HomeMy WebLinkAboutA422FIRST FLOOR
817' - 7 5/8"
MAIN ROOF
873' - 1 5/8"
FIRST BALCONY
835' - 9 5/8"
SECOND BALCONY
851' - 4 5/8"
PIT ROOF
824' - 7 5/8"
H1.5 H2
PREFINISHED METAL COPING
TYPE B
TYPE C
PIT ROOF
22' - 0"
FIRST BALCONY
33' - 2"
SECOND BALCONY
48' - 9"
CATWALK 58' - 3"
MAIN ROOF
70' - 6"
LEVEL-1
15' - 0"
LEVEL-2 UPPER
LEVEL
28' - 0"
A602
12
PREFINISHED ALUMINUM
COPING; NO EXPOSED
FASTENERS
PERIMETER FIRE
CONTAINMENT SYSTEM
FULLY ADHERED EPDM ROOF SYSTEM; 2 LAYERS OF 1.5"
RIGID INSULATION ON STEEL DECK; ADDITIONAL TAPERED
INSULATION AS REQUIRED TO MAINTAIN MINIMUM SLOPE 1/4"
PER FT. REF. A251 FOR TAPERED INSULATION LOCATIONS
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
FULLY ADHERED EPDM ROOF
MEMBRANE ;1/4" DENSDECK
SHEATHING; 2" RIGID ROOF INSULATION
ON SLOPED STEEL DECK
FULLY ADHERED EPDM ROOF SYSTEM; 2 LAYERS OF
1.5" RIGID INSULATION ON STEEL DECK; ADDITIONAL
TAPERED INSULATION AS REQUIRED TO MAINTAIN
MINIMUM SLOPE 1/4" PER FT. REF. A251 FOR
TAPERED INSULATION LOCATIONS
CONTINUE ROOF MEMBRANE UP
PARAPET WALL, TERMINATE
2" RIGID INSULATION; BUILDING BENEATH COPING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 1/2" DENSDECK
EXTERIOR SHEATHING & ROOF
MEMBRANE
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
TYPE B
TYPE B
PERIMETER FIRE
CONTAINMENT SYSTEM
STEEL ROOF STRUCTURE; SEE
S-SERIES DRWGS.
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
26' - 9" 6' - 9 15/16"
21' - 9" 6' - 4 1/4"
FULLY ADHERED EPDM ROOF
SYSTEM; 2 LAYERS OF 1.5" RIGID
INSULATION ON STEEL DECK;
ADDITIONAL TAPERED
INSULATION AS REQUIRED TO
MAINTAIN MINIMUM SLOPE 1/4"
PER FT. REF. A251 FOR TAPERED
INSULATION LOCATIONS
STEEL ROOF STRUCTURE; SEE
S-SERIES DRWGS.
CONTINUE ROOF MEMBRANE UP
EXTERIOR WALL MIN. 48"; COVER
WITH EXTERIOR WALL FINISH
CONTINUE ROOF MEMBRANE UP
EXTERIOR WALL MIN. 48"; COVER
WITH EXTERIOR WALL FINISH
INTERIOR WALL,
SEE SCHEDULE
FOR TYPE
STEEL ROOF STRUCTURE; SEE
S-SERIES DRWGS.
CONCRETE ON STEEL DECK ON
STEEL FLOOR STRUCTURE; SEE
S-SERIES DRWGS.
TYPE C
CONTINUE ROOF MEMBRANE UP
PARAPET WALL, TERMINATE
BENEATH COPING
6" STEEL STUDS @ 16" O.C. CLIPPED
TO VERTICAL STRUCTURAL STEEL
WITH 1/2" DENSDECK EXTERIOR
SHEATHING
VERTICAL STRUCTURAL STEEL FOR
PARAPET SUPPORT; SEE S-SERIES
DRAWINGS
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.
F2
7' - 0" 11' - 2" 15' - 7"
VARIES. SEE. BUILDING ELEVATION
SIM.
A602
13
A602
14
A602
15
A603
1
A602
11
FIRST FLOOR
817' - 7 5/8"
PIT LEVEL
808' - 7 5/8"
FIRST BALCONY
835' - 9 5/8"
SECOND BALCONY
851' - 4 5/8"
Y Y2
7' - 2" 5' - 4"
TYPE B
PREFINISHED ALUMINUM
COPING; NO EXPOSED
FASTENERS
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 1/2" DENSDECK
EXTERIOR SHEATHING & ROOF
MEMBRANE
PERIMETER FIRE
CONTAINMENT SYSTEM
FULLY ADHERED EPDM
ROOF SYSTEM; 2 LAYERS
OF 1.5" RIGID INSULATION
ON STEEL DECK;
ADDITIONAL TAPERED
INSULATION AS
REQUIRED TO MAINTAIN
MINIMUM SLOPE 1/4" PER
FT. REF. A251 FOR
TAPERED INSULATION
LOCATIONS
CONTINUE ROOF
MEMBRANE UP
PARAPET WALL,
TERMINATE BENEATH
COPING
STEEL ROOF
STRUCTURE; SEE S-
SERIES DRWGS.
TYPE B
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
2" RIGID INSULATION; BUILDING
WRAP; 1/2" EXTERIOR GYPSUM
SHEATHING & 6" STEEL STUDS
@ 16" O.C.; 6" BATT INSULATION
& VAPOR BARRIER; 5/8" TYPE
'X' GYPSUM SHEATHING
TYPE B
TYPE A2
WALL BEYOND
HOLLOW METAL DOOR, PAINTED;
SEE SCHEDULE FOR TYPE
PERIMETER FIRE
CONTAINMENT SYSTEM
PERIMETER FIRE
CONTAINMENT SYSTEM
CONCRETE ON STEEL
DECK ON STEEL FLOOR
STRUCTURE; SEE S-
SERIES DRWGS.
CONCRETE ON STEEL
DECK ON STEEL FLOOR
STRUCTURE; SEE S-
SERIES DRWGS.
CONCRETE SLAB ON
GRADE WITH VAPOR
BARRIER ON
COMPACTED
GRANULAR BASE
2" RIGID PERIMETER
FOUNDATION
INSULATION; 24"
HORIZ., & VERT. TO
TOP OF FOOING
CONCRETE WALK, SLOPE AWAY
FROM BUILDING; REFER C-SERIES
DRWGS.
15' - 1" 6' - 8 11/16"
CONCRETE FOUNDATION;
REFER TO F-SERIES
DRWGS.
RETAINING WALL
BEYOND; REFER TO C-
SERIES DRWGS.
DOOR BEYOND. SEE
DOOR SCHEDULE.
S11B
GALV. STEEL ANGLE WITH
CONTINUOUS THRU-WALL
EPDM FLASHING
PREFINISHED ALUMINUM
FLASHING; NO EXPOSED
FASTENERS
A602
13 SIM.
SIM.
A602
11
A603
2
A603
3
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
No. Description Date
1/2" = 1'-0"
6/12/2008 5:02:02 PM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A422
WALL SECTIONS
NEW WORSHIP
CENTER
Checker
Author
06-10-2008
535-3581
A422 1/2" = 1'-0"
1 WALL SECTION
SECTION KEY NOTES
TYPE-A1
FACE BRICK
TYPE-A2
SPLIT FACED CONCRETE MASONRY
UNITS
TYPE-B
CENTRIA EXPOSED FASTENER
ECONOLAP 3/4" (HORIZONTAL) (BASIS
OF DESIGN)
TYPE-C
WATER-DRAINAGE EXTERIOR
INSULATION AND FINISH SYSTEM (EIFS)
TYPE-D
EXTERIOR ALUMINUM-FRAMED
STOREFRONT SYSTEM
2 DESIGN DEVELOPMENT 01.18.08
3 CD 50% 03.14.08
4 PERMIT SET 04.25.08
A422 1/2" = 1'-0"
2 WALL SECTION
EXTERIOR COLD FORMED METAL FRAMING
GENERAL NOTES:
1. ALL LIGHT GAUGE FRAMING SHALL
BE DESIGNED IN ACCORDANCE
WITH THE AMERICAN IRON AND
STEEL INSTITUTE, “SPECIFICATION
FOR DESIGN OF COLD- FORMED
STEEL STRUCTURAL MEMBERS”
2. CONTRACTOR SHALL SUBMIT DESIGN
CALCULATIONS AND SHOP
DRAWINGS, SEALED BY A
PROFESSIONAL ENGINEER
REGISTERED IN INDIANA FOR ALL
LIGHT GAUGE EXTERIOR COLD
FORMED FRAMING SHOWING SIZE
AND GAUGE OF ALL MEMBERS AND
COMPLETE CONNECTION DESIGN.
3. ALL MEMBERS SHALL BE FORMED
OF CORROSION- RESISTANT STEEL,
CONFORMING TO THE
REQUIREMENTS OF ASTM A653.
4. ALL STUDS SHALL BE HAVE A
MINIMUM THICKNESS AND A
MAXIMUM SPACING AS REQUIRED
BY THE DESIGN, EXCEPT THAT
THE THICKNESS SHALL NOT BE
LESS THAN 18 GAUGE AND THE
SPACING SHALL NOT EXCEED 16”
ON CENTER.
5. ALL STRUCTURAL MEMBERS SHALL
BE GALVANIZED MEETING ASTM
A924 WITH A G60 COATING.
6. WELDS SHALL BE PERFORMED BY
WELDERS QUALIFIED IN
ACCORDANCE WITH SECTION 6.0 OF
THE AMERICAN WELDING
SOCIETY’S, “STRUCTURAL WELDING
CODE-SHEET METAL”, (AWS D1.3)
7. STUDS, HEADERS, RUNNERS AND
STRAPS SHALL HAVE A MINIMUM
YIELD STRENGTH OF Fy = 33 ksi FOR
18 GAUGE MEMBERS AND THINNER
AND Fy = 50 ksi FOR 16 GAUGE
MEMBERS AND THICKER.
8. TORCH CUTTING OF HOLES OR
MEMBERS IS NOT PERMITTED.
GENERAL NOTES
KEY NOTES
5 ADDENDUM # 2 05.16.08
9 ADDENDUM # 6 06.10.08
10 PERMIT SET 06.10.08