HomeMy WebLinkAbout07050197 Correspondence (2)Pale 1 of I
Lillard, Sarah N
From: Ellison, Christopher M I C( I
Sent: Tuesday, October 09, 2007 3:51 PM O 0 1
To: Blanchard, Jim E; Lillard, Sarah N D
Cc:
Subject: Red Ellison, Robin Christopher Michigan M; Rd. Knott, Bruce
Failed Inspection
FYI,
I went out to do the Final Inspection to allow a temp. Occupancy for furniture and fixtures at the Red Robin at 991h
and Michigan Rd this afternoon. The Inspection Failed due to the Hood Fire Suppression System not closing
natural gas valves when tripped after multiple attempts. Also we could not complete all the required fire sprinkler
system testing due to the test valves not having the needed clearance to operate. They are not approved for any
type of occupancy at this time, until these problems are corrected. I have a reinspection set up for 1 PM
tomorrow.
Thanks,
Chris
10/9/2007