HomeMy WebLinkAboutE-601 - ELECTRICAL SCHEDULES - CORE & SHELL275 Veterans Way
Carmel, Indiana 46032
317.810.1502
Client Information
Architect / Interiors / Structural Design
Construction Manager
Status
Revisions
Project Information
Design Team Member
275 Veterans Way
Carmel, Indiana 46032
317.344.8044
2/14/2025
E-601
ELECTRICAL
SCHEDULES -
CORE & SHELL
Ardalan on Main
ISSUED FOR BID AND
STATE PERMIT
Project Number 24062
331 W. Main Street
Carmel, IN 46032
1. LIGHTING SHALL COMPLY WITH THE FOLLOSING CODES AND STANDARDS: NATIONAL ELECTRIC CODE (NEC), NATIONAL FIRE PROTECTION AGENCY (NFPA), IESNA STANDARDS AND RECOMMENDED PRACTICES, AMERICAN NATIONAL
STANDARDS INSTITUTE (ANSI), INDIANA BUILDING CODE, ASHRAE 90.1-2007, CITY OF CARMEL EXTERIOR LIGHTING ORDINANCES.
2. BUILDING TO BE OCCUPIED 7 DAYS A WEEK/24 HOURS A DAY.
3. POLE MOUNT LIGHT FIXTURES ARE DUSK-TO-DAWN CONTROLLED VIA INTEGRAL PHOTOCELL. BUILDING MOUNTED LIGHT FIXTURES ARE DUSK-TO-DAWN CONTROLLED VIA BUILDING MOUNT PHOTOCELL.
NOTES:
LIGHTING FIXTURE SCHEDULE - EXTERIOR
Image UNIT ID BASE MANUFACTURER LAMP VOLTS WATTS UNITS LUMENS UNITS CCT LOCATION(S) MOUNT DESCRIPTION
S1 LITHONIA: DSXO LED-P1-30K-70CRI-BLC3-MVOLT-RPA-NLTAIR2PIRHN-EGSR-X
LED 120 V 33 W
/FIXTURE 3100 LM /FIXTURE 3000K
PARKING/DRIVE POLE
LIGHT FIXTURE W/ TYPE 3 DISTRIBUTION, BACKLIGHT CONTROL AND
EXTERNAL GLARE SHIELD ATOP A 12' POLE AND 6" CONCRETE BASE.
PROVIDE WITH PHOTOCELL ACCESSORY. ARCHITECT TO SELECT
FINISH.
S2 DIODELED: DI-12V-X-X-SL-AL-MC-ELV-X
LED 120 V 3 W
/FT 300 LM /FT 3000K
3RD FL ROOF CORNICE SURFACE
SURFACE MOUNT IP65 RATED TAPELIGHT AND CHANNEL. PROVIDE
AND INSTALL COMPONENTS AND HARDWARE NECESSARY FOR
MOUNTING, DRIVERS, CONNECTORS, ETC REQUIRED FOR PROPER
OPERATION. FIELD COORDINATE LOCATIONS FOR DRIVERS TO BE
ACCESSIBLE.
SC1 VISUAL COMFORT & CO.: 'DARLANA' #CHO 5085BZ
LED 120 V 32 W
/FIXTURE 2500 LM /FIXTURE 3000K
MAIN TENNANT
ENTRANCE WALL
EXTERIOR RATED 4-LAMP SUSPENDED DECORATIVE CHANDELIER.
17" W X 24"H. FINISH SELECTED BY ARCHITECT.
SC2 VISUAL COMFORT & CO.: 'DARLANA' #CHO 5085BZ
LED 120 V 32 W
/FIXTURE 2500 LM /FIXTURE 3000K
RETAIL/RESTAURANT
MAIN ENTRANCE WALL
EXTERIOR RATED 4-LAMP SUSPENDED DECORATIVE CHANDELIER.
12.5" W X 18.5"H. FINISH SELECTED BY ARCHITECT.
SC3 HALO: LTC406FS5B
LED 120 V 8 W
/FIXTURE 650 LM /FIXTURE 3000K
THIRD FLOOR SOFFIT RECESSED
4" DIA. CANLESS LED DOWNLIGHT WITH FLAT DIFFUSE LENS. WET
LOCATION LISTED.
SW1 VISUAL COMFORT & CO.: OL13201ANBZ - MEDIUM LANTERN
LED 120 V 24 W
/FIXTURE 1200 LM /FIXTURE 3000K
SECONDARY
ENTRANCES WALL
EXTERIOR RATED 3-LAMP DECORATIVE WALL SCONCE. 22.5"H X
10.5"W X 9.125"D. FINISH SELECTED BY ARCHITECT.
SW2 HI-LITE MFG CO: H-15114-X-HLA-X/34LED430WBCM
LED 120 V 34 W
/FIXTURE 3500 LM /FIXTURE 3000K
TENANT GARAGES WALL
EXTERIOR WALL MOUNT RLM STYLE FIXTURE WITH 14" DIA. CLASSIC
SHADE, 22" GOOSENECK ARM AND INTEGRATED LED. WET
LOCATION LISTED. ARCHITECT TO SELECT FINISH.
SW3 FC LIGHTING: FCSL2008-120-3K-CRI85-9L-SS-X
LED 120 V 15 W
/FIXTURE 900 LM /FIXTURE 3000K
RESTAURANT 1/2 WALL RECESSED
WALL
13"W X 4.5"H X 3.9"D STEP LIGHT WITH OPEN FACEPLATE. IP68
RATED.
SW4 LUMARK: ENC-SA1-A-730-1-T3-X-CBP-CEC
LED 120 V 21 W
/FIXTURE 2000 LM /FIXTURE 3000K
WATER RM EXT WALL
EXTERIOR WALL PACK WITH INTEGRATED COLD WEATHER
EMERGENCY BATTERY
SW5E LUMINAIRE LED: 'BLADE' BLD-72IN-NODIM-30W-30K-120-RALTBD-EMB310
LED 120 V 30 W
/FIXTURE 2000 LM /FIXTURE 3000K
EXTERIOR EGRESS
DOORS MULLION
6'L X 2.4"H X 5.6"D MULLION MOUNT WET LOCATION LISTED FIXTURE
WITH INTEGRATED EMERGENCY BATTERY. FIXTURE TO BE
NORMALLY OFF AND ONLY OPERATE WHEN NORMAL POWER IS
LOST.
NOTES:
LIGHTING CONTROL SEQUENCE
CONTROL
DESIGNATION SPACE/AREA TYPE CONTROL INTENT COMPONENTS EMERGENCY CEILING HEIGHT>12'-0" NOTES
LC01 BUILDING MOUNTED LIGHT FIXTURES
ON - DUSK TO DAWN
OFF - DAWN TO DUSK PHOTOCELL MOUN TED ON ROOF
UPON LOSS OF NORMAL POWER, EMERGENCY
FIXTURES FORCED TO FULL ON VIA INTEGRAL
EMERGENCY BATTERY.
TYPE 'SW1E' TO BE NORMALLY OFF AND OPERATE ONLY WHEN NORMAL POWER IS LOST.
LC02 PARKING/DRIVE POLE FIXTURES
ON - DUSK TO DAWN
OFF - DAWN TO DUSK PHOTOCELL INTEGRAL TO FIXTURE UPON LOSS OF NORMAL POWER, EMERGENCY
FIXTURES FORCED TO FULL ON VIA INVERTER.
1. PROVIDE LED RETRIFIT LAMPS FOR ANY FIXTURES WITH A SCREW IN SOCKET.
2. CONTRACTOR TO ISSUE AND RFI FOR CLARIFICATION IF LIGHTING PLANS AND ARCHITECTURAL REFLECTED CEILING PLANS DO NOT ALIGN.
3. VERIFY ATTIC STOCK WITH OWNER.
4. REFER TO ARCHITECTURAL AND INTERIOR PLANS FOR EXACT LOCATION AND MOUNTING HEIGHTS.
5. PROVIDE ALL NECESSARY POWER SUPPLIES, CONNECTORS, MOUNTING ACCESSORIES AND COMPONENTS INCLUDING LAMPS FOR ALL FIXTURES.
6. VERIFY COMPATIBILITY OF FIXTURES WITH LIGHTING CONTROLS.
7. ALL FIXTURES TO BE UL OR ETL LISTED.
NOTES:
LIGHTING FIXTURE SCHEDULE - DECORATIVE
Image UNIT ID BASE MANUFACTURER LAMP VOLTS WATTS UNITS LUMENS UNITS CCT LOCATION(S) MOUNT DESCRIPTION
D2 VISUAL COMFORT & CO.: 'MENIL' #MF-5175SB-CG
LED 120 V 85 W
/FIXTURE 10.200 LM /FIXTURE 2700K
LOBBY SUSPENDED
40" DIA. X DECORATIVE CHANDELIER WITH SOFT BRASS FINISH AND
GLASS RODS. FIXTURE SUSPENDED VIA DELICATE SOFT BRASS
FINISHED CHAINS AND (1) 6" CANOPY. DRIVER IS LOCATED IN THE
CANOPY. 0-10V DIM. ARCHITECT TO CONFIRM FINISH AND
MOUNTING HEIGHT.
D3 VISUAL COMFORT & CO.: 'FAY' #IKF-2110HAB-FG
LED 120 V 6 W
/FIXTURE 700 LM /FIXTURE 2700K
<varies> WALL
17.5"H DECORATIVE WALL SCONCE WITH ANTIQUE BRASS FINISH.
DRIVER LOCATED IN JUNCTION BOX. ARCHITECT TO CONFIRM
FINISH AND MOUNTING HEIGHT.
D4 REJUVINATION: 24" DIA. DECORATIVE SEMI-FLUSH MOUNT CONICAL DRUM
WITH AGED BRASS FINISH AND WHITE SHADE. PROVIDE WITH (3) A19-E26
LED LAMPS.(3) A19-E26
8W LED 120 V 30 W
/FIXTURE 2000 LM /FIXTURE 2700K
CORRIDORS SEMI-FLUSH
24" DIA. X 15"H DECORATIVE SEMI-FLUSH DRUM FIXTURE WITH
ANTIQUE BRASS FINISH AND WHITE SHADE. ARCHITECT TO
CONFIRM FINISH.
1. LIGHTING SHALL COMPLY WITH THE FOLLOSING CODES AND STANDARDS: NATIONAL ELECTRIC CODE (NEC), NATIONAL FIRE PROTECTION AGENCY (NFPA), IESNA STANDARDS AND RECOMMENDED PRACTICES, AMERICAN NATIONAL
STANDARDS INSTITUTE (ANSI), INDIANA BUILDING CODE, ASHRAE 90.1-2007, CITY OF CARMEL EXTERIOR LIGHTING ORDINANCES.
NOTES:
LIGHTING FIXTURE SCHEDULE - GENERAL
Image UNIT ID BASE MANUFACTURER LAMP VOLTS WATTS UNITS LUMENS UNITS CCT LOCATION(S) MOUNT DESCRIPTION
EM1 SURE-LITES: SEL-50-SD
LED 120 V 5 W
/FIXTURE /FIXTURE
GARAGE CORRIDOR WALL
WALL MOUNT THERMOPLASTIC EMERGENCY LIGHTING UNIT WITH (2)
ADJUSTABLE HEADS AND 50' APART MOUNTING
RECOMMENDATIONS.
L1 SPITZER: ERS-0609L-R-5CC
LED 120 V 20 W
/FIXTURE 950 LM /FIXTURE 3000K
GARAGE CORRIDORS SURFACE
6" DIA. SURFACE MOUNT PUCK. PROVIDE FIRE RATED JUNCTION
BOX.
L2 METALUX: 4-SNX-51SL-FDL-UNV-CC83-1
LED 120 V 51 W
/FIXTURE 5100 LM /FIXTURE 3500K
FUTURE TENANT
SPACES/EQUIP RMS
SUSPENDED/S
URFACE
4'L SUSPENDED/SURFACE MOUNT LENSED STRIP FIXTURE. PROVIDE
AIRCRAFT CABLE KIT FOR SUSPENSION MOUNTING WHERE
APPLICABLE.
L2E METALUX: 4-SNX-51SL-FDL-UNV-CC83-1-EL10W
LED 120 V 51 W
/FIXTURE 5100 LM /FIXTURE 2700K
FUTURE TENANT
SPACES/EQUIP RMS
SUSPENDED/S
URFACE
SAME AS TYPE 'L2' WITH INTEGRAL EMERGENCY BATTERY
L3 METALUX: 4VT3-SLC3-W-UNV
LED 120 V 51 W
/FIXTURE 5100 LM /FIXTURE 2700K
METER SPACE/WATER
ROOM
SUSPENDED/S
URFACE
4' SUSPENDED/SURFACE MOUNT VAPORTIGHT
L3E METALUX: 4VT3-SLC3-W-UNV-EL10W
LED 120 V 51 W
/FIXTURE 5100 LM /FIXTURE 2700K
METER SPACE/WATER
ROOM
SUSPENDED/S
URFACE
SAME AS TYPE 'L3' WITH INTEGRAL EMERGENCY BATTERY
L4 FOCAL POINT:
FLC3D-RO-SW-2100L-UNV-120-L11-LC3-RO-SW-2100L-27K-FL2-X-X
LED 120 V 25 W
/FIXTURE 2100 LM /FIXTURE 2700K
LOBBY/CORRIDORS RECESSED
3.5"" ROUND RECESSED DOWNLIGHT WITH MEDIUM DISTRIBUTION
AND 0-10V DIM. ARCHITECT TO SELECT BEZEL AND TRIM COLOR.
L4E FOCAL POINT:
FLC3D-RO-SW-2100L-UNV-120-L11-EMR-LC3-RO-SW-2100L-27K-FL2-X-X
LED 120 V 25 W
/FIXTURE 2100 LM /FIXTURE 2700K
LOBBY/CORRIDORS RECESSED
SAME AS TYPE 'L4' WITH INTEGRAL EMERGENCY BATTERY
W1E METALUX: 4-SWLED-56HL-LW-UNV-EL14W
LED 120 V 53 W
/FIXTURE 5600 LM /FIXTURE 2700K
STAIRWELLS WALL
4'L WALL MOUNT LINEAR FIXTURE WITH INTEGRAL EMERGENCY
BATTERY, OCC SENSING AND AUTO DIMMING TO 50% WHEN
UNOCCUPIED.
W2E METALUX: 4VT3-SLC3-W-UNV-EL10W
LED 120 V 51 W
/FIXTURE 5100 LM /FIXTURE 2700K
ELEVATOR SHAFT WALL
4' WALL MOUNT VAPORTIGHT
X1 SURE-LITES: APXH7-RG
LED 120 V 2 W
/FIXTURE /FIXTURE
GENERAL WALL
WALL MOUNT THERMOPLASTIC SINGLE FACE EXIT SIGN WITH WHITE
HOUSING AND SELECTABLE LETTER COLOR. PROVIDE WITH NI-CAD
BATTERY AND SELF-DIAGNOSTICS. REFER TO LIGHTING PLANS FOR
DIRECTIONAL ARROWS.
X2 SURE-LITES: EUX7-1-X-SD
LED 120 V 2 W
/FIXTURE /FIXTURE
LOBBY/CORRIDORS RECESSED
RECESSED CEILING MOUNT SINGLE FACE EDGE-LIT EXIT SIGN WITH
NI-CAD BATTERY AND SELF-DIAGNOSTICS. REFER TO LIGHTING
PLANS FOR DIRECTIONAL ARROWS. ARCHITECT TO SELECT
LETTERING COLOR.
X3 EVENLITE: SOVII-EM-R-1C-BK-PX-NA-SD
LED 120 V 2 W
/FIXTURE /FIXTURE
RETAIL/SHELL PENDANT
PENDANT MOUNT EDGE LIT SINGLE FACE EXIT SIGN WITH RED
LETTERS. ARCHITECT TO CONFIRM FINISH AND STEM LENGTH. RED
LETTERS, SELF DIAGNOSTICS.
#DESCRIPTION DATE
1 ASI-04 5/6/2025
1
1
1