HomeMy WebLinkAboutM3.0MAKE UP AIR UNIT (MUA) SCHEDULE TAG AREA COOLING HEATING - NATURAL GAS SUPPLY FAN COND COMPRESSOR(S) FILTER ELECTRICAL WEIGHT MANUFACTURER MODEL NOTES SERVED NOM. MBH EAT LAT MBH MBH EAT LAT STAGES CFM TYPE DRIVE E.S.P. MOTOR TEMP. TYPE REFRIG. QUANT. TYPE THICKNESS EFF. VOLTS/PH/HZ MCA OR MOCP (BASIS OF DESIGN) TONS TOTAL SENSIBLE DB/WB DB/WB INPUT OUTPUT DB DB TYPE (IN. WC) (H.P.) (IN.) AMPS MUA-01 PROD. KITCHEN 142 20.00 245.1 145.5 90/74 58.1/55.7 651.0 651.0 -5.0 137.9 MOD. 4,200 FC BELT 0.75 5.00 95 SCROLL R-22 2 WASHABLE 2 NA 208/3/60 98.0 125 3,300 TRANE RRU241C3 1, 2, 3, 4, 5, 6, 7 MUA-02 PREP. KITCHEN 143 12.50 152.0 91.3 90/74 58.3/56 407.0 407.0 -5.0 136.6 MOD. 2,650 FC BELT 0.75 3.00 95 SCROLL R-22 2 WASHABLE 2 NA 208/3/60 59.0 70 2,750 TRANE RRU151C3 1, 2, 3, 4, 5, 6, 7 NOTES: 1. FURNISH AND INSTALL 14" ROOF CURB. COORDINATE ROOF CURB INSTALLATION WITH ROOF CONSTRUCTION. 2. FACTORY MOUNTED DISCONNECT SWITCHES AND UNPOWERED GFI RECEPTACLES, AND SMOKE DETECTORS ARE FURNISHED BY THE RTU EQUIPMENT SUPPLIER. RTU EQUIPMENT SUPPLIER RESPONSIBLE FOR COORDINATING DISCONNECT AND GFI RECEPTACLE TYPES WITH ELECTRICAL POWER CHARACTERISTICS AVAILABLE AT THE PROJECT SITE. RTU EQUIPMENT SUPPLIER RESPONSIBLE FOR COORDINATING SMOKE DETECTOR TYPES AND INTERFACES WITH THE FIRE ALARM SYSTEM CHARACTERISTICS AVAILABLE AT THE PROJECT SITE. 3. INSTALL SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR DUCTS FOR ALL RTUs. SMOKE DETECTORS FURNISHED BY THE RTU EQUIPMENT SUPPLIER, , INSTALLED BY THE MECHANICAL CONTRACTOR, AND WIRED BY THE ELECTRICAL CONTRACTOR. 4. PROVIDE MAKE UP AIR UNITS WITH STAINLESS STEEL BURNERS, ELECTRONIC MODULATION, REFRIGERANT CAPACITY CONTROL, AND HOT GAS REHEAT. 5. PROVIDE MAKE UP AIR UNITS WITH 2 POSITION OUTSIDE AIR DAMPERS (OPEN-CLOSE WITH AIR FLOW PROVING AND END SWITCH) AND WEATHER HOODS. 6. PROVIDE MAKE UP AIR UNITS WITH THE FOLLOWING FEATURES: REMOTE DISCHARGE AIR TEMPERATURE ADJUSTMENT WITH RESET BASED ON AMBIENT AND OUTSIDE AIR TEMPERATURE, SPACE TEMPERATURE AND HUMIDITY SENSORS, REMOTE OPERATOR DISPLAY. 7. INTERLOCK THE (4) KITCHEN HOOD EXHAUST WITH THE (2) MAKE-UP AIR UNITS AND HOOD FIRE PROTECTION CONTROLS. ELECTRIC DUCT HEATING COIL (EDHC) SCHEDULE TAG LOCATION HEATING DATA AIR FLOW DUCT ELECTRICAL MANUFACTURER MODEL NOTES KW BTUH NO. OF CFM EAT LAT PD WIDTH HEIGHT VOLTS/PH/HZ AMPS (BASIS OF DESIGN) STEPS (°F) (°F) (IN. WC) EDHC-01 BREWERY 157 3.50 11,946 2 400 58.0 85.5 0.018 10 10 208/1/60 17.0 INDEECO QUA 1, 2 NOTES: 1. ALL ELECTRIC DUCT HEATING COILS SHALL BE COMPLETE WITH FACTORY MOUNTED DISCONNECTS, AIRFLOW SWITCHES, AUTOMATIC RESET THERMAL CUTOUTS FOR PRIMARY OVERTEMPERATURE PROTECTION, MANUAL RESET THERMAL CUTOUTS FOR SECONDARY PROTECTION, AND 24 VOLT CONTROL TRANSFORMER 2. ELECTRIC DUCT HEATING COIL STEPS WILL BE CONTROLLED BY A WALL MOUNTED, 2-STAGE THERMOSTAT (INDEECO 1007030). EXHAUST FAN SCHEDULE TAG AREA SERVED LOCATION CFM E.S.P. FAN DRIVE FAN WEIGHT MANUFACTURER MODEL ELECTRICAL REMARKS (IN. WC) RPM TYPE TYPE (LBS.) (BASIS OF DESIGN) HP VOLTS/PH/HZ EF-01 TOILET 147 ROOF 125 0.30 989 BELT BI 75 GREENHECK GB-071-6 1/6 120/1/60 1, 2, 5, 7, 8, 10 EF-02 #30 EXHAUST HOOD, PREP KITCH. 143 ROOF 1640 0.60 1224 BELT BI 125 GREENHECK CUBE-141-5 1/2 208/3/60 4, 6, 10, 11 EF-03 #49 LEFT SECT. EXH. HOOD, PROD. KITCH. 142 ROOF 1895 0.75 1392 BELT BI 125 GREENHECK CUBE-141-7 3/4 208/3/60 4, 6, 10, 11 EF-04 #49 CENTER SECT. EXH. HOOD, PROD. KITCH. 142 ROOF 1895 0.75 1392 BELT BI 125 GREENHECK CUBE-141-7 3/4 208/3/60 4, 6, 10, 11 EF-05 #49 RIGHT SECT. EXH. HOOD, PROD. KITCH. 142 ROOF 1595 0.65 1473 BELT BI 100 GREENHECK CUBE-131-5 1/2 208/3/60 4, 6, 10, 11 EF-06 #62 DISHWASHER, PREP KITCH. 143 ROOF 1000 0.50 1500 BELT BI 80 GREENHECK CUBE-101-4 1/4 120/1/60 1, 3, 5, 7, 8, 10, 11 EF-07 MEN'S & WOMEN'S RR 154/155 ROOF 800 0.50 1313 BELT BI 80 GREENHECK GB-101-4 1/4 120/1/60 1, 2, 5, 7, 9, 10 EF-08 BREWERY 157 ROOF 450 0.35 1007 BELT BI 80 GREENHECK GB-091-4 1/4 120/1/60 1, 2, 5, 7, 9, 10 NOTES: 1. FURNISH AND INSTALL BACKDRAFT DAMPER FOR EF-01, EF-06, EF-07, AND EF-08. 2. FURNISH AND INSTALL 14" ROOF CURBS, WITH 1" INSULATING LINING, FOR EF-01, EF-07, AND EF-08. 3. FURNISH AND INSTALL 14" ROOF CURBS, WITH METAL LINING OVER 1" INSULATION, FOR EF-06. 4. FURNISH AND INSTALL ROOF CURBS, WITH METAL LINING OVER 1" INSULATION, FOR EF-02, EF-03, EF-04, AND EF-05. COORDINATE ROOF CURB HEIGHT SO THAT EXHAUST FAN DISCHARGE IS AT LEAST 40" ABOVE THE ROOF. 5. PROVIDE FACTORY MOUNTED AND WIRED NEMA 3R DISCONNECT SWITCHES FOR ALL EXHAUST FANS. 6. PROVIDE EXHAUST FANS EF-02, EF-03, EF-04, AND EF-05 WITH CURB SEALS, CLEANOUT PORT IN WINDBAND, HINGED CURB CAP WITH CABLES AND HASPS, AND GREASE TRAPS WITH ABSORBENT AND DRAIN CONNECTION. 7. PROVIDE EXHAUST FANS EF-01, EF-06, EF-07, AND EF-08 WITH BIRDSCREENS. 8. EXHAUST FAN EF-06 IS CONTROLLED BY A WALL SWITCH, SEE ELECTRICAL DRAWINGS. 9. EXHAUST FANS EF-01, EF-07, AND EF-08 ARE CONTROLLED BY THE LIGHTING CONTROL PACKAGE, SEE ELECTRICAL DRAWINGS. 10. COORDINATE ALL ROOF CURB INSTALLATIONS WITH ROOF CONSTRUCTION AT CURB LOCATION. 11. SEE FOOD SERVICE DRAWINGS AND MUA SCHEDULE FOR FURTHER INFORMATION. DIFFUSERS, REGISTERS, AND GRILLES TAG SERVICE TYPE DAMPER AT BLADE ANGLE CONSTRUCTION FINISH MANUFACTURER MODEL NOTES AIR TERMINAL OR CORE MATERIAL (BASIS OF DESIGN) D1 SUPPLY 24"x24" SQ. DIFFUSER SEE NOTES N.A. STEEL #26 WHITE TITUS OMNI 1, 2, 3, 4, 7 D2 SUPPLY 12"x12" SQ. DIFFUSER SEE NOTES N.A. STEEL #26 WHITE TITUS OMNI 1, 2, 3, 4, 7 D3 RETURN/TRANSFER 24"x24" SQ. DIFFUSER SEE NOTES N.A. STEEL #26 WHITE TITUS OMNI 1, 2, 3, 4, 7 D4 RETURN 12"x12" SQ. DIFFUSER SEE NOTES N.A. STEEL #26 WHITE TITUS OMNI 1, 2, 3, 4, 7 D5 SUPPLY ROUND DIFFUSER SEE NOTES N.A. STEEL #26 WHITE TITUS TMR 1, 2, 3, 4, 5, 7 L1 SUPPLY PLENUM SLOT DIFFUSER INTEGRAL N.A. STEEL #26 WHITE TITUS TBDI 1, 2, 3, 4, 6, 7 L2 RETURN PLENUM SLOT NONE N.A. STEEL #26 WHITE TITUS TBR 3, 4, 7 R1 SUPPLY REGISTER OPPOSED BLADE ADJUSTABLE ALUMINUM #26 WHITE TITUS 300FL 1, 2, 3, 4, 7 R2 RETURN/EXHAUST REGISTER OPPOSED BLADE 35° ALUMINUM #26 WHITE TITUS 350FL 1, 2, 3, 4, 7 R3 RETURN/EXHAUST REGISTER OPPOSED BLADE 0° ALUMINUM #26 WHITE TITUS 350ZFL 1, 2, 3, 4, 7 R4 RETURN/EXHAUST REGISTER OPPOSED BLADE 1/2" x 1/2" x 1/2" ALUMINUM #26 WHITE TITUS 50F 1, 2, 3, 4, 7 G1 RET./EXH./TRANS GRILLE NONE 1/2" x 1/2" x 1/2" ALUMINUM #26 WHITE TITUS 50F 1, 2, 3, 4, 7 NOTES: 1. FURNISH AND INSTALL VOLUME DAMPER FOR AIR FLOW BALANCING PURPOSES IN EACH DUCT TAKE-OFF TO A DIFFUSER, REGISTER OR GRILLE. 2. PROVIDE OPPOSED BLADE DAMPER OR REMOTELY OPERATED VOLUME DAMPER PER THE SPECIFICATIONS, FOR DIFFUSERS LOCATED IN CEILINGS THAT WILL NOT ALLOW ACCESS TO THE VOLUME DAMPER IN THE DUCT TAKE-OFF (SEE NOTE 1). 3. COORDINATE BORDER TYPES, PLASTER FRAMES, & MOUNTING METHODS WITH THE CEILING TYPE/WALL CONSTRUCTION AT EACH DIFFUSER, REGISTER, & GRILLE LOCATION. 4. FURNISH AND INSTALL DIFFUSERS, REGISTERS, AND GRILLES MANUFACTURED BY ONE OF THE FOLLOWING MANUFACTURERS: TITUS, PRICE, CARNES, KRUEGAR, METALAIRE, OR NAILOR. 5. ADJUSTABLE CONES, INSTALLED IN THE DOWN POSITION. 6. L-1: 1-1/2" SLOTS. AT EXTERIOR WALLS, ADJUST INTERIOR SLOT(S) FOR HORIZONTAL THROW TOWARDS INTERIOR OF ROOM, AND EXTERIOR SLOT(S) FOR APPROXIMATELY 45° THROW DOWN AGAINST EXTERIOR WALL. FOR DIFFUSERS AT THE BUILDING INTERIOR, ADJUST ALL SLOTS FOR HORIZONTAL THROW. 7. FINAL DIFFUSER COLORS SHALL BE AS INDICATED ON ARCHITECTURAL DRAWINGS AND SPECIFICATIONS, FIELD PAINT AS REQUIRED. ROOF TOP HVAC UNIT SCHEDULE TAG AREA COOLING HEATING - NATURAL GAS SUPPLY FAN COND REFRIGERANT COMPRESSOR(S) FILTER ELECTRICAL WEIGHT MANUFACTURER MODEL REMARKS SERVED NOM. MBH - NET EAT LAT ROWS (S)EER MBH MBH EAT LAT STAGES AGA CFM MIN OA TYPE E.S.P. MOTOR TEMP. TYPE CAPACITY TYPE QUANT. TYPE THICKNESS EFF. VOLTS/PH/HZ MCA MOCP (BASIS OF DESIGN) TONS TOTAL SENSIBLE DB/WB DB/WB INPUT OUTPUT DB DB EFF (%) CFM (IN. WC) (H.P.) (LBS.) (IN.) RTU-01 BAR 107 7.50 86.3 62.6 80.6/66.8 56.9/55.7 3 11.5 150 122 49.3 90.9 2 81% 2,720 750 FC 1.00 2.00 95 R-22 12.60 SCROLL 2 DISPOSABLE 2 MERV 7 208/3/60 38.1 50 1,500 TRANE YHC092A3 1, 2, 3, 4, 5, 6 RTU-02 DINING 109 10.00 105.4 78.1 81.1/67.2 57.5/56.6 5 11.2 200 162 46.4 89.5 2 81% 3,500 1,100 FC 1.00 3.00 95 R-22 18.30 SCROLL 2 DISPOSABLE 2 MERV 7 208/3/60 48.6 60 1,600 TRANE YHC120A3 1, 2, 3, 4, 5, 6 RTU-03 DINING 109 7.50 86.1 59.3 81.2/67.3 55.9/54.9 3 11.5 150 122 45.6 92.7 2 81% 2,400 780 FC 1.00 2.00 95 R-22 12.60 SCROLL 2 DISPOSABLE 2 MERV 7 208/3/60 38.1 50 1,500 TRANE YHC092A3 1, 2, 3, 4, 5, 6 RTU-04 OFF. 119, BREWERY 128 7.50 82.6 57.6 79.6/65.9 54.6/53.5 3 11.5 120 97 55.2 92.9 1 81% 2,400 475 FC 1.25 2.00 95 R-22 12.60 SCROLL 2 DISPOSABLE 2 MERV 7 208/3/60 38.1 50 1,500 TRANE YHC092A3 1, 2, 3, 4, 5, 6 NOTES: 1. FURNISH AND INSTALL 14" ROOF CURB FOR ALL RTUs. COORDINATE ROOF CURB INSTALLATION WITH ROOF CONSTRUCTION. 2. FACTORY MOUNTED DISCONNECT SWITCHES AND UNPOWERED GFI RECEPTACLES, AND SMOKE DETECTORS ARE FURNISHED BY THE RTU EQUIPMENT SUPPLIER. RTU EQUIPMENT SUPPLIER RESPONSIBLE FOR COORDINATING DISCONNECT AND GFI RECEPTACLE TYPES WITH ELECTRICAL POWER CHARACTERISTICS AVAILABLE AT THE PROJECT SITE. RTU EQUIPMENT SUPPLIER RESPONSIBLE FOR COORDINATING SMOKE DETECTOR TYPES AND INTERFACES WITH THE FIRE ALARM SYSTEM CHARACTERISTICS AVAILABLE AT THE PROJECT SITE. 3. INSTALL SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR DUCTS FOR ALL RTUs. SMOKE DETECTORS FURNISHED BY THE RTU EQUIPMENT SUPPLIER, INSTALLED BY THE MECHANICAL CONTRACTOR, AND WIRED BY THE ELECTRICAL CONTRACTOR. 4. PROVIDE ALL ROOF TOP UNITS WITH BAROMETRIC RELIEF DAMPERS, DISCHARGE AIR SENSING, OUTDOOR COIL HAIL GUARDS, AND FACTORY INSTALLED CLOGGED FILTER SWITCH. 5. PROVIDE ALL ROOF TOP UNITS WITH DRY BULB CONTROLLED ECONOMIZERS, AND HOT GAS REHEAT HUMIDITY CONTROLS WITH HUMIDITY SENSORS. 6. FURNISH AND INSTALL TRANE TRACER SUMMIT CONTROL PANEL, UNIT CONTROLLERS, ZONE TEMPERATURE SENSORS, AND HUMIDITY SENSORS TO CONTROL ALL RTUs. TRANE TRACER SUMMIT CONTROL SYSTEM SHALL BE COMPLETE WITH MODEM, OPERATING AND REMOTE ACCESS SOFTWARE, POWER CONTROL TRANSFORMERS, WIRING, ETC. ELECTRIC UNIT HEATER (EUH) SCHEDULE TAG LOCATION HEATING DATA FAN FILTER ELECTRICAL ENCLOSURE MANUFACTURER MODEL REMARKS KW BTUH EAT LAT STAGES CFM TYPE E.S.P. MOTOR TYPE THICKNESS EFF. VOLTS/PH/HZ AMPS HEIGHT WIDTH DEPTH (BASIS OF DESIGN) DB DB (IN. WC) (H.P.) (IN.) (IN.) (IN.) (IN.) EUH-01 VESTIBULE 101 2.00 6,826 68.0 109.9 1 150 PROP 0.00 - NONE -- -- 208/230/1/60 9.6 18-3/4 15-3/8 3-3/4 QMARK EFF4008 1, 2 NOTES: 1. PROVIDE REMOTE DOUBLE-POLE THERMOSTAT. 2. FULLY RECESSED CEILING MOUNT. PROVIDE T-BAR FRAME KIT FOR 2'x2' LAY IN CEILING.