HomeMy WebLinkAboutCorrespondence TAC u UO~I 0000<6' i.A:c December 5, 2006 ..\ ..--&.....-.:.. ,'y- "- . j/ ~,.~ ", " . '!'ir:rf\\\~~:; ~,(.;..; -' . JAMES BRAINARD, MAYOR \ .r I. \. Mr. Michael B. Jett American Consulting, Inc. 7260 Shadeland Station Indianapolis, IN 46256 '. RE: Methodist Medical Plaza Parking Expansion-Project Review #1 Dear Mr, Jett: We have reviewed the construction plans submitted for this project for review for the October 18, 2006 Technical Advisory Committee. We offer the following comments: GENERAL INFORMATION I. The project site is located within current City of Carmel Corporate Limits. 2. Jurisdictions: . Streets and Right of Way, Pennsylvania Parkway - City of Carmel . Water - City of Carmel Water Utility service area . Sanitary Sewers - Clay Township Regional Waste District service area . Storm SewersfDrainage - City of Carmel . Regulated! Legal Drains - Hamilton County Surveyor's Office. 3. Board ofPubHc Works and Safety Requirements: Cl It does not appear that this project will require Board of Public Works and Safety approvals. l!l Please be adv~ed that any open cuts 01 existing perimeter-dedicated streets under City of Carmel jurlsdiction will require separate Board of Public Works and Safety approval . Any permanent improvement (including irrigation systems) to be installed within dedicated right of way or dedicated easements. This approval would require a Consent to Encroach Agreement between the Owner and the City of Carmel. . Right of Way Dedication (if applicable) I am enclosing a schedule for Board of Public Works and Safety meeting dates and agenda deadlines for your use. Please use the Engineering Department deadlines for submissions to the Board. Any submission to the Board requires prior approval by the Carmel Clay Plan Commission and/or the Board oj Zoning Appeals (if applicable) and completion of review by the Technical Advisory Committee. All written requests to be placed on the Board's agenda must include the appropriate Docket Number and the date (or dates) o[ approval by the Plan Commlsslon and/or the Board oj Zoning Appeals (if applicable). 4. T.A.C. ReviewfDrawings submitted for approval: We request that all comments and comment letters generated by this office be answered in writing and be accompanied by a drawing reflecting requested revisions. Final drawings will not be approved for construction until all Engineering Department and Carmel Utilities issues have been resolved. The design engineer must certifY all drawings submitted for fmal approval. We will require a minimum of four-sets of drawings for approval after all issues have been resolved. The drawings will be stamped as approved and will be signed by the City Engineer. One set will be distributed to the Owner/Developer to be maintained on the construction site. The Engineering Department will retain two sets and Cannel Utilities will receive one set. [fmore than one DEPARTMENT Of ENGINEERING ONE CIVIC SQUARE, CA.RIvIEL. [N 46032 OFFICE 317.571.2441 FAX 317.571.2439 EMAIL engineering@carmeLin.gov I '. u u approved/signed set is desired, we will approve a maximum of two additional sets for a total of six. However, the additional sets must be submitted with the required four sets. 5. Please be advised that any installation of signs, walls, irrigation systems, etc. within dedicated right of way or dedicated easements will require a Consent to Encroach Agreement with the City of Carmel's Board of Public Works andSafetv. 6. We are enclosing copies of the following information for your use: . Commercial Project Approval Procedures . Permit Data, Contacts, etc. BONDING REOUIREMENTS 7. Upon initial review, it appears the following bonding requirements may apply to this project: Performance GuaranteeslEngineer's Estimates Erosion Control It is our assumption that the storm sewers/storm drainage system will be privately owned and maintained. Please contact Amanda Foley, Engineering Department Storm Water Administrator, for erosion control requirements. The amount of the Performance Guarantee is based upon a certified Engineer's Estimate for 100% of the cost oflabor and materials to construct the individual improvements, to be provided by the design engineer. Please provide detailed Engineers Estimates for each improvement including unit costs, quantities,. materials and types of materials, etc. Upon completion and release of individual Performance Guarantees, a three-year Maintenance Guarantee may be required. The Maintenance Guarantee amount is based upon 10% of the Performance amount. Performance Guarantees may be Performance or Subdivision Bonds or Irrevocable Letters of Credit. Please reference the enclosures for more detailed explanation of our procedures. Right of Way Permit and Bonding Any work in the dedicated right of way of Pennsylvania Parkway will require a Right of Way Permit. If the work is included in the scope of work ofa posted Performance Guarantee, no additional bonding will be required. If it is not included, a License & Permit type Right of Way bond will be required in the amount of $2,000.00 per instance of work in the right of way. Any open cut in the pavement of Pennsylvania Parkway will require separate Board of Public Works and Safety approval. 8. We have engaged Crossroad Engineers, PC to review all drainage plans and drainage calculations submitted to this office for review. We will share Crossroad's comments as they are received. When construction plans are submitted for review for this development, please provide 2-sets of plans and calculations to allow us to send the extra set to Crossroad to save some time in the review process. Please contact Crossroad Engineers to obtain a drainage review checklist. The Depamnent will expect .the design submitted for the development of construction drawings to adhere to this checklist. CONSTRUCTION PLAN COMMENTS 9. A seven-page Plan Certification Form has been enclosed. This form was created with the desire and intent to streamline the plan review process. We request that you please complete this form and return it to the Department of Engineering as soon as possible. Additional comments will be provided by the Department of Engineering after the Certification Form is returned. Please treat each item on the form as a requirement of the Department of Engineering. Providing a "no" or "NI A" response to any ofthe items does not relieve the Developer of the responsibility of meeting the requirements of the Department of Engineering. The Department of Engineering will make the fmal determination as to the acceptability of any "no" or "N/A" responses. 10. The addition of an overall site plan that would include the parking expansion area would be very helpful. It is difficultto determine where this parking expansion area is located in relation to Pennsylvania Parkway and the Methodist Medical Plaza. 11. The Engineering Department does not review or approve landscape plans or lighting plans. Please remove Sheets C6.1, Landscape Plans and C7.l, Site Lighting Plan from sets presented to this ., -:' u u Department for approval. Please remove the reference to these sheets from the Index on Sheet CO.l 12. The Department requires that the construction drawings be developed in accordance with the City of Carmel digital submission standards and that all required submittals for primary plat, secondary plat, and construction drawings be made. The digital files must be submitted to the Department of Engineering prior to.approval of the construction plans. 13. The City has adopted a new curbing policy. Please revise any notes, specifications, and details to accommodate this policy. The language of this policy must be added to a specification sheet on the plans. 14. This project is subject to the Carmel Stormwater Management Ordinance, which was adopted February 6, 2006. 15. Erosion and sediment control measures and post-construction best management practices must be bonded. 16. .A storm water management permit is required prior to commencing any earth disturbing activity. This permit is not issued until the construction plans are approved. Please add a note to this effect to the plans and revise General Grading Note 2. 17. Please review erosion and sediment control measures and post-construction best management practice requirements with Amanda Foley. 18. City standard curb is required by ordinance. Please replace the curb detail on C5.l with the appropriate city standard details. 19. Please confum with the Urban Forester requirements for structural soil in the parking lot islands. 20. The City defers to the County for approval of the legal drain easement encroachinent and for approval of the installation of structure #3 on the legal drain. 21. Please indicate the outfall of the existing pipe to the east from existing structure #4. 22. Where is the storm water detention for this expansion provided? If the area was master plarmed, is the proposed "c" value the same value anticipated for this area at the time of master planning or is it less (or higher)? Does the acreage of the expansion match what was anticipated at the time of the master plarming? 23. Please verifY the capacity of the existing piping to convey the new flows from the expansion. 24. A portion of the parking lot drains to storm structure No.6, directly into the legal drain. Is this runoff detained in a downstream facility? If it is not, provisions shall be made to detain the increase in runoff. These comments represent the Department of Engineering's initial review of the development plan for this project. We request that all responses to our comments be provided in writing. Failure to provide written responses may result in the delay of the review process. It is critical that our office be made aware of all modifications made on the plans being resubmitted, particularly if any such changes are considered "new" or fall outside of our previous reviews. Please provide revised plans including all revisions. Please notify us of any changes and specifically state any changes, including changes resulting from Plan Commission, BZA or other committee meetings. All bonds and performance guarantees must be posted prior to Engineering Department approval of construction plans. Also, Board of Public Works and Safety approvals and any other governing agency approvals (if required) must be obtained prior to Engineering Department approval. The Department reserves the right to provide additional comments based on subsequent reviews. If you have questions, please call me at 571-2441. r u u cc: Matt Griffin, Department of Community Services John Duffy/Paul Pace, Cannel Utilities Greg Hoyes, Hamilton COWlty Surveyor's Office Greg Ilko, Crossroad Engineers Project File Engineering Department Review S:\DHILL\PROJREV06\METHODISTMEDICALPLAZAP ARKEXT w Q.~..~ -.... " .. -,' .- '" ...... ',- ~ ' . '. -., . ' . u ~ JQ~UOotJo:~~r~c:: .~ November 21,2006 Mr. Tim King, EI American Consulting, Inc. 7260 Shadeland Station Indianapolis, IN 46256 RE: Methodist Medical Plaza Parking Expansion Dear Mr. King: The Engineering Department has received your comment letter and drawings dated November 15, 2006 based upon the storm water quality review comments of October 18, 2006. These comments have been satisfactorily addressed with the following exceptions: BONDING REQUIREMENTS I. The following bonding requirements apply to this project: Performance Guarantees An Erosion and Sediment Control Performance Guarantee is needed for this project STORMW ATER QUALITY REVIEW COMMENTS-CONSTRUCTION PLANS The following items of the storm water pollution prevention plan have not been satisfied: B6. Sediment control measures for storm sewer inlet protection The note on C4.1 should be corrected to reflect changes to planned inlet protection. 810. Location, dimensions, specifications, and construction details of each sturmwater quality measure The note on C4. I should reflect the statement in your response letter. B14. Monitoring and maintenance guidelines for each proposed stormwatcr quality measure Specific maintenance requirements for the Catch-All inlet protection are needed. C2. Sequence describing stonnwater quality measure implementation The City of Carmel requires that an stormwater leaving a site (post construction) be treated by a minimum of two different water quality BMPs and that the maj or pollutants [rom the project be treated. Although the existing pond was not originally designed as a water quality BMP and has not been demonstrated to meet the City o[ Carmel Stormwater Technical Standards Manual COT post-construction BMPs, the City is accepting it as one of the two required BMPs. This site is being converted from primarily woodland to impervious parking, which can have a significant impact on water quality. Taking these factors into account, a second BMP will still need to be planned, and the major pollutants listed in Cl will need to be addressed. C3. Description of proposed post construction slormwater quality measures C4. Location dimensions, specifications, and constl'uction details of each stormwater quality measure C5. Description of maintenance guidelines for post construction storm water quality measures Submit an executed Ov.rner Acknowledgement Agreement for the second water quality BMF. ,:" q' w u We request that all responses to our comments be provided in writing. Failure to provide written responses may result in delay of the review process. It is critical that this office be made aware of an modification made on the plans being re-submitted, paltieularly if any such changes arc considered "new" or fall outside of our previous reviews. Please provide revised plans indicating all revisions. Please notify us of any changes and specifically state a.ny changes, including changes resulting from Plan Commission, Special Studies or other committee meetings. All bonds and performance guarantees (ifrequired) must be posted prior to Engineering Department approval. Also, Board of Public Works and Safety approval and any other governing agency approvals (if required) must be obtained prior to Engineering Department approval. The Department of Engineering reserves the right to provide additional comments based on subsequent reVIews. [f you have questions, please contact the Engineering Department at 571-2441. Sinct:rely, Amanda Foley Storm Water Administrator Dt:partment of Engineering cc: Matt Griflin Scott Brewer Project File .4 u : ;C:V';K1~'Z\O r1:C-:-~--" u~-L~U c} -11\C. ~: October 18, 2006 Mr. Michael B. Jett American Consulting, Inc. 7260 Shadeland Station Indianapolis, IN 46256 RE: MethodistMedicalPlaza Parking Expansion Dear Mr. Jell: Thc following letter represents comments from the Engineering Departmcntfor this project specifically addressing the areas of storm water quality. We have reviewed the c,onstruction drawings submitted for this project for the October 18, 2006 Technical Advisory Committee meeting and offer the following comrnents: BONDING REQUIREMENTS 1. The following bonding requirements apply 10 this project: Performance Guarantees An Erosion and Sediment Control Performance Guarantee is needed for this project. STORMW ATER QUALITY REVIEW COMMENTS-CONSTRUCTION J>LANS The following items of the storm water pollution prevention plan have not been satisfied: A5. Legal Description of the Project Site I did not see this in the plans. B2. Sequence describing storm water quality measure implementation relative to land disturbing activities A preconstruction meeting should be scheduled with the City of Carmel Engineering Department. There is not any building construction. Make the sequence specific to this project. B4. Sediment control measures for sheet llow areas Where are the refetenced existing pond and wetland loeatcd? B6. Sediment control measures for storm sewer inlet protection The silt fence inlet pro'tectiondetail is the only inlet protect shown. This practice is not acceptable in paved areas. Specify another inlet protection measure for these areas. Straw bales are not a sufficient inlet protection measure either. Inlet protection is needed at the storm inlet in the existing parking lot nearest the conshuction entrance. Alllhe water appears to be draining to two existing storm inlets inside the project limits. Address how these inlets, and the Ihird inlet located inside the construction limits, will be handled during grading and construction. BI0. Location, dimensions, specifications, and construction details of each stormwater quality measure If the ponds are used for sediment control purposes, then they will need to be dredged following construction. Otherwise a plan describing what practices arc needed in order to keep sediment on site. ;" Ii / / ., ~' ~. u u A detail for silt fence was not provided. Ell. Temporary surface stabilization methods appropriate for each season Mulch should be applied with all seed. B12. Permanent surface stabilization specifications Mulch should be applied with all seed. B14. Monitoring and maintenance guidelines for each proposed stormwatcr quality measure Inspection reports may be requested by the City of Carmel, not the Soil and W aler Con~ervation District. The existing adjoining parking lot and all perimeter City slreets shall be monitored daily to prevent sediment from leaving the construction site. Only include those practices specific to this project. C2. Sequence describing.stnrmwater quality measure implementation The City of Carmel requires that all ~torniwater leaving a site (post construction) be treated by a minimum of two different water quality BMPs. A second EMP (in addition to the pond) is required for thi~ project. Due to the amount of trees that will be lost, we reconm1end you consider a permeable pavement'System as your second BMP. C3. Description Of proposed post construction stormwater quality measures C4. Location dimensions, specifications, and construction details of each stormwater quality measure C5. Description of maintenance guidelines for post construction storm water quality measures The included BMP owner agreement should be completed and submitted with the O&M manual for the second BMP. The City of Carmel will require yearly inspection reports of the water quality BMPs. The first will be due one year after the Notice of Termination is submitted. Wc request that all responses to oUr comments be provided in writing. Failure to provide written responses may result in delay of tlle review process. It is critical that this office be made aware of all modification made on the pI arts being re~submitled, particularly if any such changes are considered "ncw" or fall outside of our previous reviews. Please provide revised plans indicating all revisions, Please notify us of any changes and specifically state any changes, including changes resulting from Plan Commission, Special Studies or other committee meetings. All bonds and performance guarantees (if required) must be posted pr:ior to Engineering Department approval. Also, Board of Public Works and Safety approval and any other governing agency approvals (if required) must be obtained prior to Engineering Department approval. The Department of Engineering reserves the right to provide additional conmlents based 011 subsequent reVIews. If YOll have questions, please contact the Engineering Department at 571-2441. Sincerely, Amanda Foley Storm "Vater Administrator Department of Engineering cc: Matt Griffin Project File , /1 I ./ 10/15/2885 15:15 3177759528 U HAMILTON CD SURVEYOR PAGE 1211/02 u ,Xcillon C. 'UJal'OJ Sltn1t.')!OI' 'Ph",,/, U 17.1 77(;"':)4~'S '1-11,'- U I";) i7(;-_')('';:S Slrilc 188 October 16, 2006 American Structurepoint, Inc. AnN: Mike Jett 7260 Shadeland Station Indianapolis. IN 46256.3917 VIA FACSIMILE: 543-0270 . .RE: Meth()did.Me-diCirJl>ll!lz~ I,JafkiQ:g.~~paDsi~n Dear Mr. J en: We have reviewed the construction plans submitted to the Hamilton County Surveyor's Office on October 4. 2006 for this proje(;t and have the following comments: ]. The proposed project fall within the in.coIporated area and MS4 jurisdiction of the City of Carmel. 2. The project falls in the Clara Knotts Regulated Drain Watershed. 3. The proposed project has the Clara Knotts Regulated Drain running tbrough this area. 4. The proposed site DOES NOT fall 1n a CamJ.el Wellhead Protection Area. 5. Please submit the following procedural items to this office. outlet permit (new Structure on Clara Knotts Drain) and Individual Non-enforcement agrcemen.t (encroachments of parking lot in RD.E.). The applications are avaiJable on our website at httv:I/v,.ww,co.hamilton.in.us. go to Departments, Surveyor~ and Forms. 6. As a condition of the outlet penmt,. as-built data will need to be provided to the Hamilton County Swveyor's Office Standards for the new manhole placed on the regulated drain and the TC for the existing casting that i~ being changed.. 10/16/2005 16:15 317776952B U HAMILTON CO SURVEYOR PAGE 132/132 ;' u 7. Structure #3 win not bea1lowed to be a doghouse type structure and must be a full manhole per HCSO Standard Detail D~21 or Dm22. Please note this on the plans so the contractor is aware of this requirement and include the appropriate detail in the construction plans. 8. The casting placed on the Clara Knotts Regulated Drain will need to be per HCSO Standard Detail CT-l and CT~10. Please include these in the construction plans. 9. Please label aU $torm sewers that are part of the Clara Knotts Regulated Drain. 10. Per Indiana Code 36-9-27-33, no landscaping is to be placed in the Clara Knotts Regulated Drain Easement. Sheet C6.I does not show the existing R.D.E. and shows several trees in the easement area. 11. Please submit revised plans after all initial HCSO, Crossroad Engineering. and Cannel Engineering comments have been addressed. 12. Please note that further comments may be necessary at a later date. Should you have any questions, I can be reached at 317-776-8495. ~'~ Greg Boyes, ACl CFM Plan Reviewer cc: Matt Griffin - Cannel DOCD Amanda Foley - Carmel Engin,eering Mike McBride - RCHD Dick Hill - Carmel Engineering Greg Ilko ~ Crossroads Engineers u '~t%- .r.... -~ .; .~~\~b(""~~~~?C... "..' .,., .,~,c1" I~~ City of Carmel Fire Department Headquarters 2 CIVIC SQUARE CARMEL, INDIANA 46032 Voice (317) 571-2600 Fax (317) 571-2615 Fire Prevention Bureau Michael Jett American Consulting, Inc. 74260 Shadeland Station Indianapolis, IN 46256 ~j:: . Meth,~qJsrPI~e..@:t!ill1g~ LETTER OF APPROVAL The undersigned has reviewed the proposed plans for Methodist Plaza Parking and has approved the plans subject to the following: 1, After review of this project, I have no additional requirements to be met at this time 2. 3. 4. 5. 6. Please respond to the above noted condition(s) in writing and submit to our office prior to the scheduled Technical Advisory Meeting for this project. Date: October 12. 2006 By: Gary Hoyt. Fire Marshal Carmel Fire Department Carmd Cbv School, TAC C()lIImn~.17,06 u 11'~O ::II.m. Docket No. 06100006 T AC: Carmel Science and Tech Park. Block 11 Construction Plans The applicant seeks to construct site infrastructure. The site is located at the SE corner of 122nd Street and Carmel Drive and is zoned M3. Filed by Robert Doster of Schneider Engineering for REI Real Estate. CCS: No comment. 11 :45 a.m. Docket No. 06100007 SP: Stafford Lane Subdivision Secondary Plat The applicant seeks approval to plat 50 lots on 29.04 acres. The site is located at 4235 East 146111 Street and is zoned S I . Fi led by Eric Batt of Schneider Engineering, Tnc. for The Drees Company. CCS: No comment. 12:00 pm Docket No. 06100008 TAC: Methodist Medical Plaza Parking Expansion The applicant seeks to expand parking lot into previously approved banked parking area. The site is located at 201 Pennsylvania Parkway and is zoned B5. Filed by Bill Butz of American Consulting for HCPT Indiana LLC. CCS: No comment. 12:15 p.m. Docket No. 06100009 TAC: Police Maintenance Department Expansion The applicant seeks to construct the Cmnel Police Mai ntenance Dep~U1mcnt addition at the existing Carmel Street Department Maintenance facility. The site is located at 3562 West l3ls1 Street and is zoned S1. Filed by Karen Collins of Cripe Engineering for the Carmel Police Department CCS: No comment 12~~0 p.m, Docket No. 06080004 Z and 06080005 ADLS: Global Financial Consultants The applicant seeks rezoning construction approval for a proposed office building and related parking. The site is currently zoned S I, with a request to rezone to the B2 classification. The site is located at 3745 West 98th Street. Filed by Robert Clutter of Clark Quinn Moses Scott and Grahn, LLP for Global Financial Consultants. CCS: No comment. u u ilLJt"lbm e Jl1L t October 6, 2006 Michael B. Jett American Consulting, INC. 7260 Shadeland Station Indianapolis, IN 46256 RE: Methodist Plaza Parking Project No. IN20050482 Dear Mr. Jett: The plans submitted for the above-mentioned project have been reviewed. At the present time, I see nothing in the plans that would hamper law enforce- ment efforts. If we can be of any further assistance to you, please contact us. Respectfully, J#MkdD. ~~_. Michael D. Fogarty Chief of Police MDF:vb cc: Dept. of Community Services 131l71571-2&00 A Nationally Accredit 'forcement Agency IF"x (3]]) 5n-2G1l2 .. . ( \ AMERICAN CONSUL lING, INC. Architects Consultants Engineers 7260 Shadeland Station, Indianapolis, IN 46256 (317) 547-5580 FAX: (317) 543-0270 info@amercons.com LETTER OF TRANSMITTAL Date: 10/3/06 Project Name: Methodist Plaza Parking Project Number: IN20050482 " We are [SJ Enclosed via. C8J Mail D Messenger D Overnight sending you: D Separately D As Requested [g] For Your Review & Comment [8J For Your Information Deliver by: Time: From: Michael B. Jell Remarks: The attached items are being submitted for your review. This project has been filed allhe Carmel Department of Community Service for TAC Application Review. If you have allY questions regarding this project, please contact our office. Th k an . you. D John Duffy D Terry Krueskamp D Cindy Klaiber Carmel City Utilities City of Carmel Information Systems Carmel Postmaster 760 Third Avenue SW Three Civic Square United States Postal Service Carmel, IN 46032 Carmel, IN 46032 275 Med ical Drive Carmel, IN 46032-9998 D Bill Akers D Mark Westermeir D Ron Farrand Carmel/Clay Communications Carmel/Clay Parks Department Carmel/Clay Schools 31 First Avenue NW 760 Third Avenue SW 5201 East 131 st Street Carmel, IN 46032 Carmel, IN 46032 Carmel, IN 46033 D Shirley Hunter D Bill Hohlt D Karyn Ryg Duke Energy Duputy Building Commissioner Carmel DOCS Transportation Systems 16475 South park Drive One Civic Square Coordinator Westfield, IN 46074 Carmel, IN 46032 One Civic Square Carmel, IN 46032 o Jennifer Bruner D Scott Brewer D Gary Duncan/Nick Clay Township Regional Waste District Dept. of Community Services Ridden/Amanda Foley 10701 N. College Ave., Suite A One Civic Square Dept. of Engineering Indianapolis, IN 46280-1098 Carmel, IN 46032 One Civic Square Carmel, IN 46032 D Steve Broermann o Carmel Department D Jason LeMaster Hamilton Co. Engineering/Hamilton Ca. Dept. of Community Services Hamilton County Health Department Highway One Civic Square Hamilton Co. Judicial Center, Suite 30 1700 South 10th Street Carmel, IN 46032 One Hamilton Square Noblesville,lN 46060 Noblesville, IN 46060c2229 D Robert Hendricks o John South o Greg Hoyes Hamilton County Local Emergency Hamilton County Soil & Water Hamilton County Surveyor Office Planning Committee Conservation One Hamilton Square, Suite 146 18100 Cumberland Road 1108 South 9th Street Hamilton County Judicial Center Noblesville, IN 46060-1624 NOblesville, IN 46060 Noblesville, IN 46060 " ,,,.. u u AMERICAN CONSULTING, INC. Architects Consultants Engineers 7260 Shadeland Station, Indianapolis, IN 46256 (317) 547-5580 FAX: (317) 543~0270 info@amercons.col1l LETTER OF TRANSMITTAL We are ~ Enclosed sending you: D Separately via ~ Mail 0 Messenger D As Requested ~ For Your Review & Comment o Overnight D For Your Information Remarks: Deliver by: From: Michael B. Jell Methodist Plaza Parking IN20050482 Time: Date: D Chuck Shupperd D Ron Morris o Jennifer Marlett Vectren Energy Indianapolis Power & light Co. Indianapolis Water Co. PO B'ox 1700 3600 N. Arlington Avenue PO Box 1220 16000 Allisonville Road Indianapolis, IN 46218 1220 Waterway Blvd. Noblesville, IN 46061 Indianapolis, IN 46206 D Jason Kirkman D Gregory IIKO"PE o Gary Hoyt Brighthouse Networks Crossroads Engineering Office of Fire Chief, Fire Station #1 3030 Roosevelt Avenue' 3417 South Sherman Drive Two Civic Square Indianapolis, IN 46218 Beech Grove, IN 46107 Carmel, IN 46032 D Michael Fogarty D Teresa Magee/Mark Wood o Brooke Gajownik Office of Police Chief Panhandle Eastern Pipeline Co. Hamilton County Sheriff's Office Three Civic Square PO Box 38 18100 Cumberland Road Carmel, IN 46032 9371 Zionsville Road Noblesville, IN 46060 Zionsville, IN 46077 D Mike McBride o Shirley Hunter D Dave Klingensmith Hamilton County Highway Duke Energy Carmel Street Department 1700 South 10" Street 1441 s. Guilford Road 3400 W. 131s1 Street Noblesville, IN 46060 Carmel IN 46032 Westfield, IN 46074