DOUBLE STUD GYPBOARD WALL
2 LAYERS OF 5/8" GYPBOARD, STAGGERED
3" GLASSFIBER OR MINERAL WOOL BATT SOUND BLANKET (x2)
358ST USG STEEL STUD (x2)
COVE BASE
CONSTRUCTION NOTES
CONSTRUCTION DETAIL
BY A MINIMUM OF ONE STUD. SEAL IN ACCORDANCE WITH DETAIL A-2.
PIPE PENETRATIONS IN ACCORDANCE WITH DETAIL A-1.
NON-HARDENING ACOUSTICAL SEALANT BY U.S.G., TREMCO OR
SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS.
OUTLETS ON OPPOSITE SIDES OF PARTITIONS SHOULD BE SEPARATED
SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL DUCT & LARGE
STAGGER & SEAL ALL JOINTS ON MULTIPLE LAYER PARTITIONS.
SEAL AIR TIGHT AT FLOOR, SIDES & CEILING ON BOTH SIDES WITH
a =
b =
c =
d =
APPROVED EQUIVALENT.
SIDE VIEW
FLOOR
g
c
f
d
e =
a
AND BUTTED JOINTS, TAPE ALL LAYERS
2 LAYERS OF 5/8" GYPBOARD, STAGGERED
AND BUTTED JOINTS, TAPE ALL LAYERS
f = AIR GAP
TOP VIEW
c abbef
ISOLATED GWB CEILING
b
e
WALL SYSTEM SHOULD EXTEND FROM THE FLOOR TO BEYOND THE ISOLATED GWB CEILING.
THERE SHOULD BE NO CONNECTIONS BETWEEN THE STUDS OTHER THAN FLOOR
AND THE ISOLATED GWB CEILING.
g = ACOUSTICAL SEALANT
h
h = 2" PERIMETER ISOLATION JOINT
CONSTRUCTION DETAIL
ISOLATED GWB CEILING
A
B
E
D
C
G
F
FLOOR
TOP VIEW
A = 2 LAYERS OF 5/8" GYPBOARD, STAGGERED
AND BUTTED JOINTS, TAPE ALL LAYERS
B=3" GLASSFIBER OR MINERAL WOOL BATT
SOUND BLANKET
C=358ST USG STEEL STUD
D=COVE BASE
E=2 LAYERS OF 5/8" GYPBOARD, STAGGERED
AND BUTTED JOINTS, TAPE ALL LAYERS
F=2" PERIMETER ISOLATION JOINT
G=ACOUSTICAL SEALANT
CONSTRUCTION NOTES
1. SEAL AIR TIGHT AT FLOOR, SIDES & CEILING ON BOTH SIDES WITH
NON-HARDENING ACOUSTICAL SEALANT BY U.S.G., TREMCO OR
APPROVED EQUIVALENT.
2. STAGGER & SEAL ALL JOINTS ON MULTIPLE LAYER PARTITIONS.
3. SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL DUCT &
LARGE PIPE PENETRATIONS IN ACCORDANCE WITH DETAIL A-1.
4. OUTLETS ON OPPOSITE DIES OF PARTITIONS SHOULD BE
SEPARATED BY A MINIMUM OF ONE STUD. SEAL IN ACCORDANCE
WITH DETAIL A-2.
5. SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS.
6. WALL SYSTEM SHOULD EXTEND FROM THE FLOOR TO BEYOND
THE ISOLATED GWB CEILING.
7. THERE SHOULD BE NO CONNECTIONS BETWEEN THE STUDS OTHER THAN
FLOOR AND THE ISOLATED GWB CEILING.
CABB E
CONSTRUCTION DETAIL
AA BC FE
13-7/8"
STRUCTURE
D
B
C
A
A
E
D
CEILING
FLOOR
SIDE VIEW
TOP VIEW
A=5/8" GYPBOARD
B=3-5/8" METAL STUD, 24" O.C.
C=3-1/2" BATT INSULATION
D=ACOUSTICAL SEALANT
E=1" AIR SPACE
F=FOUNDATION WALL
CONSTRUCTION NOTES
1. SEAL AIR TIGHT AT FLOOR, SIDES & CEILING ON BOTH
SIDES WITH NON-HARDENING ACOUSTICAL SEALANT BY
U.S.C., TREMCO OR APPROVED EQUIVALENT.
2. STAGGER AND SEAL ALL JOINTS ON MULTIPLE LAYER
PARTITIONS.
3. SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL
DUCT & LARGE PIPE PENETRATIONS IN ACCORDANCE
WITH DETAIL A-1.
4. MAINTAIN CLEAR 1" AIRSPACE WITHOUT TIES, MORTAR OR
OTHER MATERIALS.
5. SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS IN
ACCORDANCE WITH DETAIL A-3.
CONSTRUCTION DETAIL
AA BC AA
6-1/8"
D
B
C
A
A
E
D
CEILING
FLOOR
TOP VIEW
SIDE VIEW
A=5/8" GYPBOARD
B=3-5/8" METAL STUD, 24" O.C.
C=3-5/8" BATT INSULATION
D=ACOUSTICAL SEALANT
E=COVE BASE
CONSTRUCTION NOTES
1. SEAL AIR TIGHT AT FLOOR, SIDES, & CEILING ON BOTH SIDES WITH
NON-HARDENING ACOUSTICAL SEALANT BY U.S.C., TREMCO OR
APPROVED EQUIVALENT.
2. STAGGER & SEAL ALL JOINTS ON MULTIPLE LAYER PARTITIONS.
3. SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL DUCT &
LARGE PIPE PENETRATIONS IN ACCORDANCE WITH DETAIL A-1.
4. OUTLETS ON OPPOSITE SIDES OF PARTITIONS SHOULD BE SEPARATED
BY MINIMUM OF ONE STUD. SEAL IN ACCORDANCE WITH DETAIL A-2.
5. SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS IN ACCORDANCE
WITH DETAIL A-3.
TEST: US GYPSUM CO. STC TEST #2-4400
CONSTRUCTION DETAIL
CABBE F
10 - 3/4"
ISOLATED GWB CEILING
TOP VIEW
A
B
E
F
D
C
G
FLOOR
SIDE VIEW
A=2 LAYERS OF 5/8" GYPBOARD, STAGGERED
AND BUTTED JOINTS, TAPE ALL LAYERS
B=3" GLASSFIBER OR MINERAL WOOL BATT
SOUND BLANKET (x2)
C=358ST USC STEEL STUD (x2)
D=COVE BASE
E=2 LAYERS OF 5/8" GYPBOARD, STAGGERED AND
BUTTED JOINTS, TAPE ALL LAYERS.
F=1" AIR GAP
G=ACOUSTICAL SEALANT
CONSTRUCTION NOTES
1. SEAL AIR TIGHT AT FLOOR, SIDES & CEILING ON BOTH SIDES WITH
NON-HARDENING ACOUSTICAL SEALANT BY U.S.G., TREMCO OR
APPROVED EQUIVALENT.
2. STAGGER & SEAL ALL JOINTS ON MULTIPLE LAYER PARTITIONS.
3. SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL DUCT &
LARGE PIPE PENETRATIONS IN ACCORDANCE WITH DETAIL A-1.
4. OUTLETS ON OPPOSITE SIDES OF PARTITIONS SHOULD BE SEPARATED
BY MINIMUM OF ONE STUD. SEAL IN ACCORDANCE WITH DETAIL A-2.
5. SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS.
6. WALL SYSTEM SHOULD EXTEND FROM THE FLOOR TO BEYOND THE ISOLATED GYPBOARD
CEILING.
7. THERE SHOULD BE NO CONNECTIONS BETWEEN THE STUDS OTHER THAN THE FLOOR AND
THE ISOLATED GWB CEILING.
CONSTRUCTION DETAIL
ISOLATED GWB CEILING
CAB E
A
H
B
E
I
D
C
G
F
SIDE VIEW
TOP VIEW
A=2 LAYERS OF 5/8" GYPBOARD, STAGGERED
AND BUTTED JOINTS, TAPE ALL LAYERS
B=3" GLASSFIBER OR MINERAL WOOL BATT
SOUND BLANKET
C=358ST USG STEEL STUD
D=COVE BASE
E=2 LAYERS OF 5/8" GYPBOARD, STAGGERED
AND BUTTED JOINTS, TAPE ALL LAYERS
F=2" PERIMETER ISOLATION JOINT
G=ACOUSTICAL SEALANT
H=MASON DNSB SWAY BRACE
I=WORSHIP CENTER FOUNDATION
CONSTRUCTION NOTES
1. SEAL AIR TIGHT AT FLOOR, SIDES & CEILING ON BOTH SIDES WITH
NON-HARDENING ACOUSTICAL SEALANT BY U.S.G., TREMCO OR
APPROVED EQUIVALENT.
2. STAGGER & SEAL ALL JOINTS ON MULTIPLE LAYER PARTITIONS.
3. SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL DUCT &
LARGE PIPE PENETRATIONS IN ACCORDANCE WITH DETAIL A-1.
4. OUTLETS ON OPPOSITE SIDES OF PARTITIONS SHOULD BE SEPARATED
BY MINIMUM OF ONE STUD. SEAL IN ACCORDANCE WITH DETAIL A-2.
5. SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS.
6. WALL SYSTEM SHOULD EXTEND FROM THE FLOOR TO BEYOND THE ISOLATED GYPBOARD
CEILING.
7. THERE SHOULD BE NO CONNECTIONS BETWEEN THE STUDS OTHER THAN THE FLOOR AND
THE ISOLATED GWB CEILING.
CONSTRUCTION DETAIL
CA B
ISOLATED GWB CEILING
A
B
D
C
E
FLOOR
TOP VIEW
A=1 LAYER OF 5/8" GYPBOARD
B=3" GLASSFIBER OR MINERAL WOOL BATT SOUND
BLANKET
C=358ST USG STEEL STUD
D=COVE BASE
E=ACOUSTICAL SEALANT
CONSTRUCTION NOTES
1. SEAL AIR TIGHT AT FLOOR, SIDES & CEILING ON BOTH SIDES WITH
NON-HARDENING ACOUSTICAL SEALANT BY U.S.G., TREMCO OR
APPROVED EQUIVALENT.
2. STAGGER & SEAL ALL JOINTS ON MULTIPLE LAYER PARTITIONS.
3. SEAL ALL CONDUIT & STRUCTURAL PENETRATIONS. SEAL DUCT &
LARGE PIPE PENETRATIONS IN ACCORDANCE WITH DETAIL A-1.
4. OUTLETS ON OPPOSITE SIDES OF PARTITIONS SHOULD BE SEPARATED
BY MINIMUM OF ONE STUD. SEAL IN ACCORDANCE WITH DETAIL A-2.
5. SEAL ALL WALL INTERSECTIONS AND CONTROL JOINTS.
6. WALL SYSTEM SHOULD EXTEND FROM THE FLOOR TO BEYOND THE ISOLATED GYPBOARD
CEILING.
7. THERE SHOULD BE NO CONNECTIONS BETWEEN THE STUDS OTHER THAN THE FLOOR AND
THE ISOLATED GWB CEILING.
SIDE VIEW
7 3/4"
CONSTRUCTION DETAILS
PIPE
CONSTRUCTION NOTES
A. GYPBOARD
B. BACKER ROD AND ACOUSTIC CAULK
C. BATT INSULATION
NOTE: HOLE IN GWB TO BE LARGER THAN PIPE BY 1" (1/2" GAP
AROUND PIPE). USE BACKER ROD AND ACOUSTICAL CAULK
AROUND PIPE (BOTH SIDES) TO CREATE AN AIRTIGHT SEAL.
C A
B
CONSTRUCTION DETAIL
E
B
A D
C
F
DO NOT USE THIS DETAIL IN FIRE RATED PARTITIONS
CONSTRUCTION NOTES
A. 12" MINIMUM (SINGLE STUD WALLS). 36" MIN (DOUBLE STUD WALLS).
CUT GYPBOARD TO ALLOW 1/4" MINIMUM OVERLAP BY FACE PLATE.
B. AT LEAST ONE STUD BETWEEN BOXES
C. FLEXIBLE CONDUIT PREFERRED
D. SCHEDULED PARTITION
E. SEAL VOIDS FROM OUTSIDE AND COVER BOX WITH 1/8" MINIMUM
LOWRY'S BOX PAD
F. CAULK ANY VOIDS BETWEEN GYPBOARD & BOX NOT COVERED BY
BOX SEALANT
CONSTRUCTION DETAILS
PARTITION INTERSECTION
PARTITION-WALL
INTERSECTION
CONTROL JOINT
C
BG
AD
D
H
A B C
H
D H
E
A
B
ACB D
CONSTRUCTION NOTES
A. GYPBOARD
B. METAL STUD
C. BATT INSULATION
D. ACOUSTICAL CAULK
E. JOINT REINFORCEMENT
G. FIBERGLASS PACKING (3#-6# DENSITY)
H. 24" MAXIMUM
CONSTRUCTION NOTES
GYPBOARD PARTITION MASONRY PARTITION
A
C
D
B
D
C
DO NOT USE THIS DETAIL IN FIRE RATED PARTITIONS
CONSTRUCITON NOTES
A. GYPBOARD WALL CONSTRUCTION
B. MASONRY WALL CONSTRUCTION
C. ACOUSTICAL SEALANT (ENTIRE PERIMETER, BOTH SIDES)
D. PACK WITH FIBERGLASS INSULATION (3# TO 6# DENSITY)
4"
2" FABRIC WRAPPED
PANEL
1/2" REVEAL, PAINT BLACK
EXPOSED PORTION OF
SCHEDULED PARTITION AT
REVEALS
1 1/2" H X 2 1/2"
SOLID WOOD
CONTINUOUS WAINSCOT
STAINED PLYWOOD
VENEER
RUBBER BASE
SCHEDULED PARTITION
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth Street
Cincinnati, Ohio 45202
w w w . c h a r c h i t e c t s . c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
900145
E
T
T
E
L
C
O
T
T
A
B
J
.
M
.
A
R
C
H
I
T
E
C
T
. .
NO
STATE OF
I
N
D
I
A
N
A
D
E
R
E
T
S
I
G
E
R
No. Description Date
As indicated
6/13/2008 11:11:42 AM
C:\!!!Bryan\Revit\NVCLC-bd.rvt
A703
PARTITION DETAILS
AND ACOUSTIC
DETAILS
NEW WORSHIP
CENTER
Checker
Author
06-10-2008
535-3581
A703 1" = 1'-0"
1 DTL- SINGLE STUD GYP. WALL ISOLATION PERIMETER
A703 1" = 1'-0"
2 DTL-COMPOSITE CONC./GYP WALL
A703 1" = 1'-0"
3 DTL-DOUBLE LAYER GYP. WALL, METAL STUD
A703 1" = 1'-0"
4 DTL-DOUBLE STUD GYP. WALL
A703 1" = 1'-0"
6 DTL-SINGLE STUD GYP. W/SWAY BRACES
A703 1" = 1'-0"
7 DTL-SINGLE STUD GYP. WALL
A703 3" = 1'-0"
8 DTL-CONDUIT OR PIPE THROUGH GYP.
A703 1" = 1'-0"
9 DTL-ELECTRICAL BACKBOX DETAIL
A703 3" = 1'-0"
10 DTL-GYPBOARD CONSTRUCTION DETAIL
A703 1" = 1'-0"
11 DTL-DUCT PENETRATION
5 ADDENDUM #2 05.16.08
A703 1 1/2" = 1'-0"
12 DTL- DETAIL AT BACK WALL OF WORSHIP CNTR.
7 ADDENDUM #4 05.30.08
A703 1" = 1'-0"
13 DTL-DOUBLE STUD GYP. WALL WITH ISOLATION JOINT
10 PERMIT SET 06.10.08