HomeMy WebLinkAboutEP105A - LEVEL 05 ELECTRICAL PLAN-AREA AF F
S
F
F S
J CR
S
S
S
CAS-3
UH-1 UH-1
HP-4
1
GP4-19
2
GP4-20
2
3
GP4-21,23
GP4-22 4
GP4-24
2
GEF-1
GEF-3
GEF-2
GEF-4
GP4-33
GP4-31GP4-32
6
7
8
5
RTU-5
UH-1
3
2
AR
C
H
I
T
E
C
T
CL
I
E
N
T
CO
N
S
U
L
T
A
N
T
PR
O
J
E
C
T
DR
A
W
I
N
G
T
I
T
L
E
SE
A
L
SH
E
E
T
PR
O
J
E
C
T
I
N
F
O
RE
V
I
S
I
O
N
S
10
1
7
W
e
s
t
M
a
i
n
S
t
r
e
e
t
Ca
r
m
e
l
,
I
N
4
6
0
3
2
22028
05-19-23
PERMIT SET
EP105A
LE
V
E
L
0
5
E
L
E
C
T
R
I
C
A
L
PL
A
N
-
A
R
E
A
A
N
1/8" = 1'-0"
LEVEL 05 ELECTRICAL PLAN1
GENERAL NOTES
A REFER TO SHEET E-000 FOR GENERAL ELECTRICAL NOTES, SYMBOLS AND
ABBREVIATIONS.
B REFER TO SHEET E-601 FOR PANEL CIRCUIT SCHEDULES.
C ALL EXPOSED CONDUIT MOUNTED BELOW 6'-0" AFF TO BE GRC. USE
GALVONIZED EMT ELSEWHERE.
D COORDINATE ALL CONDUIT PENETRATIONS BETWEEN LEVELS WITH
STRUCTURAL ENGINEER PRIOR TO SLABS BEING POURED.
E UTILIZE MOUNTING INSERTS CAST INTO STRUCTURE/SLAB WHERE
PRACTICAL. COORDINATE ALL INSERTS AND STRUCTURAL ANCHORS WITH
STRUCTURAL ENGINEER PRIOR TO SLABS BEING POURED.
SHEET KEYNOTES
1 THIS DUCTLESS SPLIT IS TO RECEIVE POWER AND BE CONNECTED TO
ITS ASSOCIATED HP-3.
2 PROVIDE 20A,120V,1PH CIRCUIT FOR UH-1. PROVIDE 2#12 AND 1#12 G
IN 1/2" CONDUIT.
3 PROVIDE 30A,208V,1PH CIRCUIT FOR HP-4. PROVIDE 2#10 AND 1#10 G
IN 1/2" CONDUIT.THIS IS TO POWER AND BE CONNECTED TO CAS-4.
4 PROVIDE 120V POWER CIRCUIT AND FIRE ALARM CONTROL WIRING
FOR PENTHOUSE ELEVATOR VENT.
5 PIT RECEPTACLE.COORDINATE LOCATION OF DISCONNECT WITH
ELEVATOR INSTALLER PRIOR TO ROUGH-IN.
6 PROVIDE DISCONNECT FOR ELEVATOR CONTROLLER.COORDINATE
LOCATION OF DISCONNECT WITH ELEVATOR INSTALLER PRIOR TO
ROUGH-IN.
7 PROVIDE DISCONNECT FOR ELEVATOR LIGHTS AND
RECEPTACLES.COORDINATE LOCATION OF DISCONNECT WITH
ELEVATOR INSTALLER PRIOR TO ROUGH-IN.
8 PROVIDE DISCONNECT FOR ELEVATOR.COORDINATE LOCATION OF
DISCONNECT WITH ELEVATOR INSTALLER PRIOR TO ROUGH
IN.COORDINATE SIZE OF DISCONNECT,CONDUCTORS AND BREAKER
SIZE WITH ELEVATOR SHOP DRAWINGS PRIOR TO ORDERING.