HomeMy WebLinkAboutA421PIT LEVEL
808' - 7 5/8"
PIT ROOF
824' - 7 5/8"
PRECAST CONCRETE LINTEL
TYPE -D
TYPE - A2
PRECAST CONCRETE BAND
TYPE - A2
SUSPENDED ACOUSTIC
CEILING; REFER TO
SCHEDULE FOR TYPE
TYPE - A2
PREFINISHED ALUMINUM
COPING; NO EXPOSED
FASTENERS
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C. FULLY ADHERED EPDM ROOF SYSTEM; 2
LAYERS OF 1.5" RIGID INSULATION ON
STEEL DECK; ADDITIONAL TAPERED
INSULATION AS REQUIRED TO MAINTAIN
MINIMUM SLOPE 1/4" PER FT. REF. A251
FOR TAPERED INSULATION LOCATIONS
CONTINUE ROOF MEMBRANE UP
PARAPET WALL, TERMINATE
BENEATH COPING
CONCRETE FOUNDATION;
SEE F-SERIES DRWGS.
CONCRETE SLAB ON GRADE WITH
VAPOR BARRIER ON COMPACTED
GRANULAR BASE
X
9' - 0 3/8"
A602
4
A602
2
3' - 0"
A602
3
1' - 8 3/8"
16' - 0"
6" STEEL STUDS @ 16" O.C.
CLIPPED TO VERTICAL
STRUCTURAL STEEL WITH 1/2"
DENSDECK EXTERIOR SHEATHING
STEEL ROOF STRUCTURE; SEE
S-SERIES DRWGS.
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
PERIMETER FIRE
CONTAINMENT SYSTEM
PREFINISHED INSULATED
ALUMINUM PANEL INTEGRAL
WITH STOREFRONT SYSTEM
P-LAM WINDOW STOOL
PERIMETER DRAIN TILE;
SEE P-SERIES DRWGS.
FOR INVERTS
PERIMETER FOUNDATION
WATERPROOF MEMBRANE
WITH 2" RIGID FOUNDATION
INSULATION AND DRAINAGE
GRID
PRECAST CONCRETE SILL
VERTICAL STRUCTURAL STEEL FOR
PARAPET SUPPORT; SEE S-SERIES
DRAWINGS
3 5/8" 5' - 4 3/8" 3 5/8" 5' - 4 3/8" 3 5/8" 10 7/16"
TOP OF PARAPET SLOPES;
REFER TO A3 SERIES
DRWGS.
PRECAST CONCRETE BAND
2 1/2" STEEL STUDS @ 16" O.C.
ANCHORED TO CONCRETE
FOUNDATION WALL; VAPOR
BARRIER & 5/8" TYPE 'X' GYPSUM
SHEATHING
4 1/2"
GRANULAR FILL TO
ALLOW FOR DRAINAGE
TO DRAIN TILE
FINISHED GRADE; REFER
TO C-SERIES DRWGS.
1' - 0"
VARIES
CONTINUOUS THRU-WALL
EPDM FLASHING
MASONRY WALL AT JAMB
BEYOND
BUILDING COLUMN BEYOND
3 5/8"
A602
1
NOTE:
WHERE PRECAST BAND INTERSECTS WITH COPING ,
PRECAST TO BE NOTCHED AS REQUIRED SO COPING
REMAIN TIGHT AND SMOOTH WITHOUT DEFORMATION AT
THIS INTERSECTION.
FIRST FLOOR
817' - 7 5/8"
MAIN ROOF
873' - 1 5/8"
FIRST BALCONY
835' - 9 5/8"
SECOND BALCONY
851' - 4 5/8"
PIT ROOF
824' - 7 5/8"
L
TYPE - A2
CONCRETE SLAB ON GRADE WITH
VAPOR BARRIER ON COMPACTED
GRANULAR BASE
PERIMETER FOUNDATION
WATERPROOF MEMBRANE
2" RIGID PERIMETER FOUNDATION
INSULATION; 24" HORIZ., & VERT. TO
TOP OF FOOTING
A602
5
A602
6
A602
7
18' - 2" 15' - 7" 21' - 9" 5' - 2"
PREFINISHED ALUMINUM
COPING; NO EXPOSED
FASTENERS
TYPE - A1
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 1/2" DENSDECK
EXTERIOR SHEATHING & ROOF
MEMBRANE
PRECAST CONCRETE BAND
TYPE - A1
2" RIGID INSULATION;
BUILDING WRAP; 1/2"
EXTERIOR GYPSUM
SHEATHING & 6" STEEL
STUDS @ 16" O.C.; 6" BATT
INSULATION
PERIMETER FIRE
CONTAINMENT SYSTEM
FULLY ADHERED EPDM ROOF SYSTEM;
2 LAYERS OF 1.5" RIGID INSULATION ON
STEEL DECK; ADDITIONAL TAPERED
INSULATION AS REQUIRED TO MAINTAIN
MINIMUM SLOPE 1/4" PER FT. REF. A251
FOR TAPERED INSULATION LOCATIONS
CONTINUE ROOF MEMBRANE UP
PARAPET WALL, TERMINATE
BENEATH COPING
PRECAST CONCRETE BAND
STEEL ROOF STRUCTURE; SEE
S-SERIES DRWGS.
7' - 4 3/8" 3 5/8" 7' - 4 3/8" 3 5/8" 7' - 4 3/8" 7' - 4 3/8"
3 5/8" 3 5/8"
7' - 4 3/8" 3 5/8" 4' - 0"
2" RIGID INSULATION;
BUILDING WRAP; 1/2"
EXTERIOR GYPSUM
SHEATHING & 6" STEEL
STUDS @ 16" O.C.; 6" BATT
INSULATION
TYPE - A1
INTERIOR WALL WITH VAPOR
BARRIER AND 5/8" TYPE 'X'
GYPSUM SHEATHING
PRECAST CONCRETE BAND
PRECAST CONCRETE BAND
NOTE: BREAK-LINE; REFER
TO EXTERIOR BUILDING
ELEVATIONS FOR
LOCATIONS OF ALL
PRECAST CONCRETE
BANDS
NOTE: BREAK-LINE; REFER TO
EXTERIOR BUILDING ELEVATIONS
FOR LOCATIONS OF ALL PRECAST
CONCRETE BANDS
INTERIOR WALL WITH VAPOR
BARRIER AND 5/8" TYPE 'X'
GYPSUM SHEATHING
FINISHED GRADE; REFER
TO C-SERIES DRWGS.
SHELF ANGLE WITH
CONTINUOUS THRU-WALL
EPDM FLASHING
PRECAST CONCRETE BAND
TYPE - A1
PRECAST CONCRETE BAND
4' - 8" 3' - 0" 7' - 4 3/8" 3 5/8" 3 5/8" 7' - 4 3/8"
PERIMETER DRAIN TILE;
SEE P-SERIES DRWGS.
FOR INVERTS
GRANULAR FILL TO
ALLOW FOR DRAINAGE
TO DRAIN TILE
CONCRETE FOUNDATION; REFER TO
F-SERIES DRWGS.
SHELF ANGLE WITH
CONTINUOUS THRU-WALL
EPDM FLASHING
F4
FIRST FLOOR
817' - 7 5/8"
LEVEL-2 UPPER
LEVEL
830' - 7 5/8"
FIRST BALCONY
835' - 9 5/8"
PIT ROOF
824' - 7 5/8"
TYPE - B
TYPE - A-2
Z
A602
9
A602
10
A602
16
PREFINISHED ALUMINUM
COPING; NO EXPOSED
FASTENERS
CONCRETE SLAB ON GRADE WITH
VAPOR BARRIER ON COMPACTED
GRANULAR BASE
2" RIGID PERIMETER FOUNDATION
INSULATION; 24" HORIZ., & VERT. TO
TOP OF FOOTING
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
TYPE - B
7' - 0" 6' - 0" 5' - 2"
FULLY ADHERED EPDM ROOF SYSTEM; 2
LAYERS OF 1.5" RIGID INSULATION ON
STEEL DECK; ADDITIONAL TAPERED
INSULATION AS REQUIRED TO MAINTAIN
MINIMUM SLOPE 1/4" PER FT. REF. A251
FOR TAPERED INSULATION LOCATIONS
CONTINUE ROOF MEMBRANE UP
PARAPET WALL MIN. 48"; OVERLAP
WITH BUILDING WRAP
6" STEEL STUDS @ 16" O.C.
CLIPPED TO VERTICAL
STRUCTURAL STEEL WITH 1/2"
EXTERIOR GYPSUM SHEATHING,
BUILDING WRAP
STEEL ROOF STRUCTURE; SEE
S-SERIES DRWGS.
PERIMETER FIRE
CONTAINMENT SYSTEM
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.
4' - 8"
BUILDING COLUMN BEYOND
FINISHED GRADE; REFER
TO C-SERIES DRWGS.
VARIES. 13' - 10 1/SEE. 4" BUILDING ELEVATION
CONCRETE FOUNDATION; REFER TO
F-SERIES DRWGS.
TYPE - B
TYPE - B
PREFINISHED ALUMINUM
FLASHING; NO EXPOSED
FASTENERS
A602
8
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
No. Description Date
1/2" = 1'-0"
6/12/2008 4:55:58 PM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A421
WALL SECTIONS
NEW WORSHIP
CENTER
BR
KJ
06-10-2008
535-3581
A421 1/2" = 1'-0"
1 WALL SECTION
A421 1/2" = 1'-0"
2 WALL SECTION
A421 1/2" = 1'-0"
3 WALL SECTION
SECTION KEY NOTES
TYPE-A1
FACE BRICK
TYPE-A2
SPLIT FACED CONCRETE MASONRY UNITS
TYPE-B
CENTRIA EXPOSED FASTENER ECONOLAP 3/4" (HORIZONTAL)
(BASIS OF DESIGN)
TYPE-C
WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM
(EIFS)
TYPE-D
EXTERIOR ALUMINUM-FRAMED STOREFRONT SYSTEM
2 DESIGN DEVELOPMENT 01.18.08
3 CD 50% 03.14.08
4 PERMIT SET 04.25.08
EXTERIOR COLD FORMED METAL FRAMING GENERAL NOTES:
1. ALL LIGHT GAUGE FRAMING SHALL BE DESIGNED IN
ACCORDANCE WITH THE AMERICAN IRON AND STEEL
INSTITUTE, “SPECIFICATION FOR DESIGN OF COLD-
FORMED STEEL STRUCTURAL MEMBERS”
2. CONTRACTOR SHALL SUBMIT DESIGN CALCULATIONS AND
SHOP DRAWINGS, SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN INDIANA FOR ALL LIGHT GAUGE EXTERIOR
COLD FORMED FRAMING SHOWING SIZE AND GAUGE OF
ALL MEMBERS AND COMPLETE CONNECTION DESIGN.
3. ALL MEMBERS SHALL BE FORMED OF CORROSION-
RESISTANT STEEL, CONFORMING TO THE REQUIREMENTS
OF ASTM A653.
4. ALL STUDS SHALL BE HAVE A MINIMUM THICKNESS AND A
MAXIMUM SPACING AS REQUIRED BY THE DESIGN, EXCEPT
THAT THE THICKNESS SHALL NOT BE LESS THAN 18
GAUGE AND THE SPACING SHALL NOT EXCEED 16” ON
CENTER.
5. ALL STRUCTURAL MEMBERS SHALL BE GALVANIZED
MEETING ASTM A924 WITH A G60 COATING.
6. WELDS SHALL BE PERFORMED BY WELDERS QUALIFIED IN
ACCORDANCE WITH SECTION 6.0 OF THE AMERICAN
WELDING SOCIETY’S, “STRUCTURAL WELDING CODE-
SHEET METAL”, (AWS D1.3)
7. STUDS, HEADERS, RUNNERS AND STRAPS SHALL HAVE A
MINIMUM YIELD STRENGTH OF Fy = 33 ksi FOR 18 GAUGE
MEMBERS AND THINNER AND Fy = 50 ksi FOR 16 GAUGE
MEMBERS AND THICKER.
8. TORCH CUTTING OF HOLES OR MEMBERS IS NOT
PERMITTED.
5 ADDENDUM # 2 05.16.08
7 ADDENDUM # 4 05.29.08
9 ADDENDUM # 6 06.10.08
10 PERMIT SET 06.10.08