HomeMy WebLinkAboutA601MAX. 12" O.C.
EPDM MEMBRANE
RIGID INSULATION
SEALANT
3"
MIN.*
CONTINUOUS ALUMINUM FLASHING
BONDING ADHESIVE
FASTENING PLATE
SPLICING CEMENT
LAP SEALANT
EPDM MEMBRANE
ROOF STRUCTURE
MECHANICAL
EQUIPMENT CURB
EQUIPMENT CURB
CLAMPING RING
EPDM MEMBRANE
WATER
CUT-OFF MASTIC
RIGID INSULATION
ROOF STRUCTURE
ROOF DRAIN
ROOF DRAIN
3" 8" 3"
6"
MEMBRANE
2x6 NON-COMBUSTIBLE
INSULATION
SEALANT
MEMBRANE
FASTENER
8"x12"x WALL DEPTH
STAINLESS STEEL
SCUPPER SLEEVE
EPDM
NON-REINFORCED
MEMBRANE
RIGID
SEALANT
WALL SYSTEM
WALL
WOOD NAILER
ROOF STRUCTURE
MEMBRANE
NON-REINFORCED
CONTINUE 4" PAST
SCUPPER OPENING
EPDM
PRIMARY SCUPPER
SYSTEM
S.S. PERIMETER
FRONT FLANGE
SEALANT
5" MIN.
WATER CUT-OFF MASTIC
TERMINATION BAR
BONDING ADHESIVE
LAP SEALANT
EPDM MEMBRANE
TERMINATION BAR ANCHOR
ALUMINUM COUNTERFLASHING
CONSECUTIVE LENGTHS OF TERMINATION BAR.
ALLOW 1/4" MIN. TO 1/2" MAX. (6 TO 13 mm) SPACING BETWEEN
(6 - 13 mm)
1/4" MIN. - 1/2" MAX.
EXTERIOR WALL SYSTEM
HORIZONTAL MEMBRANE TERMINATION
FLASHING ANCHOR
MIN.
3" (75 mm)
SPLICING CEMENT
LAP SEALANT
WATER CUT-OFF MASTIC
FLASHING
UNCURED ELASTOFORM
INSULATION
RIGID
EPDM MEMBRANE
TREATED 2x6 WOOD NAILER
ANY FLEXIBLE PENETRATION
"GOOSENECK"
ROOF STRUCTURE
FLEXIBLE PIPE (CONDUIT) FLASHING
RIGID INSULATION
NOTES:
1. TEMPERATURE OF METAL COLLAR MUST NOT EXCEED
180 F (82 C).
MIN.
3" (75 mm)
HEAT RESISTANT SEALANT
STAINLESS STEEL RAIN HOOD
TREATED 2x6 WOOD NAILER
EPDM MEMBRANE
METAL COLLAR
BOILER FLUE
1/2" MIN.
1" MIN.
UNCURED
ELASTOFORM FLASHING
LAP SEALANT
SPLICING CEMENT
(25 mm)
HOT PIPE FLASHING
PRECAST CONCRETE PANEL
TRANSITION BETWEEN
VERTICAL ROOFING TERMINATION
PER DETAIL 5/A2.42
HORIZONTAL ROOFING
TERMINATION PER
DETAIL 6/A2.42
ALUM. COUNTER
FLASHING (NOT INDICATED)
PRECAST PARAPET AND
METAL STUD PARAPET
EXPOSED PRECAST
CONCRETE PANEL
PER DETAIL 11/A2.42
COPING TERMINATION
TO ALIGN WITH FLASHING
AT COPING TERMINATION (DETAIL 11/A2.42)
PARAPET ROOFING TRANSITION
LAP SEALANT
ADHESIVE
BONDING
SURE-SEAL
MEMBRANE
EPDM ROOF
TIGHT
SEALED WATER-
FLASHING TO BE
METAL COUNTER-
MEMBER
STRUCTURAL
ERECTED AROUND
WOODEN CURB,
WELDED PLATE, WATERTIGHT
STRUCTURAL STEEL MEMBER
TERMINATION
ACCEPTABLE
SEALANT
WITH IN-SEAM
MAX. 12" O.C.
FASTENING PLATE
SEAM
ADHESIVE
BONDING
NAILER
WOOD
TREATED
RIGID
INSULATION
MEMBRANE
EPDM ROOF
STEEL COLUMN PENETRATION (@ SCREEN WALL)
NON-STAINING PRESSURE-SENSITIVE TAPE
SEALANT
WELD
TUBING WRAP
SQUARE
MIN. 1-1/2"
(40 TO 50 mm)
FASTENER AND
FASTENING PLATE, MAX.
12" O.C.
12" (300 mm) MAX.
ACCEPTABLE
INSULATION
6" WIDE
REINFORCED
MEMBRANE
CUT-EDGE
SEALANT
1-1/2" TO 2" 1" (25 mm) MIN. (APPROX.)
REINFORCED
MEMBRANE
SQUARE TUBING
WRAP OVERLAP
ENTIRE WIDTH OF
WELD
WRAP
AROUND PIPE
FASTENING PLATES
SQUARE TUBING
BELOW PIPE
WRAP FLANGE
WELD
MIN. 1-1/2"
ALUMINUM COLLAR
AND COLLAR STRAP
NOT SHOWN
NOTE: ALUM. COLLAR
TUBE STEEL PIPE PENETRATION @ SCREEN WALL
4" MIN.
CONTINOUS SEALANT
COPING CONTINUED UP WALL
ANCHOR COPING TO WALL SYSTEM
TYPICAL ALUMINUM COPING TERMINATION AT WALL
SYSTEM MIN. 4"
CONTINUOUS WOOD BLOCKING
CONTINOUS SEALANT
CONTINOUS COUNTER FLASHING
ANCHORDED TO WALL SYSTEM
ROOFING MASTIC
STAINLESS
STEEL
CLAMPING
RING
EPDM MEMBRANE
APPROX. 1/2"
WATER
CUT-OFF MASTIC
PRE-MOLDED PIPE SEAL
RIGID INSULATION
IN-SEAM
SPLICING SEALANT
CEMENT
1/2" TO 6-1/2"
LAP SEALANT
1/2"
(13 mm)
VENT PIPE FLASHING
WATER CUT-OFF MASTIC ROOF STRUCTURE
TERMINATION BAR
BONDING ADHESIVE
LAP SEALANT
EPDM MEMBRANE
TERMINATION BAR FASTENER
VERTICAL MEMBRANE TERMINATION
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
No. Description Date
1 : 6
6/13/2008 11:09:22 AM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A601
ROOF DETAILS
NEW WORSHIP
CENTER
Checker
Author
06-10-2008
535-3581
A601 1 : 6
1 ROOF DETAIL-EQUIPMENT CURB
A601 1 : 6
2 ROOF DETAIL-ROOF DRAIN
A601 1 : 6
3 ROOF DETAIL-PRIMARY SCUPPER
A601 1 : 6
5 ROOF DETAIL-HORIZONTAL MEMBRANE TERMINATION
A601 1 : 6
6 ROOF DETAIL-FLEXPIPE FLASHING
A601 1 : 6
7 ROOF DETAIL-HOTPIPE FLASHING
A601 1 : 6
8 ROOF DETAIL-PARAPET ROOFING TRANSITION
A601 1 : 6
9 ROOF DETAIL-STEEL COLUMN PENETRATION
A601 1 : 6
10 ROOF DETAIL-TUBE STEEL PIPE PENETRATION
A601 1 : 6
11
ROOF DETAIL-TYPICAL ALUMINUM COPING
TERMINATION AT WALL
A601 1 : 6
13 ROOF DETAIL-VENT PIPE FLASHING
A601 1 : 6
14 ROOF DETAIL-VERTICAL TERMINATION BAR
4 PERMIT SET 04.25.08
5 ADDENDUM #2 05.16.08
9 ADDENDUM # 6 06.10.08
10 PERMIT SET 06.10.08