
102
11
UH-1
UH-2
UH-2
CAS-1A
UH-3
HP-1
GP2-7
2
3
GP2-13,15
GP2-12,14
3
GP2-10
GP2-8
GP2-9
GP2-9
GP2-17
GP
2
-
17
GP2-19
5
5
5
2
GP2-28,30,32
4
GP2-11
GP2-11
GP2-11
GP2-25,27
6
CAS-2
CAS-3
CAS-4
HP-2
2
GP2-26
UH-1
UH-1
GP2-34
2
7
GP2-36,38
8
9
10
HP-2
CAS-2 9
7
GP2-37,39
GP2-40
GP2-41
GP2-43
GP2-42
GP2-6
GP
2
-
6
GP
2
-
5
GP2-44
GP2-45
GP2-45
1
1
GP2-51
12
12
H1B-6
H1D-10
H1D-11
H1B-5
1
MDF
106
UH-1
CAS-1B
CAS-1B
1
11
13 13
UH-1
EF-1
EF-1
EF-1
AR
C
H
I
T
E
C
T
CL
I
E
N
T
CO
N
S
U
L
T
A
N
T
PR
O
J
E
C
T
DR
A
W
I
N
G
T
I
T
L
E
SE
A
L
SH
E
E
T
PR
O
J
E
C
T
I
N
F
O
RE
V
I
S
I
O
N
S
10
1
7
W
e
s
t
M
a
i
n
S
t
r
e
e
t
Ca
r
m
e
l
,
I
N
4
6
0
3
2
22028
05-19-23
PERMIT SET
EP101A
LE
V
E
L
0
1
E
L
E
C
T
R
I
C
A
L
PL
A
N
-
A
R
E
A
A
N
1/8" = 1'-0"
LEVEL 01 ELECTRICAL PLAN1
GENERAL NOTES
A REFER TO SHEET E-000 FOR GENERAL ELECTRICAL NOTES, SYMBOLS AND
ABBREVIATIONS.
B REFER TO SHEET E-601 FOR PANEL CIRCUIT SCHEDULES.
C ALL EXPOSED CONDUIT MOUNTED BELOW 6'-0" AFF TO BE GRC. USE
GALVONIZED EMT ELSEWHERE.
D COORDINATE ALL CONDUIT PENETRATIONS BETWEEN LEVELS WITH
STRUCTURAL ENGINEER PRIOR TO SLABS BEING POURED.
E UTILIZE MOUNTING INSERTS CAST INTO STRUCTURE/SLAB WHERE
PRACTICAL. COORDINATE ALL INSERTS AND STRUCTURAL ANCHORS WITH
STRUCTURAL ENGINEER PRIOR TO SLABS BEING POURED.
SHEET KEYNOTES
1 PROVIDE ROUGH IN AND 1" CONDUIT FOR FUTURE EV CHARGERS ON
POWER SHARING MODE .THESE ARE TO BE FED FROM LOADCENTERS
FROM ADJACENT CONDOS.
2 PROVIDE 20A,120V,1PH CIRCUIT FOR UH-1. PROVIDE 2#12 AND 1#12 G
IN 1/2" CONDUIT.
3 PROVIDE 20A,208V,1PH CIRCUIT FOR UH-2. PROVIDE 2#12 AND 1#12 G
IN 1/2" CONDUIT.
4 PROVIDE 35A,208V,3PH CIRCUIT FOR UH-3. PROVIDE 3#8 AND 1#10 G IN
3/4" CONDUIT.
5 THIS DUCTLESS SPLIT IS TO RECEIVE POWER AND BE CONNECTED TO
ITS ASSOCIATED HP-1.
6 PROVIDE 40A,208V,1PH CIRCUIT FOR HP-1. PROVIDE 3#8 AND 1#10 G IN
3/4" CONDUIT.THIS IS TO POWER AND BE CONNECTED TP CAS-1A AND
CAS-1B.
7 PROVIDE 15A,208V,1PH CIRCUIT FOR HP-2. PROVIDE 2#14 AND 1#14 G
IN 1/2" CONDUIT.THIS IS TO POWER AND BE CONNECTED TO CAS-2.
8 THIS DUCTLESS SPLIT IS TO RECEIVE POWER AND BE CONNECTED TO
ITS ASSOCIATED HP-3.
9 THIS DUCTLESS SPLIT IS TO RECEIVE POWER AND BE CONNECTED TO
ITS ASSOCIATED HP-2.
10 THIS DUCTLESS SPLIT IS TO RECEIVE POWER AND BE CONNECTED TO
ITS ASSOCIATED HP-4.
11 PROVIDE ROUGH IN AND 1" CONDUIT FOR FUTURE EV CHARGERS ON
POWER SHARING MODE .THESE ARE TO BE FED FROM GP1 PANEL.
12 PIT RECEPTACLE.COORDINATE LOCATION OF DISCONNECT WITH
ELEVATOR INSTALLER PRIOR TO ROUGH-IN.
13 PROVIDE 40A/208V/1PH CIRCUIT FOR EV CHARGER TO BE INSTALLED
DURING CONSTRUCTION.PROVIDE 2#8 AND 1#10 G IN 1" CONDUIT