HomeMy WebLinkAboutE001 - LIGHTING FIXTURE SCHEDULE, LEGEND & INDEX OF DRAWINGSMOTORS, STARTERS, DISCONNECTS & CONTROLS
LIGHTING FIXTURES
LEGEND
NORMAL/EMERGENCY CIRCUIT SCHEDULE
GENERAL NOTES
WP/GF
J
H1
a
B1
b
LIGHTING FIXTURE; CAPITAL LETTER DENOTES FIXTURE TYPE. LOWER CASE LETTER
DENOTES SWITCHING ARRANGEMENT.
EXIT LIGHTING FIXTURE. COORDINATE EXIT SIGN ARROWS WITH ARCHITECTURAL
EGRESS PATHS - SEE ARCHITECTURAL DRAWINGS.
ELECTRICAL CONNECTION REQUIRED.
~
123 ROOM NUMBER.
2 DETAIL NOTE SYMBOL - APPLIES ONLY TO DETAIL ON WHICH NOTE IS SHOWN.
3 NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH NOTE IS SHOWN.
GROUND FAULT FEED THRU
GFFT
CIRCUIT
CKT
MOUNTING HEIGHT TO CENTERLINE OF ITEM UNLESS INDICATED OTHERWISE ON
MH DRAWINGS.
ABOVE FINISHED FLOOR - TO BOTTOM OF ITEM UNLESS INDICATED OTHERWISE ON
DRAWINGS
AFF
EXISTING
E
SURFACE MOUNTED
S
EMERGENCY
EM
WEATHERPROOF
WP
NOT IN ELECTRICAL CONTRACT
N.I.E.C.
EQUIPMENT SUPPLIER
E.S.
GENERAL CONTRACTOR
G.C.
FIRE PROTECTION CONTRACTOR
F.P.C.
PLUMBING CONTRACTOR
P.C.
HVAC CONTRACTOR
H.C.
ELECTRICAL CONTRACTOR
E.C.
FOUR-WAY WALL SWITCH (46" M.H.).
4
THREE-WAY WALL SWITCH (46" M.H.).
3
SINGLE POLE WALL SWITCH (46" M.H.).
MOTOR STARTER.
DISCONNECT SWITCH.
20A-125V WEATHERPROOF DUPLEX RECEPTACLE, NEMA 5-20R, WITH GROUND
FAULT CIRCUIT INTERRUPTER (18" M.H.), WITH TAYMAC #20310 STANDARD COVER,
VERTICAL MOUNT.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R. (46" M.H.).
20A-125V DOUBLE DUPLEX RECEPTACLE. NEMA 5-20R, (18" M.H.) TWO-GANG
ASSEMBLY.
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R (18" M.H.).
20A-125V SINGLE RECEPTACLE, NEMA 5-20R (18" M.H.).
JUNCTION BOX.
WIRE & CONDUIT IN OR BELOW FLOOR SLAB OR BELOW GRADE.
WIRE & CONDUIT IN WALL OR ABOVE CEILING.
EACH ARROWHEAD REPRESENTS ONE COMPLETE CIRCUIT; CAPITAL LETTER
DENOTES PANEL; NUMBER DENOTES CIRCUIT.
A-1&2
LIGHTING FIXTURE ON NIGHT LIGHT OR EMERGENCY CIRCUIT.
H1
B1
V VALVE SUPERVISORY SWITCH.
W WATER FLOW SWITCH.
S DUCT MOUNTED SMOKE DETECTOR (S/SUPPLY, R/RETURN).
S/R
H CEILING MOUNTED HEAT DETECTOR.
S CEILING MOUNTED SMOKE DETECTOR.
F FIRE ALARM SENDING STATION (46" M.H.).
FIRE ALARM SIGNALING LIGHT (80" A.F.F.), (# WHEN SHOWN INDICATES CANDELA
RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL BE RATED
15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
L
15
BE RATED 15 CANDELA IN CORRIDORS AND 30 CANDELA FOR ALL OTHER LOCATIONS.
CANDELA RATING OF STROBE. WHEN A # IS NOT SHOWN, THE STROBE SHALL
F FIRE ALARM HORN & SIGNAL LIGHT (80" A.F.F.), (# WHEN SHOWN INDICATES
15
BUSHED CONDUIT OUT ABOVE ACCESSIBLE CEILING.
"W" INDICATES 48" M.H., "P" INDICATES 48" M.H.). STUB AN EMPTY 3/4"
W TELEPHONE OUTLET (18" M.H. EXCEPT WHEN SUBSCRIPT LETTER IS SHOWN,
48" M.H.). SINGLE GANG OUTLET BOX WITH BLANK COVERPLATE. STUB AN
EMPTY 3/4" BUSHED CONDUIT OUT ABOVE ACCESSIBLE CEILING.
DATA OUTLET (18"M.H. EXCEPT WHEN SUBSCRIPT "W" IS SHOWN, MOUNT AT
CIRCUIT BREAKER PANEL, SURFACE MOUNTED.
CIRCUIT BREAKER PANEL, FLUSH MOUNTED.
ELECTRIC MOTOR.
COMBINATION MOTOR STARTER AND DISCONNECT SWITCH.
SCHEDULE NOTES:
1
2
3
4
PROVIDE MOUNTING AND DIRECTIONAL ARROWS PER PLAN. COORDINATE EGRESS PATH WITH ARCHITECTURAL DRAWINGS PRIOR TO ORDERING ANY FIXTURES.
MOUNTING HEIGHT 24'-0".
MOUNTING HEIGHT 12'-0".
SEE ALSO "GALLEGOS" LIGHTING SHEETS FOR LIGHT FIXTURE SCHEDULES.
SCHEDULE NOTES:
1 BUSSMANN POWER MODULE SWITCH. SIZE PER MANUFACTURER'S RECOMMENDATIONS.
2 FUSED DISCONNECT TO BE INSTALLED PER NEC-695 REQUIREMENTS.
3 CONTROL PANEL BY STAGE LIFT SUPPLIER. E.C. TO COORDINATE WITH SUPPLIER FOR ALL ELECTRICAL REQUIREMENTS PRIOR TO ROUGH-IN.
PROVIDE (2) DEDICATED 120V, 20A CKTS TO MCP-1 AND MCP-2. SEE SINGLE-LINE DIAGRAM IN SHEET # TP1.0 FOR DETAILS.
4 CONTROL PANEL FOR RIGGING SYSTEM BY SYSTEM SUPPLIER. E.C. TO COORDINATE FOR ALL ELECTRICAL REQUIREMENTS WITH RIGGING
SYSTEM SUPPLIER PRIOR TO ROUGH-IN. PROVIDE (10) 120V, 20A CIRCUITS PER MANUFACTURER'S REQUIREMENTS. SEE SINGLE-LINE
DIAGRAM IN SHEET # TR1.0 FOR DETAILS.
5 WEATHER PROOF DISCONNECT REQUIRED.
6 EC SHALL WIRE FAN THROUGH LINE VOLTAGE THERMOSTAT. HC SHALL FURNISH THERMOSTAT TO E.C.
A CONVEYANCE / CONDUIT INSTALLATION - SHALL MEET ALL ANSI/NFPA 70 (NATIONAL ELECTRICAL CODE) REQUIREMENTS.
B ALL CONDUCTORS WILL BE COPPER IN CONDUIT. INSULATION SHALL BE RATED FOR 600V.
C ALL WORK WILL BE DONE IN ACCORDANCE WITH THE NEC.
D ALL 20 AMP. 120 VOLT POWER CIRCUITS SHALL CONSIST OF #12 AWG CONDUCTORS UNLESS INDICATED OTHERWISE.
E CONDUITS OF DIFFERENT MATERIALS SHALL NOT BE MIXED INDISCRIMINATELY IN THE SAME SYSTEM.
F MAINTAIN 16" SPACING BETWEEN RECEPTACLES AND OTHER RECESSED OUTLETS EVEN WHEN
LOCATED ON OPPOSITE SIDES OF PARTITION TO ELIMINATE SOUND TRANSMISSION FROM ONE SPACE
TO THE OTHER. CENTER DEVICES WHERE APPLICABLE IN EACH WALL SECTION.
G NO SECTION OF A TELECOMMUNICATION CONDUIT SYSTEM SHALL BE LONGER THAN 100' OR CONTAIN
MORE THAN TWO 90° BENDS, OR 180° TOTAL OF BENDS AND ELEVATION CHANGES, BETWEEN PULL
POINTS OR PULL BOXES. FOR CONDUIT RUNS THAT TOTAL MORE THAN 100' IN LENGTH, INSERT PULL
BOXES SO THAT NO SEGMENT EXCEEDS THE 100' LIMIT.
H BENDS IN TELECOMMUNICATIONS CONDUITS SHALL BE LONG SWEEPS WITH A RADIUS OF 10 TIMES THE
INSIDE DIAMETER OF THE CONDUIT.
I ALL METALLIC RACEWAYS (I.E., CONDUITS AND CABLE TRAY SYSTEMS) SHALL BE CONNECTED TO THE
EXPANDED BUILDING GROUND LOOP, DIRECTLY TO THE COMMUNICATIONS RESOURCE ROOMS BUSBAR
OR VIA INTERCONNECTION OF CONVEYANCE ALREADY CONNECTED TO BUSBAR.
J FIRE STOPPING OF CONVEYANCE MUST MEET ALL APPLICABLE BUILDING CODE REQUIREMENTS.
K CONFIRM DATA AND COMMUNICATION DEVICE LOCATIONS WITH ARCHITECT PRIOR TO ROUGH-IN.
L REFER TO ARCHITECTURAL SHEETS FOR EXACT LOCATION OF TACKBOARDS, MARKER BOARDS,
CASEWORK, DESKS, ETC.- CONFIRM LOCATION OF ALL ELECTRICAL DEVICES WITH ARCHITECT PRIOR
TO ROUGH-IN.
M ALL EXIT SIGNAGE SHALL BE WIRED AHEAD OF LOCAL SWITCHING.
N REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF LIGHTS, DIFFUSERS, ETC.
O ALL THEATRICAL LIGHITNG REQUIREMENTS SHALL BE COORDINATED WITH THE THEATRICAL LIGHTING
CONSULTANT PRIOR TO ANY WORK BEING PERFORMED.
P VERIFY EXACT LOCATION OF ALL LIGHTING FIXTURES WITH MECHANICAL DUCTS AND SPRINKLER PIPES
AND HEADS BEFORE ROUGH-IN TO PREVENT CONFLICTS.
Q EXACT LOCATION OF ALL DEVICES SERVING EQUIPMENT TO BE VERIFIED AT SITE WITH
ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN.
R ALL EMPTY CONDUITS SHALL BE INSTALLED WITH PULL WIRE PER SPECIFICATIONS.
S ALL AUDIO / VIDEO DEVICES AND EQUIPMENT LOCATIONS AND REQUIREMENTS SHALL BE
COORDINATED WITH THE AUDIO / VIDEO CONTRACTOR PRIOR TO ANY WORKING BEING PERFORMED.
T ALL DEVICES INSTALLED IN / ON WALLS, SHALL BE DONE SO THAT THEY ARE AT EQUAL ELEVATIONS.
(I.E. DEVICES INSTALLED AT 18" M.H. SHALL ALL BE AT 18" M.H., ALL DEVICES INSTALLED AT 46" M.H.
SHALL BE INSTALLED AT 46" M.H.)
MOTOR
120V-1PH
CHARACTERISTICS
NAMEPLATE
CIRCUIT NO.
NUMBER
FLA
407/450
HP
KVA
OR
MOTOR
LOCATION
-
208V-3PH
208V-1PH
-
MAGNETIC
MANUAL
NEMA SIZE
LOCATION TYPE
AC DRIVES (VFD)
MOTOR O/L
BUILT-IN
2-SPEED
2-WINDING
MOTOR CONT.
NEAR MOTOR
SEE NOTE
TYPE
STARTER
FURNISHED BY
ROOM NUMBER
SEE NOTE
PANEL
EQUIP. CONT.
CENTER
STARTER
MANUAL
DISC. SWITCH
NEAR MOTOR
OR BREAKER
FEEDER SW.
RECEPTACLE
PANELBOARD
PANEL
EQUIP. CONT.
CENTER
MOTOR CONT.
DISCONNECT MEANS
LOCATION
FURNISHED BY
INTEGRAL WITH
MOTOR NO. BY E.C.
INTERLOCK WITH
FURNISHED BY
SEE NOTE
EQUIPMENT
STARTER
MANUAL AT
CONTROL
GRD. SIZE
WIRE SIZE
CONDUCTORS
NUMBER OF
SEE NOTE
SEE NOTE
CONDUIT SIZE
FEEDER
FIXTURE SYMBOL
CAT. NO.
G.E. LAMP
WATTS/LAMP
INCAN.
FLUOR.
FIXTURE VOLTAGE
H.I.D.
QUANTITY
LAMPS
CS-CEIL. SURFACE
BRONZE
C--CHAIN MTD.
STANDARD
SEE NOTE
ALUMINUM
BLACK
WHITE
UC-UNDER CAB.
TRIM COLOR
WM-WALL MTD.
SM-STEM MTD.
R--RECESSED
S--SURFACE
MOUNTING
SEE NOTE
DEPTH
LENGTH
WIDTH
DIAMETER OR
SIZE (IN.)
MANUFACTURER
& CATALOG NO.
OTHER ACCEPTABLE
MANUCATURES MEDIA
DIFFUSING
X1 LED INCLUDED 120 DUAL-LITE # LES SERIES MCPHILBEN, SURE-LITE
CLEAR MIRROR FACE W/RED
STENCIL LETTERS
4 PER PLAN 14.38 9.88 1.38 1
X2 LED 7 INCLUDED 120 DUAL-LITE # LT SERIES MCPHILBEN, SURE-LITE PER PLAN 14.38 9.88 1.38 1
RTU-1 MDP3-4 ROOF TOP UNIT #1
RTU-2 MDP3-5
RTU-3 MDP3-6 425/450
RTU-4 MDP3-7 165/225
ROOF
H-1A RP2-2 BOILER #1 18FLA
HWP-1 - HOT WATER PUMP 1 1.5HP
HWP-2 - HOT WATER PUMP 2 1.5HP
CP-1 - H.W. COIL PUMP 1 3/4HP
CP-2 -
CP-3 -
CP-4 -
AC-1 (15A MOCP) AIR CONDITIONER 1 8.0FLA
HC SEE MAIN
SWBD. "MDP3"
3 12 12 .75 -
-
-
-
-
AC-2 (15A MOCP) AIR CONDITIONER 2 8.0FLA -
CU-1 (40A MOCP) CONDENSING UNIT 1 20FLA 5
CU-2 (40A MOCP) CONDENSING UNIT 2 20FLA
EF-1 - EXHAUST FAN 1 (1/4HP) -
EF-2 - EXHAUST FAN 2 (1/4HP) -
EF-3 - EXHAUST FAN 3 (1/4HP) EC -
EF-4 - EXHAUST FAN 4 (1/6HP) EC -
EF-5 - EXHAUST FAN 5 (1/4HP) -
ELEV ELEVATOR 30HP EC
FP FIRE PUMP 30HP EC
1
2
SL STAGE LIFT 10HP 3
H-1B BOILER #2 18FLA
3/4HP
1HP
3/4HP
HWP-3 HOT WATER PUMP 3
HWP-4 HOT WATER PUMP 4
7.5HP
7.5HP
AC-3
AC-4
(45A MOCP)
(45A MOCP)
AIR CONDITIONER 3
AIR CONDITIONER 4
33.5FLA
33.5FLA
CU-3
CU-4
CONDENSING UNIT 3
CONDENSING UNIT 4
19.3FLA
19.3FLA
(40A MOCP)
(40A MOCP)
EF-6
EF-7
EXHAUST FAN 6
EXHAUST FAN 7
(1/4HP)
(1/6HP)
ROOF TOP UNIT #2
ROOF TOP UNIT #3
ROOF TOP UNIT #4
204/250
381/400
RP2-3
JP JOCKEY PUMP 3/4HP
AV
20A-125V DUPLEX RECEPTACLE, NEMA 5-20R, WITH ISOLATED GROUND (18" M.H.).
H1 1 250 T4 LAMP 120 GOTHAM # CQ11-250-W-6AR-WLP-STEM-DBL COOPER, KIRLIN
H2 1 500 T4 LAMP 120 COOPER, KIRLIN
H3 1 400 T4 LAMP 120 COOPER, KIRLIN
A 1 400 HPS 120 LSI # HFR5400HPS-120-F 2
B 1 125 MH 120 LSI # HFSH3175MH-120-F 3
GOTHAM # CQ11-250-W-6AR-WLP-STEM-DBL
GOTHAM # CQ11-250-W-6AR-WLP-STEM-DBL
DP2-1
DP2-2
DP2-4
DP2-8
DP2-9
DP2-19
DP2-21
DP2-22
DP2-23
EP-34
EP-35
EP-36
EP-37
EP-38
EP-39
EP-40
EP-41
EP-42
C 1 100 MH 120 GOTHAM # LAH-100M-12FW-FFL-120 COOPER, KIRLIN
WHITE FACE W/RED
STENCIL LETTERS
4
GENERAL LEGEND NOTES:
A
B
SEE A/V DRAWINGS FOR LEGEND ON A/V DEVICES.
SEE THEATRICAL LIGHTING DRAWINGS FOR LEGEND ON THEATRICAL LIGHTING FIXTURES.
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
EC
EC
PC
PC
HC
HC
HC
HC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
HC
HC
HC
HC
HC
EC
EC
EC
EC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
HC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
EC
ROOF
ROOF
ROOF
MECHANICAL ROOM
MECHANICAL ROOM
MECHANICAL ROOM
MECHANICAL ROOM
MECHANICAL ROOM
MECHANICAL ROOM
SERVE RTU-1 COIL
SERVE RTU-2 COIL
SERVE RTU-3 COIL
SERVE RTU-4 COIL
PROJECTION ROOM
PROJECTION ROOM
A/V RACK
SERVER ROOM
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ROOF
ELEV. EQUIP. ROOM
FIRE PUMP ROOM
MECHANICAL ROOM
JAN. CLOSET 109
6KW
6KW
DWH1
DWH2
DOM. WATER HEATER 1
DOM. WATER HEATER 2
3 12 12 .75
3 12 12 .75
3 12 12 .75
3 12 12 .75
3 12 12 .75
2 6 8 1
2 6 8 1
3 10 10 .75
3 10 10 .75
3 8 10 .75
3 8 10 .75
5
5
5
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
2 12 12 .75
3 1 6 1.5
3 1 6 1.5
3 12 12 .75
3 8 10 1.5
3 10 10 .75
3 10 10 .75
6
6
6
6
H.W. COIL PUMP 2
H.W. COIL PUMP 3
H.W. COIL PUMP 4
Date: Scale
Drawn By
Checked By
Project
Number
ARCHITECTURE
PLANNING
INTERIOR DESIGN
STRUCTURAL ENGINEERING
424 East Fourth
Street
Cincinnati, w w w . c h a r c h Ohio i t e c t s . 45202 c o m
tel: 513/241/4474 fax: 513/241/0081
ISSUANCES
COMPUTER FILE
1400 West Dorothy Lane
Dayton, Ohio 45409-1310
Tel: (937) 224-0861
Fax: (937) 224-5777
3417 South Sherman Drive
Beech Grove, IN 46107
Tel: (317) 780-1555
Fax: (317) 780-6525
750 North Orleans, Suite 400
Chicago, IL 60610
Tel: (312) 944-8230
Fax: (312) 944-8297
117 East Washington
Street, Suite 200
Indianapolis, IN 46204
Tel: (317) 637-2222
Fax: (317) 637-2260
1137 West Taylor St.
Suite 316
Chicago, IL 60607
Tel: (312) 224-8460
Fax: (312) 224-8961
1025 N.Watery Ln.
Brigham City, UT 84302
TEL: (453) 723-5000
FAX: (453) 538-5506
6622 Kingspointe
Parkway
Orlando, FL 33819
Tel: (407) 816-9400
Fax: (407) 816-9300
1 SCHEMATIC DESIGN 10.18.07
2 DESIGN DEVELOPMENT 01.18.08
3 CD 50% 03.14.08
4 PERMIT SET 04.25.08
5 ADDENDUM #2 05.16.08
No. Description Date
6 ADDENDUM #3 05.22.08
7 ADDENDUM #5 06.04.08
8 PERMIT SET 06.10.08
6/10/2008 1:00:11 PM
C:\Drawings\2007-06019-Central-Local.rvt
E001
LIGHTING FIXTURE
SCHEDULE, LEGEND &
INDEX OF DRAWINGS
New Worship
Center
Checker
Author
05-22-08
2007-06019
ELECTRICAL DRAWING INDEX
SHEET DESCRIPTION
E001 LIGHTING FIXTURE SCHEDULE, LEGEND & INDEX OF DRAWINGS
E002 SITE LIGHTING AND UTILITY PLAN
E003 ELECTRICAL DETAILS
E100 GATHERING CENTER - DEMO
E200 PIT LEVEL - LIGHTING PLAN
E201 FIRST FLOOR - LIGHTING PLAN
E202 BALCONY ONE - LIGHTING PLAN
E203 BALCONY TWO - LIGHTING PLAN
E205 CATWALK - NEW WORK - LIGHTING
E206 ROOF LIGHTING
E300 PIT LEVEL - POWER PLAN
E301 FIRST FLOOR - POWER PLAN
E301-A FIRST FLOOR - POWER PLAN - ALTERNATE
E302 BALCONY ONE - POWER PLAN
E302-A BALCONY ONE - POWER PLAN - ALTERNATE
E303 BALCONY TWO - POWER PLAN
E305 CATWALK-POWER PLAN
E400 SINGLE-LINE DISTRIBUTION DIAGRAM
E401 PANELBOARD SCHEDULES
E402 PANELBOARD SCHEDULES
E403 PANELBOARD SCHEDULES