HomeMy WebLinkAbout07090095 State ReleaserI i
Would you like to reduce your turnaround time?
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANA at http:ih w .in.govldhslflrelbrancheslplan_reviewlindex.html.
This on-line filing is through a secure site, you can use it to submit your project Information, pay the fees and upload your project plans.
As of July 1, 2007 the existing a-file site eft 2 e24 - 7@dho . in. gov will no longer be in service.
Project number Release date
CONSTRUCTION DESIGN RELEASE
328431 09/11/07
;y al Stale Form 41191 (R9/5-98j Construction type Occupancy classification
(1Y l
1aE :r Report Printed on: September 11, 2007 Ike 8-1
rO16 Scope of release
Indiana Department of Homeland Security INDIANA 02 ARCH FDN
STR
DIVISION OF FIRE BUILDING SAFETY 0000
ype of release
PL/11J REVIEW DIVISION I SION Type
402 W. Washington SL, Room E245 Standard
Indianapolis, IN 46204 A?'?"ER sAEEti
Avaxable M Yom Ucd Llwnce ermcn Project name
To: Owner! Architect I Engineer SUPPORT HOOSIER SAFETY Capital Group Indianapolis Expansion Meridian
TVS Interiors Inc Campus Generator Enclosure
Steven W Clem 00074 street address
2700 Promenade Two 12911N Meridian Street
1230 Peachtree St NE
Atlanta GA 30309 city County
'ax & e-mail: 4048686700, sclem@rvsa.com CARMEL HAMILTON
The plans, specifications and application submitted for the above referenced project have been reviewed for compliance with the applicable rules of
the Fire Prevention and Building Safety Commission. The project is released for construction subject to, but not necessarily limited to, the conditions
listed below. THIS IS NOT A BUILDING PERMIT. All required local permits and licenses must be obtained prior to beginning construction work. All
construction work must be in full compliance with all applicable Slate rules. Any changes in the released plans andlor specifications must be filed with
and released by this Office before any work is altered. This release may be suspended or revoked if it is determined to be issued in error, in violation
of any rules of the Commission or if it is based on incorrect or insufficient information. This release shall expire by limitation, and become null and
void, if the work authorized is not commenced within one (1) year from the above date.
CONDITIONS:
Note :(AtA & Al B): In accordance with the affidavit swom under penalties of perjury in the application for construction design release the plans
and specifications filed in conjunction with this project shall comply with all of the applicable rules and laws of Fire Prevention and Building Safety
Commission. Providing false information constitutes an act of perjury, which is a Class D felony punishable by a prison term and a nee up to $10,000.
In accordance with Section 19 of the General Administrative Rules (675 IAC 12-6-19) a complete set of plans and specifications that conform
exactly to the design that was released by the office of the state building commissioner shall be maintained on the construction jobsite as well as a
copy of the design release.
A7 Emergency generator fuel supplies shall be in accordance with Chapter 5, NFPA 37, 2002 edition
(675 IAC 28-1-15).
A7AA Rooms in which emergency generators are housed shall be provided with explosion venting in
accordance with Section 4.4.2, NFPA 37, 2002 (6751AC 28-1-15).
A7A Emergency generators shall be enclosed in rooms of one-hour fire-resistive construction with
openings protected in accordance with Section 4.1.2.3, NFPA 37, 2002 edition (675 LAC 28-1-15).
3810036 There shall be a floor or landing on each side of a door in accordance with Section 1003.3.1.5, IBC
(675 [AC 13-2.4).
4GO603AG This release does not include electrical, mechanical, and plumbing work. Plans and specifications
for adding or remodeling these systems shall be filed as a new project or as one or more partials
before commencing work on those systems in accordance with 675 IAC 12-6-3.
Please be advised that if an administrative review of this action is desired, a written petition for review must be filed at the above address with the
Fire Prevention and Building Safety Commission identifying the matter for which a review is sought no later than eighteen (18) days from the above -
stated date, unless the eighteenth day falls on a Saturday, a Sunday, a legal holiday under State statute, or a day in which the Department of Fire
and Building Services is closed during normal business hours. In the latter case, the filing deadline will be the first working day thereafter. If you
choose to petition, and the before-mentioned procedures are followed, your petition for review will be granted, and an administrative proceeding will
be conducted by an administrative law judge of the Fire Prevention and Building Safety Commission. If a petition for review is not filed, this Order will
he final, and you must comply with its requirements.
Page 1,12
Would you like to reduce your turnaround time?
ELECTRONICALLY FILE YOUR PROJECT WITH STATE OF INDIANAat hHp:ltwww.in.govldhslfirelbrancheslplan_reviewlindex.hlml.
This on-line filing is through a secure site, you can use It to submit your project information, pay the fees and upload your project plans.I
As of July 1, 2007 the existing a-file site efil e24-70dhe. in. gov will no longer be in service.
Filed By
I
Code review official
DEL SCHROEDER
Code Enforcement & Plan Review Branch Director
?/?722<?? GY
Address (name,lille of local offmal,streelpty,state and ZIP code
DEPT OF COMMUNITY SERVICE Slate Fire ktamhal
JIM BLANCHARD n
( {
ONE CIVIC SQUARE
VL/ IY?/
N n• r^• -
CARMEL, IN 46032 U
Fax & e-mail: 3175712499, jdlancharC carmel.in. ov