HomeMy WebLinkAboutI0825506 Performance Insurance CDsDocument Approval
Client / Tenant Date
Title
Property Manager
Architect / Interior Designer Date
Upon execution, the client and property manager approve all aspects of the scope of work shown
in these documents, including design content, scope of construction and finish selection for the
following phases:
Space Planning
Preliminary Pricing
Construction Documents
Other:_____________________________________
All costs incurred due to misinterpretation of these documents or changes to the project requested
after the execution of this approval shall not be the responsibility of Carson Design Associates and
shall be the sole responsibility of the client / tenant.
1. Contractor is responsible for all the design required to obtain approvals and permits and is
required for complete installation of Mechanical, Electrical and Plumbing systems.
2. The design and installation of Mechanical, Electrical and Plumbing systems shall comply
with all requirements and standards of all applicable codes, governmental regulations,
ordinances and state and local requirements.
3. Contractor shall provide construction drawings and calculations stamped by a professional
engineer licensed in the state of Indiana.
4. Contractor shall submit construction drawings and an application for construction design
release to the state of Indiana Plan Review Division of the Indiana Department of Homeland
Security for the purpose of obtaining the required construction design release(s) for the
Mechanical, Electrical and Plumbing systems.
5. Contractor shall coordinate the requirements of the Mechanical, Electrical and Plumbing
systems as required for complete installation of each system.
6. Contractor shall be responsible for providing appropriate heating, cooling and humidity
control as applicable in all spaces, including existing spaces outside the scope of this
project that are re-configured by the new construction.
7. Contractor shall be responsible for re-wiring existing light fixtures, switches, outlets and
miscellaneous devices as required, including existing light fixtures, switches, outlets and
miscellaneous devices outside the scope of this project that are re-configured by the new
construction.
CARSON
DESIGN
ASSOCIATES
SHEET NUMBER
JOB NO.
STAMP:
CARSON
DESIGN
ASSOCIATES
OF
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 CENTURY OAKS TERRACE
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
11611 N. Meridian St.
11611 N. Meridian St.
11611 N. Meridian St.
G000
EXIT
EXIT
Area of Scope
ADHESIVES & SEALANTS
Section 1: EQ Credit 3.1/3.2 LEED EB
Adhesives, sealants and sealant primers must comply with the requirements of the South Coast Air Quality Management District (SCAQMD) Rule #1168, January 1, 2003 and the rule amendment
of
October 3, 2003. A full copy of the requirements are available at http://www.arb.ca.gov/DRDB/SC/CURHTML/R1168.PDF.
A person shall not apply adhesives, adhesive bonding primes, adhesive primers, sealants, sealant primers, or any other primer which have a VOC content in excess of the limits specified
below.
Please note that if an adhesive is used to bond dissimilar substrates together, the adhesive with the highest VOC content shall be allowed.
VOC Limit, Less Water and Less Exempt Compounds in Grams per Liter for Indoor Applications:
Architectural Applications
Carpet Adhesives 50
Carpet Pad Adhesives 50
Wood Flooring Adhesive 100
Rubber Floor Adhesives 60
Subfloor Adhesives 50
Ceramic Tile Adhesives 65
VCT and Resilient Tile Adhesives 50
Dry Wall and Panel Adhesives 50
Cove Base Adhesives 50
Multipurpose Construction Adhesives 70
Glazing Adhesives 100
Specialty Applications
PVC Welding 285*
CPVC Welding 270*
ABS Welding 400
Plastic Cement Welding 250*
Adhesive Primer for Plastic 250*
Contact Adhesive 80
Special Purpose Contact Adhesive 250
Structural Wood Member Adhesive 140
Substrate Specific Applications
Metal to Metal 30
Plastic Foams 50
Porous Material (except wood) 50
Wood 30
Fiberglass 80
Sealants
Architectural 250
*These are the updated requirements of January 1, 2005. It is assumed that the USGBC will update their requirements based upon those of the SCAQMD.
Aerosol Adhesives are governed by Green Seal Product Standards and Certification
GS-36 with its limits as listed below. The full copy of the requirements are available on the Green Seal website at http://www.greenseal.org/standards/commercialadhesives.htm.
Aerosol Adhesives
General Purpose Mist Spray 65% VOCs by weight
General Purpose Web Spray 55% VOCs by weight
Special Purpose Aerosol Adhesives (all types)70% VOCs by weight
Carpet Adhesives are governed by the Carpet and Rug Institute’s Green Label Testing Program. The description of the requirements can be found on their website at http://www.carpet-
rug.org/drill_down_2.cfm?page=8&sub=8. The criteria for the adhesive testing program are based on a maximum emission factors as follows:
Carpet Adhesives
Total VOC’s 10.00 mg/m2 . hr.
Formaldehyde .05 mg/m2 . hr.
2-Ethyl-1-Hexanol 3.00 mg/m2 . hr.
PAINTS & COATINGS
Section 2: EQ Credit 3.1/3.2 LEED EB
Paints and coatings used on the interior of the building and applied on-site must not exceed the VOC limits and must not include any of the chemical components limited or restricted
by the standards
listed below. This applies to all paints and coatings used on the interior of the building and applied on-site. For topcoat paints the reference standard is Green Seal Standard GS-11,
dated May 20,
Room Name
101
1
A101
SIM
A101
1
1
A101
SIM
- Refer to drawing where shown.
- Door number
- Room Name, Size and Number
Elevation Nnumber
Sheet Number
Section Number
Sheet Number
Detail Number
Sheet Number
Revision
Elevation Target
Enlarged Plan or
Detail
101
1
Wall construction (refer to floor plan) center on window
mullion
Note: Provide tight fit where wall is coped around any window
sill construction.
Black neoprene seal adhered to face of mullion and sill cap
at all exposed surfaces adjacent to aluminum channel.
Aluminum brake metal channel w/ edges returned (color
to match window framing system).
Edge of sill below.
New or existing window mullion
Match new wall type with
existing wall construction to
remain.
Align face of any new
construction w/ face of
adjacent existing construction
to remain unless otherwise
indicated.
Proposed interior wall
construction. Refer to floor
plans for wall type.
Existing construction
(wall, column wrap, etc.)
to remain (typ.)
Align face of any new
construction w/ face of
adjacent existing
construction to remain
unless otherwise indicated.
Existing construction
(wall, column wrap,
etc.) to remain (typ.)
Existing construction
(wall, column wrap, etc.)
to remain (typ.)
Refer to general demolition notes for additional information.
Indicates existing partitions to be removed.
Dashed lines indicate portion of existing partition to be
removed for future construction. See floor plan for
required usage.
Indicates existing door and frame to be removed (or door &
sidelight if indicated as such). Note: Doors may be re-used.
Coordinate with building owner possible door re-use. Use
only best condition doors for this purpose. Refer to floor
plans for possible new location.
Hatching indicates area not in contract. Refer to floor plans
for additional information.
Indicates existing partitions to remain.
1
13' - 1"
4' - 4" 8' - 7 1/8"
7'- 6 3/4"
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A101
I0825506 5-13-08
Demolition Plan
4100
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
NORTH
Demolition Plan Keynotes
1 Remove existing coffered ceiling detail and raise low portion of ceiling.
Demolition Notes
Refer to demolition plan for additional notes and demolition information.
A. Dashed lines indicate existing items to be removed. Unless noted otherwise, contractor shall be
responsible for the off-site disposal of all demolition items.
Suspended acoustical ceiling
tile - refer to room finish
schedule.
Refer to wall type schedule
for wall construction.
Chicago metallic eliminator
track. Built-in trim edge w/
3/4" protective tape. Flat
tape only. Spackle and sand.
G
Suspended acoustical ceiling
tile - refer to room finish
schedule.
Refer to wall type schedule
for wall construction.
Chicago metallic eliminator
track. Built-in trim edge with
3/4" protective tape. Flat
tape only. Spackle and sand.
GI
Acoustical batt insulation
above ceiling. Extend 2'-0"
min. each side of wall.
Framed to ceiling grid. Insulate Framed to ceiling grid
ceiling 2'-0" (min.) each side of wall
Existing Partition to Remain.
M3
D
Type of Wall Stud
M = Metal Stud Framming
Wall Stud Size / Type
2 = 2 1/2" Stud Size
3 = 3 5/8" Stud Size
6 = 6" Stud Size
S = Sound Insulation
F = Fire Rated
Top of Wall Conditions
(See Standard Top of Wall Condition Details)
G=Grid
GI = Grid / Insulation
+6 = +6 Above Grid
D = Framed to Deck Above
R = Fire Rated
New Partition - Non-Insulated
New Partition Insulated
613A
Conference
605
Office
606
Server
614
Break
616
616B
Office
609
Mail
617
Files
3
Existing ceiling grid to
remain.
Indicates new ceiling grid to be
installed.
Wall mounted light switch.
Coverplate color to match
existing.
Existing building standard 2x4
fluorescent light fixture.
Building standard illuminated
exit light. Solid area denotes
direction of face plate.
Emergency light fixture with
emergency exit lighting pack and
battery back up.
New or relocated building standard
2x4 fluorescent light fixture
Existing building standard 2x2
fluorescent light fixture. See typical
2x4 notes above.
Building standard 2x4 fluorescent
light fixture on night light circuit
(U.O.N.)
New or relocated building standard
2x2 fluorescent light fixture. See
typical 2x4 notes above.
N
Recessed wall wash fixture.
3-way switch. Coverplate color to
match existing.
1. Contractor is responsible for all the design required to obtain approvals and permits and is
required for complete installation of Mechanical, Electrical and Plumbing systems.
2. The design and installation of Mechanical, Electrical and Plumbing systems shall comply
with all requirements and standards of all applicable codes, governmental regulations,
ordinances and state and local requirements.
3. Contractor shall provide construction drawings and calculations stamped by a professional
engineer licensed in the state of Indiana.
4. Contractor shall submit construction drawings and an application for construction design
release to the state of Indiana Plan Review Division of the Indiana Department of Homeland
Security for the purpose of obtaining the required construction design release(s) for the
Mechanical, Electrical and Plumbing systems.
5. Contractor shall coordinate the requirements of the Mechanical, Electrical and Plumbing
systems as required for complete installation of each system.
6. Contractor shall be responsible for providing appropriate heating, cooling and humidity
control as applicable in all spaces, including existing spaces outside the scope of this
project that are re-configured by the new construction.
7. Contractor shall be responsible for re-wiring existing light fixtures, switches, outlets and
miscellaneous devices as required, including existing light fixtures, switches, outlets and
miscellaneous devices outside the scope of this project that are re-configured by the new
construction.
Open Office
612
Office
611
Office
610
Office
609
Office
N
Wall mounted direct connection
location for power and
telephone/data for systems furniture
panels. Coordinate exact location(s)
and requirements with furniture
dealer and installer.
Indicates new item location as
shown. See note below.
Wall mounted duplex outlet at
standard height.
Wall mounted telephone and data
shared outlet.
+42" Indicates outlet at 42" A.F.F.
Flush floor mounted duplex outlet.
Flush floor mounted voice/data
outlet.
1. Contractor is responsible for all the design required to obtain approvals and permits and is
required for complete installation of Mechanical, Electrical and Plumbing systems.
2. The design and installation of Mechanical, Electrical and Plumbing systems shall comply
with all requirements and standards of all applicable codes, governmental regulations,
ordinances and state and local requirements.
3. Contractor shall provide construction drawings and calculations stamped by a professional
engineer licensed in the state of Indiana.
4. Contractor shall submit construction drawings and an application for construction design
release to the state of Indiana Plan Review Division of the Indiana Department of Homeland
Security for the purpose of obtaining the required construction design release(s) for the
Mechanical, Electrical and Plumbing systems.
5. Contractor shall coordinate the requirements of the Mechanical, Electrical and Plumbing
systems as required for complete installation of each system.
6. Contractor shall be responsible for providing appropriate heating, cooling and humidity
control as applicable in all spaces, including existing spaces outside the scope of this
project that are re-configured by the new construction.
7. Contractor shall be responsible for re-wiring existing light fixtures, switches, outlets and
miscellaneous devices as required, including existing light fixtures, switches, outlets and
miscellaneous devices outside the scope of this project that are re-configured by the new
construction.
Open Office
612
Office
611
Office
610
Office
609
Office
608
Office
606
Conference
605
Server
614
Files
615
Break
616 Reception
601
Small Conf.
603
Indicates Wall Base Finish Material.
Indicates Floor Finish Material.
Indicates Wall Finish Material.
Indicates Keynotes.
Indicates Casework / Countertiop Finish Material.
Open Office
612
Office
611
Office
610
Office
609
Office
608
Office
606
Conference
605
Storage
604
Small Conf.
603
Reception
601
Mail
617
Server
614
Files
615
Break
616
Corr.
602
Corr.
607
1
2
P1
CPT1
B1
P1
CPT1
B1
P1
CPT1
B1
P1
CPT1
B1
P1
CPT1
B1
WC1
CPT2
B2
P2
P2
WC1
CPT2
B2
WC1
CPT2
B2
WC1
CPT2
WC1 B2
CPT2
B2
WC1
CPT2
B2
P1
VCT1
B1
P1
VCT1
B1
P1
VCT1
B1
P1
VCT1
B1
G1
CM1
CM1
CM1
CM1
CM1
CM1
3
3
P1
VCT1
B1
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A204
I0825506 5-13-08
Finish Plan and
Schedule
820
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
NORTH
Finish Key and Abbreviations
Finish Legend
Mark Description Manufacturer Pattern / Finish Number / Color Comments
B1 Vinyl Base Johnsonite Color Match
B2 Wood Base
CM1 Crown Mold
CPT1 Carpet Building Standard Carpet
CPT2 Carpet Upgraded Carpet
G1 Granite Match Entry at Suite 650
P1 Paint Sherwin Williams
P2 Paint Shersin Williams
VCT1 Vinyl Composition Tile Armstrong Imperial Texture Standart Excelon
WC1 Wall Covering
WT Window Treatment
Finish Legend Key
XXX-D Indicates finish to be determined
XXX-E Indicates existing finish to remain
Q Quartz
QT Quarry Tile
QTB Quarry Tile Base
S Stone (Granite, Marble, Limestone,
Slate)
SC Sealed Concrete
SCF Specialty Ceiling Finish
SP Specialty Paint
SS Stainless Steel
SSM Solid Surface Material
SV Sheet Vinyl
TR Trim (Includes stair treads, nosings,
transition strips, corner guards, etc.)
TZ Terrazzo
VCT Vinyl Composition Tile
VT Vinyl Tile
WB Wood Base
WC Wall Covering (Vinyl, Textile or
Acoustical)
WCB Wall Covering Border
WD Wood
WF Wood Flooring
Finish
ACT Acoustical Ceiling Tile
AG Architectural Glass (Art Glass)
B Base (Resilient, Rubber or Vinyl)
CKT Cork Tile
CKTB Cork Tile Base
CMT Ceramic Mosiac Tile
CMTB Ceramic Mosiac Tile Base
CPT Carpet
CT Ceramic Tile
CTB Ceramic Tile Base
EP Epoxy Paint
F Fabric / Textile
IRWP Impact Resistant Wall Protection
LF Laminate Flooring
ML Metal Laminate
P Paint
PC Painted Concrete
PL Plastic Laminate
PLB Plastic Laminate Base
PT Porcelain Tile
PTB Porcelain Tile Base
Abbreviations
E.T.R. Existing To Remain
N.I.C. Not In Contract
V.I.F. Verify In Field
General
A All dimensions are taken to the finished face of wall(s) or to the face of the existing finish material, unless
otherwise noted.
B Verify all critial dimensions within and/or related to the exisitng building dimensions and conditions indicated by
visual survey and/or information from existing drawings.
C Field verify all dimensions indicated as either +/- or V.I.F. (Verify in field).
D Refer to Room Finish Schedule and Finish Legend for all required finish information.
E All existing walls, floors and ceilings shall be finished/repaired smooth to be suitable to receive new finishes as
indicated on the Room Finish Schedule and Finish Legend.
F All existing and new surfaces to be prepared for finishes per the manufacturer's recommended instructions.
G Contractor to submit (3) samples of all finish materials to the architect/designer for approval prior to ordering
materials.
H Plans are not to be scaled for finish information or dimensions. Contact the architect/designer for clarification
of finish information or dimensions.
I Walls behind and directly adjacent to all toilet room fixtures (lavatories, toilets and urinals) shall have a
smooth, hard, nonabsorbent surface. Partitions in these areas shall be constructed with cement board or
moisture resistant gypsum board in lieu of gypsum wall board and/or finished with an epoxy paint. Toilet room
accessories (grab bars, toilet paper dispensers, etc.) in these areas shall be installed and sealed to prevent
moisture penetration.
Flooring
A Where dissimilar flooring materials meet they shall do so under centerline of door, unless otherwise indicated.
B Flooring contractor to submit floor seaming diagram to architect/designer for review and approval.
Finish Notes
A204 1/8" = 1'-0"
1 Finish Plan
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
Finish Keynotes
1 Upgraded carpet to end at this point.
2 Wrap wallcovering and wood base in Corridor 607 to inside corner as shown on plan.
3 Stopping point of crown molding.
5-13-08 State Submittal Set
Storage
604
Mail
617
Corr.
607
Corr.
602
N
N
N
N
N
N
N
N
N
N
N
N
N N
N
N
N
N
N
N
N
N
N
N
N
N
N
N
+42"
+42"
N
N
N
N
N
N
+42"
1
2
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A203
I0825506 5-13-08
Electrical Location
Plan
720
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
NORTH
Electrical Legend
Mechanical, Electrical & Plumbing Design
Requirements
Electrical Location Keynotes
1 Existing floor outlets to remain.
2 Install (2) core drills in Open Office Area/ G.C. to coordinate locations with Tenant.
Electrical Notes
A. This drawing is intented to provide information relating to the location of wiring devices and outlets
only. It is the responsibility of the electrical design/build contractor to provide necessary documents
relating to the actual electrical installation to install all wiring devices in accordance with all
applicable state and local codes.
B. All dimensions are from finished wall surface or column centerline to centerline of outlets or
centerline of pairs of outlets.
C. All wall mounted wiring devices and receptacles shown back to back shall be offset a minimum of 8"
and acoustically sealed.
D. Where direct connection to prewired furniture panels occurs, provide power and telecommunication
feeds to indicated panel locations from wall, column or floor source directly adjacent to this location.
E. All existing floor mounted electrical/telecommunication locations which are not reused are to be
removed. Remove all associated cable, wire and conduit back to the source. Properly patch and
repair affected wall, floor and/or ceiling construction.
F. Unless otherwise noted, all device elevations refer to bottom of outlet box.
G. Refer to reflected ceiling plans for locations of light switches.
H. All outlets that are in the vacinity of any wet areas (kitchens, break rooms, restrooms, janitorial
rooms with floor sinks, laundry rooms, stand alone wall mounted sinks, electrical water fountains,
etc.) ground fault interrup (G.F.I.) type. See electrical legend.
I. Furniture will be provided by tenant and is shown for reference only.
A203 1/8" = 1'-0"
1 Electrical Location Plan
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
5-13-08 State Submittal Set
608
Office
606
Conference
605
Storage
604
Small Conf.
603
Reception
601
Break
616
Files
615
Server
614
Mail
617
Corr.
602
Corr.
607
N
N
N
N
N
1
2
3
3
3
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A202
I0825506 5-13-08
Reflected Ceiling
Plan
6100
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
NORTH
Reflected Ceiling Legend
Mechanical, Electrical & Plumbing Design
Requirements
Reflected Ceiling Plan Keynotes
1 Install bulkhead for ceiling transition.
2 Install recessed wall washer to accent signage wall.
3 Location of switches for Open Office 612. G.C. to coordinate circuiting.
Reflected Ceiling Plan Notes
Not all may apply. Refer to reflected ceiling plan for additional notes and ceiling information.
A. Refer to index sheet for typical wall types (walls to deck, rated walls, etc.) and additional wall-to-ceiling
design conditions and considerations.
B. Provide night light circuits as required.
C. Refer to room finish schedule for specific ceiling types and materials.
D. The architectural reflected ceiling plan shall govern the layout of all ceiling elements and/or
penetrations. Coordinate any field verified or as-built conditions that differ from what is shown on
these plans with the architect..
E. Sizes of mechanical equipment (if shown) are for reference only. Coordinate actual sizes with the
mechanical engineer.
F. Sizes and shapes of lighting and other miscellaneous electrical equipment (if shown) are for reference
only. Coordinate actual sizes with the electrical engineer.
G. Install suspended ceiling grid with equal size panels at each side or end of the individual spaces
unless otherwise indicated. No panel shall be less than 1'-0" wide.
H. All ceiling mounted items (sprinkler heads, mounting mechanisms, etc.) shall be centered in the
ceiling panels unless otherwise indicated.
I. Where existing ceiling grid is remodeled to meet new construction, the contractor shall:
A. Replace all damaged or un-repairable portions of the existing grid with new grid to match the
existing building standards.
B. Remove portions of the existing grid or provide new grid as required by new construction. All
new grid must match existing grid to remain or match the existing building standards.
C. Replace all damaged ceiling tiles with new tiles to match the existing to remain or that match the
existing building standards..
J. Contractor to provide an allowance for replacement of all damaged ceiling tiles in areas of project
scope.
A202 1/8" = 1'-0"
1 Reflected Ceiling Plan
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
5-13-08 State Submittal Set
615
Open Office
612
603
Reception
601
Small Conf.
603
Corr.
607
Office
611
Office
610
Office
608
Storage
604
611
610
609
608
615
614
616A
604
605
606
Corr.
613
Corr.
602
617
13' - 1"
20' - 9"
14' - 0" 15' - 2"
4' - 8 1/8"
4'- 6"
7' - 8"
3 2
1
4
5
6
7
8
6
6
6
7
5
5
5
5
9
12' - 5 1/2"
15' - 2 5/8"
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3S
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3
G
M3S
G
14' - 4 7/8"
5' - 1 3/4"
10' - 10 7/8" +/-
5
3' - 0"
5' - 0"
26' - 8 1/8"
38' - 1 5/8"
M3S
G
M3S
G M3S
G
M3S
G
M3S
G
10
9
11
5
A201
6
M3
G
A201
7
13
12
5
601
M3S
G
M3S
G
1
2"
2" 2"
Note:
Refer to door schedule for door opening
sizes unless otherwise indicated.
A B
Building standard
frameless glass entry.
Wall Construction - Refer
to Floor Plan for Wall Type
Door Frame (Typ.)
Note: Unless otherwise noted or dimensioned on
plans, provide 6" of space at hinge side of door
frames.
Wall Construction - Refer
to Floor Plan for Wall Type
Door Frame (Typ.)
6" 6"
OFFICE LOCK
FINISH: BLDG. STD.
3 MUTES
1 PASSAGE LATCH
3 HINGES
HARDWARE SET #1
1 WALL STOP
FINISH: BLDG. STD.
3 MUTES
1 ENTRANCE/
3 HINGES
HARDWARE SET #2
1 DOOR STOP
Cylinder balance of hardware
by glass door supplier
HARDWARE SET #3
3' - 0" 2' - 9" 3' - 0"
3' - 0" 2' - 9" 3' - 0"
3' - 0" 1' - 6" 2' - 6"
4"
Building standard wall cabinets
(Merillat or equal).
Building standard base cabinets
(Merillat or equal).
Plastic laminate countertop and
backsplash.
Verify in Field
2' - 9" 2' - 9" 2' - 9"
2' - 9" 2' - 9" 2' - 9"
3' - 0" 1' - 6" 2' - 6"
4"
Building standard wall
cabinets (Merillat or
equal).
Building standard base
cabinets (Merillat or
equal).
Plastic laminate
countertop and
backsplash.
Refrigerator by Tenant.
Single bowl stainless steel
sink with ADA compliant
handles.
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A201
I0825506 5-13-08
Construction Plan
5100
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
NORTH
1/2" = 1'-0"
Top of Wall Condition Details
Wall Legend
Construction Keynotes
1 Replace existing door with new Herculite frameless glass entry with brushed chrome finish.
2 G.C. to provide and install water line for refrigerator and coffee maker.
3 Replace existing upper and lower cabinets in Break 612 with new cabinets stained to match
Tenant's existing furniture. Install new plastic laminate countertop (color to be determined)
with building standard sink and faucet. Sink base and faucet to be ADA compliant.
4 Install 4'x4' plywood sheet.
5 Align new constuction with existing construction.
6 Center new wall on window mulion. See detail 3/A002.
7 Center new wall on corner of column.
8 Center new wall on center of column.
9 Align new wall with existing column.
10 Location of fire extinguisher. See detail 1/A002 for more information.
11 Align new walls.
12 Additional HVAC for Server Room not to exceed 10,000 BTUs. Tenant to provide wattage
requirement.
13 Infill door opening. Match adjacent wall construction as to acheive a smooth and seamless
transition.
Construction Notes
A. Provide moisture resistant gypsum board in lieu of gypsum wall board in all wet areas.
B. Refer to room finish schedule for wall base type, ceiling type, and ceiling heights unless otherwise
indicated.
C. Refer to top of wall condition legend, this sheet for additional information regarding wall heights and
termination.
D. Provide air-tight acoustical sealant around perimeter of all wall types with acoustical insulation.
E. Provide 3-1/2" acoustical insulation at the ceiling in all walls with acoustical insulation unless
otherwise indicated. Ceiling acoustical insulation shall extend 2'-0" minimum on each side of the wall.
F. All joints and penetrations of fire rated assemblies to be sealed with approved U.L. listed "F" and "T"
systems. Submit product data and installation information prior to installation for architect's approval.
G. All dimensions are taken to finished metal stud to finished face of metal stud unless otherwise noted.
H. Verify all critical dimensions within and/or related to the existing building. Dimensions and conditions
indicated were determined by visual survey and/or information from existing drawings.
I. +/- Dimension is equal to verify in field.
J. All existing walls, floors, and ceilings shall be finished/repaired smooth to be suitable to receive new
finishes as described on room schedule/legend.
K. E.T.R. means existing to remain.
L. N.I.C. means not in contract.
M. All existing and new surfaces to be prepared for finishes per manufacturers recommended
instructions.
N. Plans are not to be scaled for finish or wall information. Contractor to contact Carson Design
Associates for any questions or clarifications on plan dimensions.
O. Walls behind and directly adjacent to all toilet room fixtures (lavatories, toilets and urinals) shall have
a smooth, hard, non-absorbant surface. Partitions in these areas shall be constructed with cement
board or moisture resistant gypsum board in liue of gypsum wall board and/or finished with an epoxy
paint. Toilet room accessories (grab bars, toilet paper dispensers, etc.) in these areas shall be
installed and sealed to prevent moisture penetration.
Wall Type Schedule
Wall Type
Wall Construction Top of Wall Condition
Stud Size Insulation Fire Rating Description Code Description
M3 3 5/8" No -- Metal studs @ 16" O.C. with (1) layer 5/8" gypsum
board each side
G Framed to ceiling grid
M3S 3 5/8" Yes -- Metal studs @ 16" O.C. with (1) layer 5/8" gypsum
board each side
G Framed to ceiling grid
A201 1/8" = 1'-0"
1 Construction Plan
Door Schedule
Door
Number
Door Frame Fire
Type W H T Material Finish Type Material Finish Rating Hardware Remarks
601 B 6' - 0" 7' - 0" Glass -- -- 3
603 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
604 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
605 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
606 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
608 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
609 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
610 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
611 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
613A A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 2
614 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 2
615 A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
616A A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
616B A 3' - 0" 7' - 0" 1 3/4" Solid Core Wood Stain to Match Tenant Sample 1 Timely Bldg. Std. -- 1
617 A 3' - 0" 7' - 0" Gyp. Board Cased Opening
Door and Hardware Notes
1 Door stops to be wall mounted unless otherwise noted in door
schedule remarks. Provide blocking inside wall for stops.
2 All new and existing doors to receive building standard lever handles.
3 All existing doors to be repaired for any damaged, scratched or worn
areas.
4 All office doors to receive (1) coat hook. All coat hooks to be mounted
on center of door at 5'-0" a.f.f.
5 Egress doors shall be readily openalbe from the egress side without
the use of a key, special knowledge or effort. In group A occupancies,
having an occupant load less than 300 and group B,M & S
occupancies, the main exterior door(s) are permitted to be equipped
with key operated locking devices or deadbolt from the egress side
provided that the locking device is readily distinguishable as locked
and a readily visible durable sign is posted on the egress side on or
adjacent to the door stating "This door to remain unlocked when
building is occupied". The sign shall be 1" high letters on a
contrasting background. Refer to Indiana Building Code Section
1003.3.1.8
A201 1/4" = 1'-0"
2 FRAME TYPES
A201 1/4" = 1'-0"
3 DOOR TYPES
A201 1" = 1'-0"
4 Typical Door Jamb Detail
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
HARDWARE SCHEDULE
A201 1/2" = 1'-0"
6 Mail 617
5-13-08 State Submittal Set
A201 1/2" = 1'-0"
7 Break 616
B. Relocated items shall be cleaned and placed in storage, per owner's directions until items are ready
to be reinstalled. If item is damaged during demolition or relocation it shall be repaired or replaced
with new item as approved by owner at no expense to owner.
C. Demolition shall be done without damage to existing construction to remain. Where such damage
occurs patch, repair, or restore walls, floors, ceilings, etc to match existing. Provide shoring, bracing,
or support as required to prevent movement or settlement of existing construction.
D. Contractor shall be responsible for the coordination of demolition items with the other trades prior to
the start of demolition work.
E. Remove all existing construction, items and finishes made obsolete by, or in conflict with new
construction. Coordinate with architectural. Remove wiring back to source at all outlets, etc. made
obsolete by wall removal or any other new construction.
F. Where existing walls, bulkheads, or finishes are removed or partially demolished, each trade shall be
responsible for patching or refinishing of existing construction required by that trades work on this
project. This work must be done in a matter which will accept new finishes.
G. All contractors are responsible for removal and replacement of ceiling grid and/or tiles in any area
where they need access and the existing ceiling is to remain. Unless otherwise noted, contractor
shall replace any ceiling tiles or grid damaged in this process.
H. At the owner's request salvaged items shall be turned over to the owner or stored in an area
designated by the owner.
I. Dimensions shown for existing construction to be demolished are approximate and are intended to
give a general idea of work to be removed or work to be temporarily removed in order to complete
new construction. Coordinate demolition work with design intent of new construction to provide
adequate area for this work.
J. Contractor must field verify all areas and/or work to be demolished prior to beginning work.
Contractor must coordinate with architect any differences between field verified conditions and/or
construction, and what is shown on demolition drawings.
K. Prior to beginning demolition, dust control barriers shall be constructed to prevent the spread of dust
into surrounding areas.
L. Exiting from structure, if required to pass through demolition area(s), shall have approved barriers,
etc., to insure public safety.
M. When applicable, refer to structural, mechanical, electrical, and plumbing demo drawings for
additional demolition requirements and information.
N. Remove and reinstall all equipment or construction on walls receiving new finishes. Coordinate with
architectural finish plan and/or schedule.
O. Refinish entire surfaces as necessary to provide an even finish. Refinish entire assemblies.
Continuous surfaces will be taken to the nearest intersection.
P. Remove all dirt, dust, debris, etc. daily. Do not allow refuse to block corridors, stairs, or any other
traffic area.
Q. It is essential that the client be able to function as normal as possible in areas adjacent to renovation
or new construction.
Demolition Legend
A101 1/8" = 1'-0"
1 Demolition Plan
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
5-5-13-13-08 08 CD Set State Submittal Set
Align face of any new
construction w/ face of adjacent
existing construction to remain
unless otherwise indicated.
Proposed interior wall
construction. Refer to floor
plans for wall type.
Wood shims as required at sill and jambs.
Note: Coordinate minimum required wall thickness with fire extinguisher
cabinet manufacturer prior to purchase. Size and type of extinguisher must
meet all local and state code requirements.
Recessed fire extinguisher cabinet. Refer to floor or
code plans for locations. Anchor cabinet to double
studs at jambs.
Metal stud runner between vertical studs
Refer to floor plan for wall types.
5'-4" From finshed floor to top of rough opening
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A002
I0825506 5-13-08
General
Information and
Standard Details
3
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
Symbol Legend
A002 1 : 1
3 Typical Wall Alignment at Mullion
A002 1 : 1
2 Wall Alignment Detail
A002 1" = 1'-0"
1 Recessed Fire Extinguisher Cabinet Detail
VERT Vertical
VT Vinyl Tile
W. Wide/Width
W/ With
W/O Without
WB Wood Base
WC Wallcovering
WD Wood
WH Water Heater
WP Working Point
UR urinal
V.I.F. Verify in Field
VCT Vinyl Compostion Tile
TYP Typical
UON Unless Otherwise Notes
T.O. Top Of
TB Tack Board
TEL Telephone
TMPR Tempered
TV Television
SA Supply Air
SCHED Schedule
SEC Section
SF Square Foot
SIM Similar
SPECS Specifications
SS Stainless Steel
STD Standard
STL Steel
SUSP Suspended
REF Reference
REFR Refrigerator
REQD Required
RO Rough Opening
QT Quarry Tile
RRiser
RA Return Air
PS Projection Screen
OPP Opposite
P Paint
PL LAM Plastic Laminate
PLWD Plywood
N.I.C. Not in Contract
O TO O Out to Out
O.H. Opposite Hand
OD Outside Diameter
OPNG Opening
MIN Minimum
LLV Long Leg Vertical
M.O. Masonry Opening
MAS Masonry
MAX Maximum
MB Marker Board
MECH Mechanical
MEZZ Mezzanine
MFG Manufacturer
KIT Kitchen
LAM Laminate
LAV Lavatory
LLH Long Leg Horizontal
JT Joint
HW Hot Water
JST Joist
GWB Gypsum Wall Board
H. High/Height
HDWR Hardware
HM Hollow Metal
HORIZ Horizontal
HVAC Heating, Ventilation and Air Conditioning
FT Feet
GA Gauge
GB Grab Bar
EXT Exterior
FD Floor drain
FE Fire Extinguisher
FEC Fire Extinguisher Cabinet
FIN Finish
FLR Floor
DWG Drawing
E.T.R. Existing to remain
EA Each
EIFS Exterior Insulation Finish System
EJ Expansion Joint
EL Elevation
EXIS Existing
EXP Expansion
CW Cold Water
DET Detail
DF Drinking Fountain
DIM Dimension
DP Deep/Depth
DWC Drinking Water Cooler
BOT Bottom
CAB Cabinet
CJ Control Joint
CL Center Line
CMU Concrete Masonry Unit
COL Column
CONST Construction
CPT Carpet
CT Ceramic Tile
B Resilient Base
B.O. Bottom of
BLKG Blocking
A.F.F. Above Finished Floor
ACT Acoustical Ceiling Tile
APP Approximate
AWT Acoustical Wall Treatment
Abbreviations
BC. Do not scale drawings. Refer to dimensions illustrated on drawings notify the
architect/designer of discrepancies of for clarification.
BD. Interior finishes shall have a flame spread classification of III (76-200 tunnel test) and a smoke
density of no greater than 450.
BE. All stud walls shall be secured to the concrete floor and ceiling or floor/roof construction above.
Provide expansion/control joints in the gypsum wall board walls over 30'-0" in length per the
manufacturer's recommendations. Coordinate locations of expansion/control joints with the
architect prior to installation for compliance with design intent.
BF. All stud or masonry walls extending from floor to roof/floor structure above must provide for a
minimum of 2" vertical roof/floor deflection.
BG. All joints and penetrations of fire rated assemblies to be sealed with approved U.L. listed "F"
and "T" systems. Submit product data and installation information prior to installation for
architects approval..
BH. Furnish and install plumbing fixtures as shown. The plumbing fixtures and toilet seats shall be
white unless otherwise indicated. All exposed piping and supply fittings shall be chrome plated
unless otherwise indicated. All wall penetrations shall be fitted with chromium plated
escutcheons.
BJ. Fixtures indicate as handicap accessible shall comply with A.D.A. requirements.
BL. Hot water and drain pipes under lavatories and handicap accessible sinks shall be installed or
otherwise configured to protect against contact.
BM. Faucets shall comply with A.D.A. requirements. Lever-operated, push-type and electronically
controlled mechanisms are acceptable unless otherwise indicated.
BN. Where dissimilar floor materials meet, they shall do so under the centerline of a door unless
otherwise indicated.
BP. Hinge side of finish door jamb in metal stud walls shall typically be located 6" from adjacent wall
unless otherwise indicated.
BQ. Materials exposed within plenum spaces designed to allow air movement and function as part
of the air distribution system are required to be noncombustable or shall have a flame spread
index less than 25 and a smoke developed index less than 50 when tested in accordance with
ASTM E 84. All combustible materials located within these plenum spaces shall be enclosed in
noncombustible material (5/8" gypsum wall board) unless otherwise indicated. Refer to
mechanical drawings for air distribution system design and details..
AA. The drawings indicate the general scope of the project in terms of architectural design concept,
dimensions of the building, major architectural elements and the type of structural system. As
scope documents, the drawings do not indicate or describe all the work required for full
performance and completion of the requirements of the contract documents. On the basis of
the general scope indicated or described, the trade contractors shall furnish all items required
for the proper execution and completion of the work.
AB. These contract documents do not attempt to instruct the contractor in the specific details of his
trade.
AC. All work shall be in accordance with the quality standards of the trade and shall be installed in
compliance, as a minimum standard, to all applicable local, state and federal codes and
manufacturer's recommendations..
AD. All work shall be warranted satisfactory, in materials and workmanship, for a minimum period of
one (1) year or for the customary period of warranty or as stipulated for the trade, craft or
product whichever is longer..
AE. General contractor shall be responsible for field verification of all dimensions and job conditions
prior to starting construction unless otherwise indicated. Notify the architect/designer of any
discrepancies prior to proceeding with construction.
AF. The contractor shall be responsible for obtaining a clarification from the architect prior to bid
submittal and/or start of construction with regard to any question regarding the contract
documents, existing conditions aor design intent..
AG. It is the owner's and/or tenant's responsibility to review and check the construction documents
prior to construction and verify any and all locations, sizes quantity and specific materials used
in conjunction with the owner's/tenant's special equipment layout, use or function.
AH. The coordination of all materials, labor and workmanship is the sole responsibility of the
general contractor.
AJ. The contractor shall be responsible for advising the owner and architect of all long lead items
that may adversely affect the project schedule and shall, upon request from the owner or
architect, submit order confirmations and delivery dates for such items.
AK. The contractor shall be responsible for verifying all existing work to remain and determining the
suitability for repair and/or reconditioning to match and blend with new materials and
components. Contractor shall obtain the owner's/tenant's approval of the scope and limit of
existing work to remain prior to starting construction. No change orders shall be accepted for
completed work that does not conform to the standard established prior to the start of
construction..
AL. The contractor shall coordinate with the building owner and/or manager access to the space
and all ongoing construction work. Disruptive or potentially hazardous construction activities
shall be coordinated to occur after normal business hours to minimize the disturbance to
building occupants..
AM. The contractor shall coordinate with the building owner and/or manager for delivery to the
space of all building materials, and shall arrange for the usage of the appropriately designated
elevator. The contractor shall coordinate such deliveries in a manner which poses no hazard
to any personnel within or around the building and construction site.
AN. Commencing work by a contractor or subcontractor constitutes acceptance of the conditions
and surface concerned. If such conditions or surfaces are unacceptable, the general
contractor shall be notified immediately and work should cease until the unacceptable
conditions can be remedied.
AP. The make and model numbers specified are preferred or minimum standards. Other
equipment may be considered, if proven equal.
AQ. All contractor or supplier requests for substitutions of specified items shall be submitted in
writing accompanied by the alternative product information to the architect/designer for
approval. Substitutions shall be submitted no later than one (1) working day prior to the bid
opening date. Substitutions shall not sacrifice quality, appearance or function. It is incumbent
on the contractor or supplier to provide adequate information to determine if the substitute is of
equal quality to the product specified.
AR. The contractor is responsible for contacting local building officials and inspectors for permits
and inspections. Advise the architect immediately of an discrepancies.
AS. The contractor shall maintain all printed instructions, manuals and warranties that are provided
with equipment and materials used or installed. Instructions, manuals and warranties to be
delivered to the owner at the time of substantial completion.
AT. The contractor or subcontractor shall instruct the owner or owner's representative in the proper
use and maintenance of the equipment furnished or installed by their trade.
AU. The general contractor shall provide a thorough construction clean-up prior to owner/tenant
taking occupancy of any space. Clean-up shall include, but not be limited to cleaning all
surfaces and vacuuming and cleaning all carpeting and window treatments.
AV. All fixtures, equipment and materials shall be installed per the manufacturer's specifications,
recommendations and suggested instructions.
AW. Shop drawings, product data and/or samples shall be provided on items as noted to ensure
that the specified products are furnished and installed in accordance with the design intent.
The manufacture or construction of any pieces of equipment, device or other item for which
shop drawings, product data and/or samples are required to be furnished, shall not commence
prior to complete processing of the appropriate approval of the submittal.
AX. Reviewed shop drawings and schedules prepared by others shall not be construed to be part
of the contract documents. The architect assumes no responsibility for drawings, schedules
and/or specifications for work on the project prepared or accomplished by others.
AY. Items noted "N.I.C" (Not in Contract), "By owner/Tenant" or "Existing" shall not be included in
the contract. Provisions shall be made by the respective trades to allow for the installation or
preservation of the items noted. All finishes of floors, bases, wainscots, walls and ceiilngs
behind, under and/or over these items shall be included in the general contract unless
otherwise indicated. .
AZ. Provide metal or fire retardant treated wood blocking in new and existing walls for all wall
supported items. At all existing walls, patch and repair wall finish to match adjacent wall
surface as required following the installation of blocking..
BA. Transport trash, rubbish and debris from the site and legally dispose of same. The manner of
removal must be confirmed with the owner and as allowed by city and state regulations.
BB. Dimensions are taken from face of block walls, column lines and/or finish face of walls unless
otherwise indicated.
General Notes
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
5-13-08 State Submittal Set
1993. The ratings below are for VOC content only since this section is about indoor air quality; the standards also include ratings for scrubbability (abrasion resistance), opacity,
and washability (stain
removal). A full copy of the requirements is available on the Green Seal website at http://www.greenseal.org/standards/paints.htm. For the anti-corrosive paints the reference standard
is Green Seal
Standard GC-03, dated January 7, 1997. A full copy of the requirements is available on the Green Seal website at http://www.greenseal.org/standards/anti-corrosivepaints.htm.
VOC Limit, Less Water and Tinting Color in Grams per Liter for Indoor Applications:
Paint Top Coating Type
Non-flat Paint 200
Flat Paint 100
Chemical Component Restrictions: The following chemical compounds cannot be used as ingredients in the manufacture of the product.
Methylene Chloride
1,1,1-trichlorethane
Benzene
Toluene
Ethylbenzene
Vinyl Chloride
Naphthalene
1,2-dichlorobenzene
Di (2-ethylhexyl) Phthalate
Butyl Benzyl Phthalate
Di-n-butyl Phthalate
Di-n-octyl Phthalate
Diethyl Phthalate
Dimehtyl Phthalate
Isophorone
Antimony
Cadmium
Hexavalent Chromium
Lead
Mercury
Formaldehyde
Methyl Ethyl Ketone
Methyl Isobutyl Ketone
Acrolein
Acrylonitrile
Toxics in Packaging: The manufacturer shall demonstrate that paint cans and their components are not fabricated with lead.
CARPET SYSTEMS, CARPET
Section 3: EQ Credit 3.1/3.2 LEED EB
Carpet systems including the carpeting, seam sealers and adhesives must meet the criteria of the Carpet and Rug Institute’s Green Label Plus system. See Section 1, Adhesives and Sealants,
above for the requirements of the carpet sealers and adhesives.
Green Label Plus is an independent testing program that identifies carpets with very low emissions of volatile organic compounds (VOCs). It is an enhancement to the CRI Green Label Testing
program which has been consistently upgraded since it was developed in 1992. Green Label Plus meets California’s CHPS (Collaborative for High Performance Schools) criteria. To receive
Green
Label Plus certification, carpets must undergo a 14-day testing process that measures emissions for a range of chemicals and is administered by an independent laboratory. The test methodology
was developed in cooperation with the U.S. Environmental Protection Agency (EPA). Every carpet receiving Green Label Plus certification has been tested for emission levels for 13 chemicals,
utilizing a 14-day test. The 13 chemicals measured are: Acetaldehyde, Benzene, Caprolactam, 2-Ethylhexanoic Acid, Formaldehyde, 1-Methyl-2-Pyrrolidinone, Naphthalene, Nonanal, Octanal,
4-
Phenylcyclohexene, Styrene, Toluene, and Vinyl Acetate. Subsequent annual tests are based on 24-hour testing that targets 13 chemicals. Plus, quarterly testing will measure for the total
level of
volatile organic compounds (TVOC).
Commercial carpet that meets the criteria for Green Label Plus certification is listed on the CRI websites available at www.carpet-rug.org. If the carpet being considered is not Green
Label Plus
certified, it can be submitted to the manufacturer for testing, in order to determine if it qualifies for Green Label Plus certification.
CARPET SYSTEMS, CUSHION
Section 4: EQ Credit 3.1/3.2 LEED EB
Carpet cushion must meet the criteria of the Carpet and Rug Institute’s Green Label system.
Criteria are based on a maximum emission factor as follows:
Total Volatile Organic Compounds 1.00 mg/m2 . hr.
BHT (butylated hydroxytoluene) 0.30 mg/m2 . hr.
Formaldehyde 0.05 mg/m2 . hr.
4-PC (4 phenylcyclohexene) 0.05 mg/m2 . hr.
CRI has established a program that tests for volatile organic compounds (VOCs) in cushion used under carpet. This program will help the carpet manufacturer, installer and end user to
identify and
utilize low-emission cushion. Cushion products that meet the emissions criteria can display the program’s green and white label. Products are re-tested regularly for continued compliance.
Consumers
seeking a low-emitting cushion can confidently select those bearing the label. Cushion products are characterized as: prime polyurethane, bonded polyurethane, mechanically frothed polyurethane,
rubber – hair, rubber – jute, synthetic fiber, resinated or coated synthetic fiber, rubber and rubberized polyurethane. Cushions are tested for total volatile organic compounds, BHT
(butylated
hydroxytoluene), formaldehyde and 4-phenylcyclohexine (4-PC).
Commercial carpet cushion that meets the criteria for Green Label certification is listed on the CRI websites available at www.carpet-rug.org. If the carpet cushion being considered
is not Green
Label certified, it can be submitted to the manufacturer for testing, in order to determine if it qualifies for Green Label certification.
COMPOSITE PANELS & AGRIFIBER PRODUCTS
Section 4: EQ Credit 3.1/3.2 LEED EB
Formaldehyde is a natural component of wood products, but some wood glues and wood products made with these glues contain significantly higher amounts than does wood alone. Regarding
composite panels and agrifiber products used on site it is required that no additional urea-formaldehyde be added to the products during the manufacturing process.
Pressed wood products often contain urea-formaldehyde glues. Products that may add formaldehyde to the air include particleboard used as flooring underlayment, shelving, furniture and
cabinets;
MDF in cabinets and furniture; hardwood plywood wall panels, and urea-formaldehyde foam used as insulation or fiberglass insulation. The glue or adhesive in pressed wood products such
as
particleboard, hardwood plywood, and medium density fiberboard (MDF) are common sources.
Avoid the use of foamed-in-place insulation containing formaldehyde, especially urea-formaldehyde foam insulation and use alternative products such as wood panel products not made with
urea-
formaldehyde glues.
Composite wood and agrifiber products must contain no added urea-formaldehyde resins.
APPLICABLE
BUILDING CODES
Indiana Administrative Rules
2003 Indiana Building Code (2000 International Building Code with Indiana Ammendments
2003 Indiana Fire Code (2000 International Fire Code with Ammendments)
Americans with Disabilities Act Accessible Guildelines (ADAAG) for Buildings and Facilities
American National Standards Institute Accessible and Usable Buildings and Facilities Standard
(CABO/ANSI A117.1-1992)
BUILDING AREA Total Building Area (Existing) = 180,000 square feet
Project Scope
Tenant Office Area = 4,093 square feet
OCCUPANCY
CLASSIFICATION
Business - Group B
CONSTRUCTION
TYPE
Type II-B (non-combustible)
ALLOWABLE
BUILDING AREA
This project does not involve a change of Use or Occuapncy Classification of the existing
building. This project does not include the construction of existing building area.
AUTOMATIC
SPRINKLER SYSTEM
Fully Sprinkled
OCCUPANT LOAD Occupant Load Factor (Occupants per Floor Area)
Office 100 s.f. / occupant
Storage 300 s.f. / occupant
Occupant Load(s)
Office = 41
Storage = 0
Total Occupant Load = 41
ALLOWABLE
TRAVEL DISTANCE
200'-0" (w/o sprinkler system) or 300'-0" (w/ sprinkler system)
Dead End passages limited to 20'-0" in length (50'-0" w/ sprinkler system)
Common Path of Travel limited to 75'-0" in length (100'-0" w/ sprinkler system)
EGRESS WIDTH
REQUIREMENTS
Minimum Require Width Factors
Stairs: .2" / occupant (w/ sprinkler system)
.3" / occupant (w/o sprinkler system)
Other Components (doors): .15" / occupant (w/ sprinkler system)
.2" / occupant (w/o sprinkler system)
Egress Width Provided (2) 3'-0" Doors = 6'-0" Total Egress Width
CARSON
DESIGN
ASSOCIATES
THIS DRAWING AND THE IDEAS, CONCEPTS AND DESIGNS
CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL
PROPERTY OF CARSON DESIGN ASSOCIATES, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR IN PART,
WITHOUT THE WRITTEN CONSENT OF CARSON DESIGN
ASSOCIATES.
COPYRIGHT 2006 CARSON DESIGN ASSOCIATES
SHEET NUMBER
JOB NO. DATE:
DRAWING TITLE:
STAMP:
OF
SQUARE FOOTAGE:
TEL 317.843.5979
FAX 317.843.5975
2325 POINTE PARKWAY
SUITE 200
CARMEL, INDIANA 46032
TEL 512.977.0520
FAX 512.977.0384
11401 Century Oaks Terrace
SUITE 200
AUSTIN, TEXAS 78758
www.carsondesign.com
ISSUE:
11611 N. Meridian St.
A001
I0825506 5-13-08
Code Information
2100
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
Life Safety Plan LEED - EB Material Requirements
NORTH
Code Summary
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N
5-13-08 State Submittal Set
I0825506
5-13-08
1100
Performance Insurance
Performance Insurance
Meridian Mark I- 6th Floor
Construction Documents
Meridian Mark I- 6th Floor
Construction Documents
Location Map
Drawing Index
Sheet
Number Sheet Name
G000 Cover Sheet
A001 Code Information
A002 General Information and Standard Details
A101 Demolition Plan
A201 Construction Plan
A202 Reflected Ceiling Plan
A203 Electrical Location Plan
A204 Finish Plan and Schedule
NORTH
Project Location
Mechanical, Electrical & Plumbing Design
Requirements
D
C
A
R
I
N
A
T
R
C
H
I
T
E
C
19400026
No.
I
A
N
D
I
A
N
STATE OF
R
D
E
G
I
S
T
E
R
E
H
I
N
A
L
E
D
V
E
N